I watched all your videos,Simply explained, thanks the video easy understanding the system in tamil I have issue in my Hotel, None of the unit not achieve setpoint AHU,FCU,TFAHU FCU-485nos AHU -9nos Chiller -3nos FAHU - 3nos One FAHU 100% Fresh Air Two FAHU with HRV Both TFAHU i found HRV Not working, 3nos chiller always two chiller running with 4compressur And all the location water condensation is there Can you advise what I need check?
Hi sir. Thanks it was too informative. I have a small doubt. Why is ahu connected to fcu before entering into a space, why it is not directly entering into a space through ducts? Thanks
Hi sir....I'm working in bank building there's two fcu connected one ac working good condition another one ac cooling good but too much noise coming what's the problem can you tell me pls I'm facing this problem one week Note : I'm three month once doing the ppm service checking the coil and motor everything but last two weeks this issue I'm facing can you explain sir
Bro. How to calculate AHU TR (newly to be installed) for a Electrical panel room, which has VFD's, controllers, breakers. How to know its quantity of heat generation.
That's ok bro. How could I calculate AHU capacity for that panel room? Those drives will generate a huge amount of heat. Chilled water temperature is around 7 -8 deg C in our plant.
@@shipraprasath Hi! Consider the heate mission rate (inefficiency of the VFD will convert into heat say 98% efficiency from VFD and 2% will be dissipating as a heat inside the room)from VFDs and add the same in your heat load calculation as sensible heat so that you can arrive the tonnage of the AHU.
Hello sir.. I have a doubt regarding Fcu. In a closed room/building from where Fcu is getting intake air, from ahu or existing air inside the closed building /room. If it is taking existing air inside the building /room the co2 level is more ryt, Please advice for the above
Hi, Basically FCU will circulate room air + some amount of fresh by the help of FAHU . Hence the fresh from the FAHU will ensure the oxygen level inside the room for human comfort. Better study carrier HVAC design Hand book.
வணக்கம் bro Bro beauti salon kku என்ன type ac use பன்னா நல்லா இருக்கும் bro, vrf okya, or normal spilt ok yaa, or vera ஏதாவது model இருக்கா bro, centralised ac duct panni podlaamaa, மொத்தம் 1300 sqft , pls advice me, my no 7373530666
@@lohisya_media thanks bro, Bro one more help which company is best and cheap , i understand vrv is daikin ,apart from that which company is best and cost effect bro