HVAC TROUBLESHOOTING LG MULTI V 5 

D2D NY Real World HVAC Simplified
Подписаться 18 тыс.
Просмотров 8 тыс.
50% 1

LG MULTI V 5 NO AC SERVICE CALL
HVAC TROUBLESHOOTING ON
LG Multi V 5 error code 116 oil level sensor error, actual error code 116 1 (C2) master compressor 2 oil level sensor error. After replacing the sensor system ran fine.
#d2dnyac
#heatingventilationandairconditioning

Опубликовано:

 

5 окт 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 55   
@andyjones7836
@andyjones7836 3 года назад
Thanks for uploading! Very interesting, I assume if you could swap the dodgy oil module over to C1 compressor - the fault would shift to 116 1 C1. That is a pain though unwrapping the tape to get to it, especially with one hand✋. It's amazing how many youtubers only have one hand🖐️ - what are the odds 😂😂😂😂 Keep up the good work 👍👍
@D2DNYAC
@D2DNYAC 3 года назад
Thanks for stopping by
@jameshandshy
@jameshandshy 2 года назад
You should be able to pull the leads off the oil sensor and short them together and watch LGMV service tool to see if the oil indicator goes green. If it does and you put it back on and it goes off again then it's a good indication you are low on oil. If tho when you short them out and the green light doesn't go green then it's a faulty oil level sense and cable. Order it for inv2 so the plug colors are the correct ones. Then as alway watch it and make sure it does go green if not you'll need to run oil recovery mode and follow other comments abovevas you might have another issue with valves
@D2DNYAC
@D2DNYAC 2 года назад
@James Handshy very nice 👍 sounds good I will definitely be testing this out ! Thank you 🙏and thanks for stopping by
@Syedpir
@Syedpir 3 года назад
Hello brother good job.
@davidbrown7423
@davidbrown7423 3 года назад
Usually oil return is a fault of the indoor units needing to be reset. Sometimes the outdoor unit will lose an indoor units address or HR boxes could have failed eev. It's hard to troubleshoot without using their service checker LGMV
@D2DNYAC
@D2DNYAC 2 года назад
👍
@HVAC559
@HVAC559 8 месяцев назад
Thank you sir
@D2DNYAC
@D2DNYAC 8 месяцев назад
Thank you for stopping by
@alikhalid76dxb
@alikhalid76dxb 3 года назад
Pls post next vdo also what was actual problem thanks
@D2DNYAC
@D2DNYAC 3 года назад
I replaced that oil sensor board/ module and the system ran error did not return and client haven’t called back since!
@NC-it6im
@NC-it6im Год назад
Thanks for the info!
@D2DNYAC
@D2DNYAC Год назад
Thanks for watching
@Zavrian12
@Zavrian12 10 месяцев назад
LG Indonesia hadir
@D2DNYAC
@D2DNYAC 10 месяцев назад
Thanks for watching
@percyfranco8360
@percyfranco8360 Год назад
Very interesting troubleshoot..good job... you know ,how to fix error code same unit LG multi V.5 ..error code 1042?
@D2DNYAC
@D2DNYAC Год назад
Do you have double condensers?
@D2DNYAC
@D2DNYAC Год назад
Twined ODU?
@robertmedina9267
@robertmedina9267 3 года назад
Hello sir, I am having trouble on slave and master multi v.5 vrf, both accu are not running but no error is being displayed. I have also tried LGMV but all parameters are normal. Hope you can help. Thank you!
@D2DNYAC
@D2DNYAC 3 года назад
Does the compressors starts or runs?
@RogamoMape
@RogamoMape 13 дней назад
Can you do one for CH150
@killslveslowly
@killslveslowly 2 года назад
Hello, I have a Multi Vs system and I I have 2 thermostats one works fine connected to one ducted unit and the other is daisy chained between 3 units, I keep getting error 53-1, when the system starts to blows cool but then stops on the 3 units. Help if you can
@dimaslespier2688
@dimaslespier2688 3 года назад
Curious 🧐 is there a vale to oil level from the compressor thermistor? Some way of checking to see if you are getting the proper value from within the compressor? Just sayin
@D2DNYAC
@D2DNYAC 3 года назад
Good question! perhaps 🤔 I will check for that the next time I have the service checker/tool hocked up to the system and add a comment regarding.
@yaqoobk2
@yaqoobk2 Год назад
Sir vrv multi v s some time ch05 some time run any solution pls
@D2DNYAC
@D2DNYAC Год назад
Can someone with knowledge of LGMV systems help please?
@marksimpson4122
@marksimpson4122 Год назад
So I’m on a Multi V with 2 HRUs and have a 200-1 Fault. Can u post step by step APD Auto pipe detection instructions plz. Something is lost in the Korean to English translation on the HRU panel
@D2DNYAC
@D2DNYAC Год назад
I will see what I can do
@vusalmmmdov4204
@vusalmmmdov4204 2 года назад
we have error code C2 1 CH-116 in our Multi V5 air conditioner. Do we need to remove and re-install the oil sensor or measure its voltage to fix this problem?
@D2DNYAC
@D2DNYAC 2 года назад
After replacing the sensors on the jobsite I went the error never came back
@nikopineira6001
@nikopineira6001 Год назад
Thanks
@D2DNYAC
@D2DNYAC Год назад
Thanks for watching
@ganeshmotiram2847
@ganeshmotiram2847 2 года назад
Lol it’s funny I did that job at 65 bleecker at core yoga at the last company I worked
@D2DNYAC
@D2DNYAC 2 года назад
@Ganesh Motiram what are you talking about friend?
@yousoufabbas3577
@yousoufabbas3577 3 года назад
Hello what does the code 571 vrf LG multi4 mean?
@D2DNYAC
@D2DNYAC 3 года назад
I believe that's a lost of communication between indoor and outdoor units
@HungNguyen-kd6kb
@HungNguyen-kd6kb Год назад
Máy nén tuyến tính công nghệ của LG nay ứng dụng trên VRF luôn rồi.
@D2DNYAC
@D2DNYAC Год назад
Nice
@MerajAhmad-ni8re
@MerajAhmad-ni8re Год назад
I need job I have good experience of lg from Bahrain
@D2DNYAC
@D2DNYAC Год назад
USA 😂 my friend
@merajahmad8976
@merajahmad8976 Год назад
I am from middle east I need job pls help me I have 9 year experience in vrf system daikin vrv lg Toshiba like that
@D2DNYAC
@D2DNYAC Год назад
I am in the USA my friend
@jamessaeger8113
@jamessaeger8113 2 года назад
Does anyone realize that they put the sensors on for a reason. Just because you get an error doesn't mean the sensor is bad. Just sayin
@D2DNYAC
@D2DNYAC 2 года назад
@james Saeger I agree ☝️my friend however sensors do go bad and if you are the one providing service for the equipment and you know it’s history then it’s easier for you to make the decision to replace sensor or chase it’s diagnostics
@cdefreit1
@cdefreit1 3 года назад
If any indoor unit or HR/Branch selector box loses power, can the entire system shut itself down? Has anyone ever experienced that?
@D2DNYAC
@D2DNYAC 3 года назад
On this site 1 indoor unit had no power and the rest of system stayed online
@mwdub02
@mwdub02 2 года назад
System would still run even if you lose one or two indoor units, unlike daikin crap
@AtalaTheGreat
@AtalaTheGreat 2 года назад
@@mwdub02 Does the system bypass the faulty addressible unit then? (the faulty fan coil or branch box with no power in this case)
@D2DNYAC
@D2DNYAC 2 года назад
@chris Def still runs
@mwdub02
@mwdub02 2 года назад
@@AtalaTheGreat yes it’ll pass it.
@MerajAhmad-ni8re
@MerajAhmad-ni8re Год назад
Only vrf exp in daikin lg Hitachi Samsung
@D2DNYAC
@D2DNYAC Год назад
Nice
@MerajAhmad-ni8re
@MerajAhmad-ni8re Год назад
U did not reply me about the job
@yousoufabbas3577
@yousoufabbas3577 3 года назад
Hello what does the code 241 vrf LG multi4 mean?
@D2DNYAC
@D2DNYAC 3 года назад
I will check and get back to you
Далее
HVAC | MAIN PCB HACKED AND FIXED
10:07
Просмотров 1,1 тыс.
LGMV HAVC TROUBLESHOOTING LOW REFRIGERANT
30:31
Просмотров 6 тыс.
LG Multi V : How to Replace SVC Compressor I LG
14:16
#1 Failure with Commercial HVAC
13:50
Просмотров 100 тыс.
HVAC TROUBLESHOOTING
11:26
Просмотров 872
LG AS Multi V Cambio Compresor Multi V 5
14:16
Просмотров 5 тыс.