Emerson Control Techniques Unidrive SP Open Loop Set Up - SM Keypad | Galco 

GalcoTV
Подписаться 125 тыс.
Просмотров 54 тыс.
50% 1

Опубликовано:

 

12 сен 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 38   
@md.aliakbar5646
@md.aliakbar5646 5 лет назад
I talking from Bangladesh in south Asia. This inverter have in my office .. So, It is important for me... Thanks ....
@jugnu361
@jugnu361 Год назад
Alla tumhari madad karega ........... faristey parmeter set karne aaenge.......jannat se......
@Royal_Eye
@Royal_Eye 3 года назад
Hello, please guide me where sircuit position for data encoder? I want re-wiring data encoder sircuit
@mosharofhossen1666
@mosharofhossen1666 4 года назад
UNI4403 HF88 Display show.What is causing this problem? Please help me
@angel63141
@angel63141 10 лет назад
Very good all this information, I really like learning about Variable Speed ​​Drives, but I'm starting to learn about the management of Emerson Unidrive that possibilities exist to publish this information in Spanish?
@GalcoIndustrial
@GalcoIndustrial 10 лет назад
Unfortunately, we do not currently have the resources to overdub the videos in different languages. There might be a Emerson Control Techniques manual with information published in Spanish.
@alisuliman1529
@alisuliman1529 10 лет назад
GalcoTV thank you for reply , but in open loop (without encoder) i can change in parameter 4:11 just from 0 to 1 , or change from 0 to 4 in close loop . i want to rum torque mode (unlimited speed )in open loop . thanks
@alisuliman1529
@alisuliman1529 10 лет назад
Ali Suliman i hope to help me of above problem as soon as possible
@GalcoIndustrial
@GalcoIndustrial 10 лет назад
Ali Suliman You're right, then you will only be able to change it to a 1 for open loop. This should put you in torque control mode. I would also suggest downloading a manual from CT or from Galco's website. To find it on Galco, check out the links above in the description page and navigate to the docs and links part on the product page. A digital manual can also allow for easier searching by using Ctrl+F to find your selection.
@alisuliman1529
@alisuliman1529 10 лет назад
GalcoTV i have a manual and i can do close loop but open loop its difficult in old unidrive its easy to do torque (unlimited speed ) in open loop
@hamzabutt4499
@hamzabutt4499 2 года назад
How to change tha Control setting of emerson ev6000 vfd
@abdulsamadkonnur8222
@abdulsamadkonnur8222 Год назад
I have an Emerson drive SP 2402, facing an alarm/fault “trip it.AC”. I tried to change the parameter 5.07 (by changing 0.49->L2). The par 5.07 doesn’t allow me to change the stored value that’s 0.00. Please I am seeking for the help. Does anyone know how I can fix the issue..
@Technology.furious
@Technology.furious 6 лет назад
HELLO SIR HOW CAN WE RESET DRIVE TO DEFAULT SETTING
@mukhtiarmukhtiarahmed7998
@mukhtiarmukhtiarahmed7998 Год назад
Can you help me????
@laterrazabbq5647
@laterrazabbq5647 5 лет назад
Hello. We have sp1406 indicating SL3.Er And SL3.Hf. could you please tell me how to solve this trip problem? Thank you very much
@GalcoIndustrial
@GalcoIndustrial 5 лет назад
Ok the SL3.er fault means the drive isn't seeing the module in slot 3, or that module has been changed. Having said that, we have found on older SP drives sometimes these connectors become corroded slightly and may be able to clean enough to restore operation by simply removing and reinserting several times and push red reset/stop button. You must take special care when reinserting module to line up connector correctly so as to not cause more damage to unit. The SL3.Hf fault is a type of hardware fault. If this does not reset with the red reset/stop button or cycle the power, the failure may be terminal.
@laterrazabbq5647
@laterrazabbq5647 5 лет назад
@@GalcoIndustrial Thank you very much for your soon answer. When you Say terminal un lastre sentencie do you mean fatal failure or connection terminal fail?
@GalcoIndustrial
@GalcoIndustrial 5 лет назад
@@laterrazabbq5647 Fatal or time to replace
@abdormotin7019
@abdormotin7019 3 года назад
Good
@mukhtiarmukhtiarahmed7998
@mukhtiarmukhtiarahmed7998 Год назад
I have on problem
@ronnymathew5300
@ronnymathew5300 8 лет назад
how to measure power?
@ganeshKumar-bi6ls
@ganeshKumar-bi6ls 6 лет назад
How to save the parameters settings in sp5401 unidrive?
@GalcoIndustrial
@GalcoIndustrial 6 лет назад
All SP Control Techniques drives save parameters the following way,,, x.00=1001 and initiate a drive reset with the Stop/Reset button.
@yasirumer5765
@yasirumer5765 7 лет назад
please guide me how can i see trip history in SP-1403 unidrive and M-701
@yasirumer5765
@yasirumer5765 7 лет назад
thanks
@GalcoIndustrial
@GalcoIndustrial 7 лет назад
Ok in the SP-1403 go to parameter 10.20 for the last fault, 10.21 .22.23 etc. For the M701 got to parameter 10.020 to 10.029 for the trip history.
@yasirumer5765
@yasirumer5765 7 лет назад
thank you
@sunithaent
@sunithaent 4 года назад
Unidrive sp1405 close loop setting video
@sunithaent
@sunithaent 4 года назад
Pl send details
@anouarchahboun9245
@anouarchahboun9245 9 лет назад
i have problem thé message TRIP hf25 in unidrive SP. helpe me plz
@GalcoIndustrial
@GalcoIndustrial 9 лет назад
+Anouar Chahboun HF 25 = Current Feedback offset error. HF means a hardware fault. You can download the Advanced UserGuide Here: www.galco.com/techdoc/cont/unidrive_sp_aug.pdf
@nsero
@nsero 8 лет назад
i want how the unidrive communicate with @calco TV please help me out !
@GalcoIndustrial
@GalcoIndustrial 8 лет назад
Hi nasreddine ramdani, can you be a little more clear about what you are asking please? We would be happy to help you.
@nsero
@nsero 7 лет назад
i want to know how can i communicate with UNIDRIVE SP M using Labview and how can i generate its values?
@GalcoIndustrial
@GalcoIndustrial 7 лет назад
Hi nasreddine ramdani, The drive has a serial communication port that is EIA485 type from an RJ45 connector. This port is isolated from the high voltage in the drive. It supports to different protocols “MODBUS RTU” (default) and “CT ANSI” that are parameter selectable at parameter #11.24 (or zero menu 0.35 is same thing). A 0 = CT ANSI, and a 1 = MODBUS RTU. Let me know if this helps you out.
@nsero
@nsero 7 лет назад
Hi Galco TV Thank you a lot for your help ! I found that very helpful, and i would know if you have an labview structure of what you just explained to me. That would be a pleasure to work with you !
@alisuliman1529
@alisuliman1529 10 лет назад
i have unidrive sp i want to run torque control(unlimited speed) open loop in old unidrive is easy .just select in macro by put 2004 in xx.00 please help me
@GalcoIndustrial
@GalcoIndustrial 10 лет назад
Sorry for the late response. You should be able to change to toque mode by going to parameter 4.11. From here you can change it to a 1 for torque control or a 2 for torque control with a speed override. I hope this helps.