50% 1

Pumped down 6 individual high-wall split systems to make way for a new Daikin Heat Recovery 3 Pipe VRV unit. This was a lot of fun to do. I’m excited I get to work on more of these complete units moving forward.
I also have an Instagram page where I post other content: @hvacr_tech_aust
For any enquirers email me at: hvacrtechaustralia@gmail.com

Опубликовано:

 

19 авг 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 27   
@lwilliams3285
@lwilliams3285 Год назад
Shouldn't ever use b presses on annealed copper, in fact I'm sure it says not to use them on the data sheets, it compresses too easily and never seals right. I only use on hard drawn, but you can't go past soldering. Awesome to see more Aussies techs doing videos. It's great to bounce ideas and knowledge off each other.
@hvacraustralia
@hvacraustralia Год назад
I’ve been meaning to look into the data sheets for them. It’s seems they will become more prevalent going forward, but I’m the same with soldering. Thanks mate, the interactions with people on here have been great. I’ve learnt good information from the comments. Like you said, it’s great to bounce information and ideas off each other.
@HVACR_VINYLS
@HVACR_VINYLS Год назад
Huge, you’ll be VRV king soon
@hvacraustralia
@hvacraustralia Год назад
😂 thanks mate. Long way to go!
@HVACR_VINYLS
@HVACR_VINYLS Год назад
@@hvacraustralia it’s a hard game. I can help tho 💪
@hvacraustralia
@hvacraustralia Год назад
Thanks mate! Appreciate it.
@EverythingHVACR
@EverythingHVACR Год назад
Nice job! Keep doing what you do, your channel will continue to grow, great content. You should look in to the fieldpiece vacuum pump, I love mine and makes oil change much easier without having to stop your vacuum.
@hvacraustralia
@hvacraustralia Год назад
Thanks mate, love the feedback! I used the fieldpiece vacuum pump with my last company and absolutely loved it. My new company provides the CPS one but I’m considering just purchasing my own. Either the Fieldpiece of the Appion. Love the oil change one the fly, so much better.
@Cre666in666
@Cre666in666 Год назад
I've always been told/advised never to B-press soft drawn. A lot of installs 3 years old or less I've seen leaks with soft drawn. Good video too!
@hvacraustralia
@hvacraustralia Год назад
Thanks mate. That’s interesting. I’ve never had the opportunity to do an install with them, I just always follow up after it’s all done. I need to do more research into it. Have you used them much?
@Cre666in666
@Cre666in666 Год назад
@@hvacraustralia I don't do a lot of installs but I have used the Rothenberger one a few times on some install jobs, its very nice for the fact that you can put piperuns up way quicker than soldering but I still feel more comfortable and confident inspecting a weld I have done than a b-press
@hvacraustralia
@hvacraustralia Год назад
I’m the same. I haven’t used it for installs and prefer inspecting welds. Maybe one day I’ll get to test it and bit more.
@stueyknuxx
@stueyknuxx Год назад
conex bänninger (b press fitting manufacturer) do state in their tech data that you can b press on soft drawn copper. I’ve heard same thing from people saying to not do it. But then again I’ve seen plenty of soft drawn copper b pressed that have been installedfor years with no issues.
@joelmcdermott7129
@joelmcdermott7129 Год назад
Hey Mate, for an interesting bit of reading get a copy of ASHRAE RP1808. They did a small sample test between different fitting types and suggested when properly installed there was a 1% failure rate. They probably needed to sample more though. From an engineers perspective I would only be specifying them where the risk of open flame is unacceptable, e.g. heritage wooden structure, etc.
@joelmcdermott7129
@joelmcdermott7129 Год назад
Their tests did show brazing has its own failures when done by inexperienced installers, but atleast with brazing its easier to see the potential mistake and rectify.
@hvacraustralia
@hvacraustralia Год назад
That’s interesting. They’re one of those things that I haven’t used for installs. I’m so used to brazing so I just do that. I’ll have to look into them more. The benefits are definitely there, especially for places like this one where they have fire alarms all over the place.
@hvacraustralia
@hvacraustralia Год назад
I don’t get the opportunity to do many installs these days either, so there’s that too 😂
@azim_skyz8741
@azim_skyz8741 3 месяца назад
Hi im aircond student, i found this video, i really like this but i need to know how to service vrv like troubleshoot and more, i really like ur video sir🥰
@hvacraustralia
@hvacraustralia 3 месяца назад
Thanks mate. The best place to get information on VRV/F is from the service manuals. There is a lot of great information in them. Learning how things should work is a great way to know when they’re not operating as they should.
@nunya6081
@nunya6081 10 месяцев назад
B-Press is awful, deforms the pipe and structural integrity of it. RLS is far better to use from my experience! Love these videos, keep them coming. I also saw another one of your colleagues that does videos on TikTok or is that you aswell?
@hvacraustralia
@hvacraustralia 10 месяцев назад
I’m still yet to use b-press. But next install I’d love to try the RLS system. I only heard of this recently! It’s not me. He’s a great tech! Worth following.
@alonsoacosta8545
@alonsoacosta8545 Год назад
Hello friend very good your video, I want to ask you where I could buy the magnetic holder for the umbrella. Thank you very much for your efforts. Grüße aus Berlin
@hvacraustralia
@hvacraustralia Год назад
Hey mate. Thanks, appreciate the feed back. The umbrella holder is from The Trade Shade: thetradeshade.com.au. Highly recommend, it comes in very handy. Especially for summer.
@jaydencabarrus4860
@jaydencabarrus4860 Год назад
Great Vid. What type of Schrader removal valves are they And where you get them? Also your vacuum hoses?
@hvacraustralia
@hvacraustralia Год назад
Thanks mate. It’s all Appion gear. You can buy it all individually but this is from the MegaFlow kit they sell. Awesome for larger systems.
@LC-qi5ff
@LC-qi5ff Год назад
Great vid. When you put it in mode 2:20 were you able to charge via the liquid line?
@hvacraustralia
@hvacraustralia Год назад
Thanks mate. It’s basically just a forced cooling option so I slowly charged through the suction. I broke the vacuum with half the additional charge through the liquid line before opening the stop valves though.
Далее
Daikin / Compressor is Ramping Down After 10 Minutes
10:31
Auto charge VRV A series
3:30
Просмотров 106 тыс.
VRV IV | Modo 2.20 | Modo Carga Manual
1:26
Просмотров 6 тыс.
Daikin / 27kW Package Unit is Covered in Ice
20:11
Просмотров 3,7 тыс.
Heat Pumps in 2024 | What You Should Know
20:11
Просмотров 136 тыс.
Crucial Knowledge To Heat Pump Troubleshooting
14:15
Просмотров 26 тыс.
THAT DAIKIN U4 FAULT ! BUT DID YOU KNOW WHY ?
17:23
Просмотров 46 тыс.
Air Conditioning isn't free... but we're close.
25:45