Found ac going off on high head pressure, washed down & degreased dirty condenser, also replaced contactor for compressor, restarted had to let condenser coil dry, upon further inspection found make up air systems cooling not working due to bad battery’s in thermostat, replaced and 2 stage cooling started working which played a big part of cooling down kitchen.