Hi again sorry if I ask so much questions, in the vista 20p how can I wire it so the strobes don’t flash in code 3? Is that in programming? Also what resistors should I use in the NAC and zones? Thanks
I'm not sure if you can set the nac to continuous in fire mode. Resistors are 2.1-2.2k, you don't need a resistor for the nac unless the jumper for Bell supervision has been cut
can you guide me how to where to connect the vista to the network like where should I connect the phone line and the ethernet cable ( I have the same one vista 32fb)
No, it has to be programmed and be connected to some sort of communications line. Even then, you'll still need to program it. The vista by itself can't call the police anyway, it has to be programmed to dial into a central station and from there the central station will dispatch fire, police, medical etc
On the vista 20p what terminals do you wire the horn strobe? Where do you wire the pull station? Can anyone give me some info on how to wire this ( I know it’s not code complaint)