expansion fault finding 

Geoffrey Needs training
Подписаться 7 тыс.
Просмотров 20 тыс.
50% 1

WORCESTER EXPANSION VESSEL FAULT FINDING BLOCK EXPANSION HOSE

Опубликовано:

 

6 сен 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 24   
@sir-dil-a-lot
@sir-dil-a-lot 3 года назад
Best video on expansion vessel so far. Bravo.
@muhammadAli-kd2zp
@muhammadAli-kd2zp 3 года назад
Great explanation I have a customers cdi classic to look at with same issues .. Zero pressure then goes up to 2.5 bar ...
@stuartsinclair6269
@stuartsinclair6269 5 лет назад
Ok, thanks for the info. Appreciated 👍
@kojakxx
@kojakxx 6 лет назад
I do like your videos, very informative, but only one gripe, please don't fill 1/4 screen with 'needs training' watermark, very offputting.
@guido7412
@guido7412 5 лет назад
To echo the last comment, very helpful video but turn off that irritating electronic noise throughout...
@tadhgmuldowney4563
@tadhgmuldowney4563 7 лет назад
Good video
@robcliffe5083
@robcliffe5083 4 года назад
Great video 👍 where can I get one of those little pressure testers from ?? Looks really handy. Thanks
@gjmheating8857
@gjmheating8857 2 года назад
Hello this happens on ours but no water comes out when draining it also fills very quickly 1bar within second
@jmqmin
@jmqmin 3 года назад
Fantastic video.!! Can I ask where you got those grips from?
@davem3833
@davem3833 5 лет назад
How did you know it was the hose that was blocked? What was the pressure difference supposed to be on a system that's up to temperature?
@stuartsinclair6269
@stuartsinclair6269 5 лет назад
Got a Worcester Greenstar 3si, not holding pressure. Keep topping up everyday, put air in vessel, and prv leaking when boiler is on, oh and water comes out of vessel, is it the vessel or prv at fault??? Thanks, feedback Welcome 👍
@yensabi
@yensabi 5 лет назад
If water coming out of valve then vessel needs replacing and it's advisable to replace prv also......👍
@stuartsinclair6269
@stuartsinclair6269 5 лет назад
@@yensabi It's was the expansion in the end, no air in it, so let all pressure out of system, turn off boiler, pumped up expansion vessel to just below 1bar, top off with water, turn boiler on, ran heating, and all is ok, no more prv leaks. When I said water was coming out of vessel, it was just that one time it came out. Everything still ok. Thanks for the feedback.
@rayc1503
@rayc1503 5 лет назад
@@stuartsinclair6269 check your prv is not letting by. You only have to isolate the return and flow pipes on the boiler. Drain the boiler itself and recharge the tank. Bubble the Schrader valve with dish soap to make sure it's not letting by and seated correctly. I hope you put some fresh inhibitor in the system. When you recharged it. You wouldn't drive your car without Antifreeze in the radiator, would you?
@dangas6422
@dangas6422 4 года назад
Can you show how drain.boiler but step by step pls😊
@cduffy4925
@cduffy4925 5 лет назад
The music is good
@jeremydrake5098
@jeremydrake5098 5 лет назад
NOT
@slangking1
@slangking1 5 лет назад
So, what was the expansion vessel pressure just after you had drained down/prior to recharging to 1 bar ? - there must have been something in it, would be useful to know to understand typical behaviour of a unit that hasn't failed...Thanks
@rayc1503
@rayc1503 5 лет назад
Expansion vessel holding 1 bar of water plus 2 bar of water in the system brings it near on the release pressure of the prv. It's basically a neoprene membrane which expands and shrinks. When water boils it expands and creates steam. Hot water needs somewhere to go. In a stream engine excess water is blown out similar to a prv. If the hot steam had nowhere to go it would explode the heat engine. If there were no prv the boiler would blow.
@rayc1503
@rayc1503 5 лет назад
A unit thaat has failed will pass water through the Schrader valve. Briefly press it, if water comes out replace the vessel. If air comes out, drain the boiler and recharge it. Simplz
@daviddraper5485
@daviddraper5485 3 года назад
Needs to find some other annoying music
@davejohnson4783
@davejohnson4783 5 лет назад
That Thumping Music is both unnecessary and annoying yet the video explanation is very good, Who's idea was it to accompany this with such ridiculous banging music
@martinlong8739
@martinlong8739 5 лет назад
Music is awful and completely unnecessary. Also did it solve the problem? The video doesn't show this?
@geoffreyneedstraining5856
@geoffreyneedstraining5856 5 лет назад
the problem was a block expansion vessel hose