How to Reset Flammable Vapor Sensor on Water Heater AO Smith or Rheem Step by Step Directions 

Mikey Pipes - Pipe Doctor Plumbing & Heating & Air
Подписаться 158 тыс.
Просмотров 48 тыс.
50% 1

Got Hot Water? If your water heater is giving a error for Flammable Vapor Sensor then keep reading and watch this video! Fortunately this error code can be reset and hot water can be restored in less than one hour. The reset procedure will vary depending on which gas valve you have - I've listed all the popular models below.
Before attempting to reset the gas control, you must be certain to remove any substances that may have caused the FV sensor to activate and air out the area near the water heater thoroughly for at least one hour. The FV sensor must also be dry. Once you’ve determined there are no flammable vapors or liquids near the water heater, you may reset the gas control.
Flammable Vapor Lockout Error
1. If you cannot perform the work safely, then have a service technician replace this part.
2. Turn power to the water heater off. Thoroughly check the area near the water heater for any substances that may give off flammable vapors. If you find any flammable vapors or liquids near the water heater, remove them. Open doors and windows and air out the location for at least one hour. Once you are certain the area is clear of any flammable vapors or liquids and the sensor has been replaced, you may reset the gas control.
3. The FV sensor can also lock the gas control if it is exposed to certain non-flammable vapors such as ammonia, bleach, air fresheners, or other “smelly” chemicals. Remove any such substances located near the water heater. Open doors and windows to air out the location for at least one hour.
4. In rare cases, moisture in the air or direct contact with water can cause the gas control to lockout. If the FV sensor gets wet, you'll have to replace it. If your water heater has been flooded, do not attempt to reset the gas control. And contact phone number on the side of your water heater.
5. If you've gone through the FV Sensor reset procedure before but the sensor continues to activate, you'll need to have a service technician look at the water heater to determine the issue.
Honeywell Control Reset Procedure
1. Turn the gas control switch to off for at least two seconds
2. Turn the power switch back on and allow three seconds for the gas control to initialize and self-check.
3. In the next 30 seconds, Increase the temperature setting past the “HOT” mark, then back to “VAC.” Do this twice. Then return the dial to the preferred set point. "HOT" is recommended to reduce the risk of scalding.
4. Wait 10 seconds and see if the fault will clear. If the gas control is reset successfully and there are no flammable vapors near the water heater, the control will resume normal operation.
5. If the gas control fails to reset, air out the room again and repeat steps 1 - 3. If the gas control fails to reset after several attempts, call the manufacture or a licensed and qualified professional.
Intelli-vent Control Reset Procedure
1. Turn off power to the water heater and wait at least one minute.
2. Turn power to the water heater back on and immediately (within 10 seconds) press and hold both the HOTTER and COOLER buttons until the green VACATION LED light begins to flash.
3. Release the HOTTER and COOLER buttons and immediately press and hold the HOTTER and COOLER buttons again until the green VACATION LED light is steady (NOT FLASHING). When the green VACATION LED is steady, release both buttons.
4. If the gas control reset was successful, all LED lights on the gas control will light briefly then go out. At this point, the water heater should be working normally. No LEDs are lit when the water heater is working normally.
5. If the gas control fails to reset, air out the room again and repeat steps 1 - 4. If the gas control fails to reset after several attempts, call the manufacture or a licensed and qualified professional.
Robertshaw Gas Valve:
1. Turn the manual lever on the Control Gas Valve counter clockwise until it snaps to the "ON" position.
2. Keep the temperature dial on VACATION.
3. Plug in the power cord and turn on blower switch and wait 3 seconds for the system self-diagnostic check.
4. Within the first 30 seconds, the temperature dial must be rotated back and forth crossing the 120° F mark at least six times.
5. This will reset the Control Gas Valve and cause it to display a normal flash code for the LED on the left bottom of the Control Gas Valve. Note: Slow blinking is the normal flash code.
▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
🛒 Flammable Vapor Sensor:amzn.to/3cF1iQg
▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
🅿️ Want to Support This Channel? You can donate via:
PayPal: office@pipedoc.net
Venmo: @PipeDoctor
CashApp: $mikeypipesny
Want to send a love letter, note or gift? Our mailing address is:
Mikey Pipes
C/O Pipe Doctor Home Services, Inc.
80 E Hawthorne Ave
Valley Stream, NY 11580
#mikeypipes #waterheater #repair

Хобби

Опубликовано:

 

31 авг 2022

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 115   
@sharonbronzetti2845
@sharonbronzetti2845 Год назад
Thanks!
@susanaespinoza4711
@susanaespinoza4711 18 дней назад
OMG! I reset the vapor sensor pulled it out and everything and it worked! I followed all the steps and it worked because the 7 time knob reset thing alone wasn't working I had to pull out that sensor! Thank you!I just paid over 2K in my furnace a few months ago I was devastated to think I had to pay for this now! thank you!
@PipeDoctor
@PipeDoctor 17 дней назад
Great job!
@sherriealvarez1182
@sherriealvarez1182 Год назад
OMG Mikey you are a life saver! I was able to reset my flammable vapor sensor on my AO Smith water heater because of this awesome video. Thank you so much! Too bad I already took a cold shower this morning, at least everyone else will have a hot shower lol. I followed your instructions for resetting the flammable vapor sensor starting at 9:03 in your video and water heater started right up woohoo! Oh and yes we just had our roof replaced, so when they ripped off all the old roofing, the amount of dust and debris that fell into the garage and covered everything, was shocking and foul, we had to take everything out and clean it off thank heaven for our shop vac!
@johnbaer7956
@johnbaer7956 Год назад
Pipe doctor keeps giving , great content , now great shirts , man stand up fella
@srtmcnair
@srtmcnair Год назад
Wow im a plumber in the DMV area followed your instructions and boom bang boom it work A+ your awesome
@PipeDoctor
@PipeDoctor 2 месяца назад
Glad it helped!
@lori241
@lori241 Год назад
Mikey, you are my hero. It looks like my water heater is back in action after watching your video. We had a lot of construction activity surrounding the unit yesterday and today, so I hope it was just that and won't happen again. Thank you!!
@matthewfasullo4983
@matthewfasullo4983 Год назад
Rheem has those vapour sensors as well as Bradford white and gsw brands. You don't always have to replace them. If you have a multimeter tester, you can pull the sensor off and use the tester to check resistance. The range it should fall in is between 3k and 100k ohms. My rule of thumb if it reads under 60k ohms I'll reset the valve and all is good and hot water is restored. If it's 80k or higher I replace it. It won't take much of a smell to throw it off again. Some people think it's a stupid sensor,but it's there for a reason it will save your life one day if you ever have a gas leak. I went to a customer's house with that same scenario and I walk into the basement and I smell gas. I look down and tank is off on vapor sensor lockout. We found the leak and fix it ,but if it weren't for that sensor who knows what may have happened.
@c21meister
@c21meister Год назад
It’s a stupid sensor
@matthewfasullo4983
@matthewfasullo4983 Год назад
@@c21meister might be stupid but it will save an explosion
@robertcopeland9298
@robertcopeland9298 9 месяцев назад
Glad you made this video. I had the manual with the gas heater I bought and all it said was to turn it off then back on to reset, that didn't work, but this method did!
@PipeDoctor
@PipeDoctor 9 месяцев назад
Glad it helped
@menashelandau4293
@menashelandau4293 Год назад
wow thanks a lot for the vid- i came across a similar issue with a customer i called ao tech support said i need to replace gas valve. customer was hesitant as its an expensive repair for a relatively new water heater , he got ao smith tech to come down to fix it - customer described to me exactly what you did here to reset it. in my case it probably needed a reset ( as they were doing home renovations) . i guess ao smith could have mentioned this little “trick” when i was talking to them before recommending replacing gas valve
@danielfaust2456
@danielfaust2456 Год назад
Thanks for making a 15 second video 13 minutes.
@PipeDoctor
@PipeDoctor 2 месяца назад
You’re welcome 😇
@Eddy63
@Eddy63 Год назад
Perfect timing , I needed to kill some time before Tenn plays Ball State tonight ... Thx ...
@realestateservicessaleshea99
Nice floor, I'm still not taking my shoes off!🥃🍺🥃🍺🍺😅🤣🤣 Thanks again for the videos!
@marty0715yt
@marty0715yt Год назад
OHHHH Shiney!!!
@kevinpoore5626
@kevinpoore5626 Год назад
hey good old number two again LOL hope everybody had a good day
@karlohocurscak1066
@karlohocurscak1066 Год назад
Thanks Mikey, I never guessed that you had to cycle the temperature control to reset after replacing the vapor sensor.
@PipeDoctor
@PipeDoctor 2 месяца назад
Yes I have.
@smidgerbit
@smidgerbit Год назад
Thank you brother, saved the day. Scott and Jim in Maryland
@smidgerbit
@smidgerbit Год назад
Sure did 👍🏼
@rustyshakleford5230
@rustyshakleford5230 Год назад
Hey Mike did you ever get the ProPress Jaws I sent you that fit the zoom lock nibco press?
@franks6837
@franks6837 Год назад
To reset either FVS turn gas valve off at switch on gas valve and turn it back on then get a slot screwdriver and turn dial min max 7 times if the switch doesn't reset it is done and needs to be replaced . I would say 80 % of the time they will reset
@grs8310
@grs8310 Год назад
Only after turning gas valve off and on and changing water heat level 7 times furnace star working! Thank you very much
@purestmuslim
@purestmuslim Год назад
I followed your steps and it worked thank you very much!
@thomasmann3560
@thomasmann3560 7 месяцев назад
Thank ls man, I was looking all over how to reset this thing. Im an HVAC/R and plumbing tech. We don't stock these sensors. So I threw a dixell sensor on it to get em thru the weekend. That reads 15k OHMS most the time so they work. And I know everyone has a few of those on their van. A bunch of our restraunts have these water heaters right next to the mop sink. So the sensors get wet.
@PipeDoctor
@PipeDoctor 7 месяцев назад
No problem 👍
@danielrandolph9170
@danielrandolph9170 Год назад
Good video Mikey good info !! Stay safe
@jaykim1071
@jaykim1071 5 месяцев назад
Your video saved my ass today Thank you Mikey
@jefferyallen8863
@jefferyallen8863 8 месяцев назад
Bro. Thank you! I was about to pull my hair out!
@PipeDoctor
@PipeDoctor 8 месяцев назад
Glad I could help
@waynebrathwaite3856
@waynebrathwaite3856 Год назад
Nice work i had a similar problem.👍🏽👍🏽
@albart3203
@albart3203 4 месяца назад
Good job sr. Thank you.
@PipeDoctor
@PipeDoctor 4 месяца назад
Thanks!!! Did you subscribe?
@albart3203
@albart3203 4 месяца назад
I will do now. 👌
@tedsmith5058
@tedsmith5058 Год назад
Hello from the great state of Michigan
@conundrumconundrum5589
@conundrumconundrum5589 Год назад
Just read an article where a power company declared a power emergency where too much power was being used during a heatwave in colorado. The power company locked out its customer's thermostats and prevented them from cooling their house that day. That should be a concern of all smart thermostat owners in the future as to the government or private companies beeing allowed to do this. To be fair these power customers volunteered for this program.
@snidelywhiplash8923
@snidelywhiplash8923 Год назад
It's always a good idea to have facts before getting outraged. There's a VOLUNTARY program in Colorado (and in other locations) where customers CAN CHOOSE to participate in thermostat cutbacks (not turn-offs) on days of high power demand, in return for cash. Don't want to do it, don't do it. This is called load shedding. The alternative to proper management is to either have rotating blackouts (areas turned off completely) or to have the systems crash. Which approach do you prefer?
@Silky_boi
@Silky_boi Год назад
Oh wow I heard similar out here in SoCal haven’t had a service call on it but will keep an eye on it
@conundrumconundrum5589
@conundrumconundrum5589 Год назад
@Snidely Whiplash Neither, I prefer systems to be built out and improved to provide for demand. Also, money not wasted on stupid things. I also prefer people read and comprehend comments in their entirety.
@snidelywhiplash8923
@snidelywhiplash8923 Год назад
@@conundrumconundrum5589 Your "reading with comprehension" comment is funny. I offered three alternatives, and your reply was : "Neither".
@throttlebottle5906
@throttlebottle5906 Год назад
they could just do rolling blackouts instead of stopping cooling. then you can enjoy hours of no electric at all and short on periods that never allow the refrigerator to recover enough and all your food spoils. pretty much your choice by allowing them to control it or not and forcing them to load reduce the bad way. 🤣 and the government wants you/us all to have electric everything, a big show of how stupid that is will occur sooner than later, much worse than the Texas freezup.
@intlsuperstar
@intlsuperstar 2 месяца назад
Thank you so much!
@PipeDoctor
@PipeDoctor 2 месяца назад
You're welcome!
@tompuhalla7774
@tompuhalla7774 Год назад
Thank you. Going to buy one of those sensors now just to have
@xDailyCodx
@xDailyCodx Год назад
Mikey, what are the chances I can receive one of those prestigious long sleeve shirts all the way out here in Canada?
@jnev9046
@jnev9046 25 дней назад
This just worked for me. Save rme $300
@PipeDoctor
@PipeDoctor 25 дней назад
Awesome
@staticpressurenerd5182
@staticpressurenerd5182 Год назад
I remember the first time I came across one of these “oh I’ll just bypass it to get some hot water” 🤣
@michaelburgess7703
@michaelburgess7703 Год назад
I would like a large for the winter time down here in Warner Robins Ga. Love all of videos and learning at lot too.😄⚛️🚿🚽⚕️
@tonydelgrego2906
@tonydelgrego2906 Год назад
Thanks
@aguttz1312
@aguttz1312 Месяц назад
Fvs lockout reset.. 1. unplug 2.plug 3.off 4. on 5. rotate temp pilot to very hot x3 .. 💪🏾
@zahrajafari8269
@zahrajafari8269 10 месяцев назад
Thanks it was very helpful video 👍👌
@PipeDoctor
@PipeDoctor 10 месяцев назад
Glad it helped
@bruceshad7241
@bruceshad7241 Год назад
same thing happen at my place after painting... I was able to reset vapor sensor by turning knob on Honeywell back n forth like 5 times fast and it work fine again
@Ben-xo3bj
@Ben-xo3bj Год назад
Just an FYI you don't need to replace those typically in this happens. Sometimes they do go bad and you have to replace them but if it was just tripped because of actual vapors you can do the same thing you did to reset the gas valve without replacing the paper sensor
@lawabidingbaddie9595
@lawabidingbaddie9595 Год назад
What minute mark is that. My unit is less than 2 years old and it was simply pain.
@eddiew.6485
@eddiew.6485 Год назад
That had to be the WORST dryer vent blockage I have ever seen! She said they just bought the house…..did she have the home inspected before the sale? That’s an easy one!
@bigdaddy4975
@bigdaddy4975 Год назад
I need to get into zoom lock I’m still brazing I use stay bright 8 also usually down by the txv.
@MilesVogel
@MilesVogel Год назад
you get a free shirt and you get a free shirt.
@Silky_boi
@Silky_boi Год назад
I’m going to have to get a new iPhone…. Cause I SMASHED THAT LIKE BUTTON!!!!!!!
@Silky_boi
@Silky_boi Год назад
@@PipeDoctor just sent it over! Thanks Don Mikey! - Matthew
@walterdubiel5741
@walterdubiel5741 Год назад
SWEET!!
@savonegrafton5364
@savonegrafton5364 Год назад
Thank you sir 🫡
@natepeterson7145
@natepeterson7145 Год назад
I always replace them because a callback will irritate the customer especially when they conveniently forget that you said it's a 50/50 chance it'll work.
@realestateservicessaleshea99
@realestateservicessaleshea99 10 месяцев назад
Just got stuck today!😂😂😂😂
@ChrisHVAC
@ChrisHVAC Год назад
Death Box Incorporated! Got that brand right
@chrisebo9390
@chrisebo9390 9 месяцев назад
Thanks Bro saved my a** today
@PipeDoctor
@PipeDoctor 2 месяца назад
Glad to hear
@bauhnguefyische667
@bauhnguefyische667 Год назад
The number you schould have had in mind was Nest’’s customer service hotline. Kidding of course😉🖐👍
@chadschafer1723
@chadschafer1723 Год назад
You can bypass them by taking the two leads that normally attach to the sensor and put them in a bowl of water with the two leads on opposite sides
@chadschafer1723
@chadschafer1723 Год назад
@@PipeDoctor ok, believe what you want
@justin6296
@justin6296 Месяц назад
Dumb question. Can you dry off these sensors if they get wet? Thank you
@PipeDoctor
@PipeDoctor Месяц назад
I don’t see why not?
@jeffsworld2
@jeffsworld2 Год назад
Couldn't help notice the temp on the WH was set to Very Hot, if it was that way when you got there I hope you lower it, that is like 160 or so water temp. Very dangerous.
@tkgotwings_6401
@tkgotwings_6401 Год назад
the homeowner probably did that hoping they would get hot water lmao we all know thats why
@2pugman
@2pugman Год назад
Mikey, did you see where the power company in Colorado took control of all NEST thermostats and re-set them for 78* ? They were having a power shortage and decided to control all the NEST A/C controls. Reported by FOX.
@2pugman
@2pugman Год назад
@@PipeDoctor The power company offered a $100 credit for those who joined their program. Suckers.
@gtpforever
@gtpforever Год назад
Can't control it if you don't let them🤷‍♂️
@alanpaulin8175
@alanpaulin8175 5 месяцев назад
I did the same start up sequence without replacing the sensor and it started right up. No sensor replacement needed.
@PipeDoctor
@PipeDoctor 5 месяцев назад
Lucky
@c21meister
@c21meister Год назад
Are t shirts still available?
@snidelywhiplash8923
@snidelywhiplash8923 Год назад
Wouldn't it be better if the exhaust vent extended out some inches from under the overhang? Wouldn't seem like a good thing to expose the underside to a pretty regular stream of hot, humid air. That dryer vent is a mess. If that house has a new owner, I would have thought looking at such things would be a standard step for a home inspector. Problem diagnosis (whether the broken flap or the obviously clogged line) doesn't require much training. Thanks
@snidelywhiplash8923
@snidelywhiplash8923 Год назад
@@PipeDoctor If you by yourself were putting in a new install, where would the exhaust pipe end? ;-)
@throttlebottle5906
@throttlebottle5906 Год назад
dryer venting in unconditioned/outdoor space is a big no-no, it will condensate on the inside(and outside), the lint builds up inside very fast and clogs, killing the dryer thermal cutoff(non-resettable) now you need appliance service and will tear it out and start over again. it may work in Arizona, where it's always hot and dry climate.
@snidelywhiplash8923
@snidelywhiplash8923 Год назад
@@throttlebottle5906 " it will condensate on the inside". I think you mean "condense" Where else would you vent a dryer other than outside into "unconditioned, outdoor space"? That's where they all go. My comment asked about whether the termination of the exhaust line (not dryer line) under the overhang was a good idea. Maybe you're saying the exhaust line shouldn't extend so far beyond the wall of the structure?
@throttlebottle5906
@throttlebottle5906 Год назад
@@snidelywhiplash8923 I thought you meant the dryer exhaust, extending that outside the building will clog the pipe very fast. as for the water heater exhaust, it will cause very minimal compared to the dryer vent being under there, which also shouldn't be near the gas meter(no vents/intakes should be nearby) the water heater is probably far enough away being extended outside, condensation inside it's pipe would be ok, as long as it's pitched properly for drainage. a sag or bow could make it ice dam.
@geetsippy8234
@geetsippy8234 Месяц назад
Resideo gas valve with 4 blinks every 3 sec … what to bee done powerflex gas tank
@stephwaylonwells3218
@stephwaylonwells3218 Год назад
👍
@Hvac-dude
@Hvac-dude Год назад
I want one 😊😊😊😊
@lawabidingbaddie9595
@lawabidingbaddie9595 Год назад
Mine happened after some contractors painted in my washer room. The unit is only 2 years old.
@PipeDoctor
@PipeDoctor 2 месяца назад
Sucks.
@redriot9144
@redriot9144 7 месяцев назад
Is this Kurt Russell?😮
@PipeDoctor
@PipeDoctor 2 месяца назад
lol
@joseg.8589
@joseg.8589 6 месяцев назад
Want the large sleve please.
@PipeDoctor
@PipeDoctor 2 месяца назад
Of what?
@jondolan8551
@jondolan8551 Год назад
you send me them shirts I will be a walking billboard for you. you are an inspiration to me. do or XXL.
@jondolan8551
@jondolan8551 Год назад
@@PipeDoctor if you are hiring I will apply and out work most of these young guys. I'm 52 no licenses and have done most everything I see you do minus the freon part. I have never played with the freon. Can and have done the rest.
@lookbehindyou8703
@lookbehindyou8703 Год назад
did anybody tell you you look like roger clark
@PipeDoctor
@PipeDoctor 2 месяца назад
No
@delaneyjane4834
@delaneyjane4834 Год назад
Wtf does vacation mean? What temperature is vacation ?
@PipeDoctor
@PipeDoctor 2 месяца назад
Like standby. Room temp
@daddygc5814
@daddygc5814 Год назад
Finally, a gal with nice feet in your videos, lol
@RETread-xh6fr
@RETread-xh6fr Год назад
FVR sensors are arguably a good thing but having to call a professional to replace an FVR sensor is rucking fidiculous! Make it difficult and/or expensive to replace FVRs and people WILL replace them with 22k resistors.
@throttlebottle5906
@throttlebottle5906 Год назад
or gas valve that doesn't have it at all.....
@cwedenfield
@cwedenfield Год назад
love your channel i lke to have xxx large shirt if still in stock
@mikeboyle397
@mikeboyle397 Год назад
Thanks!
@Rello690
@Rello690 8 месяцев назад
Thanks
@PipeDoctor
@PipeDoctor 8 месяцев назад
No problem
Далее
Новые iPhone 16 и 16 Pro Max
00:42
Просмотров 1,4 млн
Kettim gul opkegani😋
00:37
Просмотров 439 тыс.
How To Reset Flammable Vapor Sensor on Water Heater
6:25
Flammable vapor sensor, permanent, fix
7:46
Просмотров 67 тыс.
FAILURE TO START - RPM SENSE LOSS
2:15
Просмотров 260
Montage des Mighty Bracket
1:41
Просмотров 10 тыс.
Omnibuild- Marriott Hotel NYC Boiler Start Up Day
6:37
VOC sensor bypass Rheem Platinum
5:10
Просмотров 50 тыс.
Будни пекаря. Часть 6
0:59
Просмотров 2,2 млн
🍁 Ты остался незамеченным
0:26
CAA Conversion kit at ZAHAL 🎯
0:14
Просмотров 64 млн