Introduction to ET 200SP Base Unit (Overview & Usage) 

RealPars
Подписаться 1,1 млн
Просмотров 218 тыс.
50% 1

▶ Order ET 200SP Base Unit now
bit.ly/435iGC0
=============================
▶ Check out the full blog post over at
realpars.com/et-200sp-base-unit
=============================
▶ How to Wire Sensors to a PLC - Part 1
• How to Wire Sensors to...
=============================
⌚Timestamps:
00:00 - Intro
00:50 - ET 200SP Remote I/O
04:03 - ET 200SP Base Unit
05:36 - How to Install the ET 200SP Remote I/O Components
08:05 - How to Power up the ET 200SP Remote I/O
10:30 - How to Connect a Sensor to the ET 200SP Base Unit
This video will answer two important questions for you.
First, what is an ET 200SP base unit?
And second, how can you install and use this device in your system?
The base unit is, as the name indicates, a base where you can install the I/O cards.
In order for you to be able to install the I/O cards on the et 200sp, you must first have a base unit installed on the din rail. Once in place, you can install your I/O card.
Let’s examine how to install each component of this ET 200SP remote I/O on the din rail.
With the rail in place, you put the head module on the rail.
Then push in the lower part lightly until you hear a click sound.
The same goes for the base unit. You put it on the rail then push it into the rail. Making sure the device clicks into the rail.
Next, push the base unit to the left to attach it to the head module.
When you hear that click sound, it means that the base unit has been properly connected to the head module.
Now, the base unit can easily communicate data with the head module.
To install the I/O cards or theI/O modules, you simply place the card on the base unit.
Then push it in slightly to hear the click sound.
Now, this card is able to communicate data with the head module through the base unit.
You can install the rest of the cards on the base units in the same way.
To power up the head module, you need to first connect a 24-volt power to the module.
Then to power up the rest of the modules in the unit, you simply take the same two wires and connect them to these terminals of the first base unit.
By doing this, you’ll not only be able to power this module, but you’ll see the power also follows through the rest of the base units on right. And turns on the rest of the modules as well.
Bottom line? You don’t have to connect any wire to these base units. Just connect the power to the first unit and the rest will be taken care of.
Now you may ask, does this work with any other base unit setup as well? In other words, can I simply connect the power to the first one, and then the power flows through to the rest of the modules?
The answer is… no!
The reason the power can flow through from this base unit to the rest on the right is because i’m using a type A0 light-colored base unit here.
While the rest of the base units are type B0 dark-colored.
As with any other module, there are several types of base units.
This module features, for example, type A0, A1, B0, B1, C0, and C1 among several others.
Additionally, some of these types come in both light and dark colors.
As a rule of thumb, light-colored base units are usually installed as the first module after the head module and can pass the power to the rest of the modules on the right.
While the dark-colored base units are usually installed from slot two onward and can receive power from the light-colored base units on the right.
How do the i/o cards receive the signals from the sensors and actuators in the field?
Well, this is where the base unit comes into play again.
To connect the sensors and actuators in the field to the I/O cards on the remote I/O, you take the wire from the sensor, put a wire ferrule on it, and then connect it to the push-in terminals on the base unit. Easy peasy, right?
=============================
Missed our most recent videos? Watch them here:
realpars.com/vibration-sensor/
realpars.com/level-sensor/
realpars.com/absolute-vs-incre...
=============================
To stay up to date with our last videos and more lessons, make sure to subscribe to this RU-vid channel:
goo.gl/Y6DRiN
=============================
TWEET THIS VIDEO ctt.ac/e23TN
=============================
▶ SIMATIC ET 200SP Manual
sie.ag/2ZHulIz
=============================
Like us on Facebook: / therealpars
Follow us on Twitter: / realpars
Follow us on LinkedIn / realpars
Follow us on instagram / realparsdotcom
#RealPars #ET200SP #ET200SPBaseUnit

Опубликовано:

 

5 авг 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 254   
@sameersalem1827
@sameersalem1827 5 лет назад
as always, another great work. thank you all realpars team ❤️
@realpars
@realpars 5 лет назад
Thanks for your support, Sameer!
@thorsten888
@thorsten888 4 года назад
I knew all of this, but this was the best explaining instruction I've found to date and I will bookmark it as a reference to my colleges when they have their first Siemens project.
@realpars
@realpars 4 года назад
Hi Daniel, Thanks a lot for your kind compliment! We are always extremely happy to hear such positive feedback! If you ever have any questions, feel free to reach out to us. Happy learning!
@derina.maleek9408
@derina.maleek9408 5 лет назад
thats why every week i hold my breathe and wait realpars video thanks#
@realpars
@realpars 5 лет назад
You are welcome, Derin! :)
@shivam5331
@shivam5331 3 года назад
Thank you, I wish god give more power to you for educating people
@melquiadesdelgadoramirez680
@melquiadesdelgadoramirez680 5 лет назад
I used to work for the instrumentation department at a consultant office, where we designed an offshore gas compression plant within a 4-level plattform. We needed to install Remote I/Os to later connect them to the main PLC. The control system arquitecture included such RIOs spreaded everywhere, linked to the main control system through profinet cables. Definetely, RIOs are the best way to interconnect field instrumentation to main control system. Thanks RealPars for sharing such a valuale information.
@realpars
@realpars 5 лет назад
You are very welcome, Melquiades! Thanks a lot for sharing your experiences and knowledge with us.
@beqeb5700
@beqeb5700 2 года назад
wow this video covered all questions that appeared in my mind. Great job, Realpars team !
@realpars
@realpars 2 года назад
Our pleasure! Happy to hear that.
@nightking9615
@nightking9615 2 года назад
I love you REALPARS Team, you are AWESOME 👍❤👍!
@realpars
@realpars 2 года назад
Thanks a lot, Sultan!
@barbaluti
@barbaluti Год назад
Amazing video. Siemens' documentation is hopeless at explaining anything in a clear fashion. I'm very thankful for your help.
@realpars
@realpars Год назад
Glad it was helpful! Thank you for sharing.
@james77011
@james77011 4 года назад
this is an amazing video... make me want to study PLCs even more
@realpars
@realpars 4 года назад
Amazing to hear that, James! We have a whole course library (400+) full of video courses. You might want to have a browse around as I am sure this is of your interest. bit.ly/30AVJaR Just to let you know, that we also have a free course on PLC Hardware bit.ly/2XnnUrF Happy learning!
@harshanamaduranga1412
@harshanamaduranga1412 3 года назад
I am a electrical engineering student. this video series is more valuable. thank you.
@realpars
@realpars 3 года назад
That's amazing to hear! Thanks for sharing
@ulf8468
@ulf8468 4 года назад
Great introduction. A video about the differences of the base units would be interessting too.
@realpars
@realpars 4 года назад
Hey! Thanks for your comment and your suggestion. I will pass this on to our course developers! Thanks for sharing and happy learning!
@user-uu6dg7tw2u
@user-uu6dg7tw2u 4 года назад
A billion thank u for making this video. I'll keeping touch ur channel~
@realpars
@realpars 4 года назад
You are very welcome!
@user-ic5re6so6e
@user-ic5re6so6e 3 года назад
Absolutely amazing, thank you
@realpars
@realpars 3 года назад
Glad you enjoyed it!
@pranaychauli233
@pranaychauli233 4 года назад
Your generosity is at extreme level. Lots of thanks.. can I get some assistance on ABB 800xa compact control builder online editing
@amankumarshrivastava2380
@amankumarshrivastava2380 4 года назад
Love this.. specially it's animation & mobile favourable layout
@realpars
@realpars 4 года назад
Happy to hear that! Thanks for sharing!
@cyrox1859
@cyrox1859 5 лет назад
I have been working with ET200 for two years and I noticed that the first left base unit was white but until now I did not know the cause thank you so much
@realpars
@realpars 5 лет назад
Great to hear that we helped you clear that up. Happy learning!
@vibhasingh4842
@vibhasingh4842 4 года назад
Thanks RealPars for sharing this it's really helpful! Can u plz update the video what exactly is difference between ET200S, ET200SP, ET200M modules & when one is to be opted. It would be very helpful!
@realpars
@realpars 4 года назад
Hi Vibha, Thanks for your comment and your suggestion. I will pass this on to our course developers! Thanks for sharing and happy learning!
@quidao663
@quidao663 5 лет назад
Thank you so much!
@athilaldurry5880
@athilaldurry5880 3 года назад
Many thanks for this wonderful videos
@realpars
@realpars 3 года назад
You are very welcome!
@Qasemzarei
@Qasemzarei 2 года назад
simpliy explained✨, Thanks Real Pars! I should mention the source voltage +24 and -24 make 48V, which technically should be correctet to +24V and 0. Thankx
@realpars
@realpars 2 года назад
Thank you, Qasem!
@shapourjalilyan3356
@shapourjalilyan3356 5 лет назад
Thanks for your video real pars
@realpars
@realpars 5 лет назад
You are very welcome, Shapour!
@andregrobler4393
@andregrobler4393 2 года назад
Thanks, Very good explanation.
@realpars
@realpars 2 года назад
Glad you liked it!
@abdelrahmangomaaabbady
@abdelrahmangomaaabbady 3 года назад
Great work, very helpful thanks very match
@realpars
@realpars 3 года назад
You're very welcome - Abdelrahman!
@ahmedmetwally4911
@ahmedmetwally4911 5 лет назад
Simply W0ooooo0o0w thanks very much :) Ahmed from egypt .
@realpars
@realpars 5 лет назад
Great to hear that, Ahmed! Happy learning.
5 лет назад
Thanks very much, it's very useful.
@realpars
@realpars 5 лет назад
Great! You are very welcome.
@cheloufiyahia5123
@cheloufiyahia5123 5 лет назад
Good information, thanks a lot
@realpars
@realpars 5 лет назад
You are very welcome!
@danishsaleem6402
@danishsaleem6402 5 лет назад
W8ing for your video.. And here it is.., ♥️
@realpars
@realpars 5 лет назад
Happy learning!
@AashishBharat
@AashishBharat 5 лет назад
Absolutely helpful. I love the animation
@realpars
@realpars 5 лет назад
Great compliment, thanks a lot!
@mr.sasani
@mr.sasani Год назад
Very instructive thank you
@realpars
@realpars Год назад
Glad it was helpful!
@amrouche.abdesselam
@amrouche.abdesselam 5 лет назад
Very nice video !
@realpars
@realpars 5 лет назад
Thank you!
@Rooth9056
@Rooth9056 5 лет назад
good job thank you for this video
@realpars
@realpars 5 лет назад
Thank you, Zouhair!
@aymendaly7888
@aymendaly7888 5 лет назад
Informative video thank you
@realpars
@realpars 5 лет назад
You are very welcome, Aymen!
@MuhammadUmar-el1ff
@MuhammadUmar-el1ff 5 лет назад
Superb, outstanding work......
@realpars
@realpars 5 лет назад
Thank you, Muhammad!
@MuhammadUmar-el1ff
@MuhammadUmar-el1ff 5 лет назад
If possible plz make some videos on delta plc also....
@DemetriusHazardus
@DemetriusHazardus Год назад
Cool!
@adeelyousuf8373
@adeelyousuf8373 3 года назад
Super cool video
@realpars
@realpars 3 года назад
Great - thanks for support!
@yehtutnaung7164
@yehtutnaung7164 5 лет назад
Thanks again.
@realpars
@realpars 5 лет назад
You are very welcome!
@charliechimples
@charliechimples 4 года назад
Great vid. Thanks for sharing. 🐵
@realpars
@realpars 4 года назад
You are very welcome!
@alibilgin9758
@alibilgin9758 3 года назад
clear description
@realpars
@realpars 3 года назад
Great to hear that, Ali!
@aqx1729
@aqx1729 5 лет назад
Best video😍
@realpars
@realpars 5 лет назад
Thank you!
@gadoragadoraa4774
@gadoragadoraa4774 2 года назад
1000 thanks
@shapourjalilyan3356
@shapourjalilyan3356 5 лет назад
Keep going
@vissusadhh7787
@vissusadhh7787 2 года назад
Excellent sir
@realpars
@realpars 2 года назад
Thank you!
@user-rl8yb7tb1k
@user-rl8yb7tb1k 5 лет назад
Many thanks
@realpars
@realpars 5 лет назад
You are very welcome, Abdo!
@morningstar8954
@morningstar8954 2 года назад
Thank you so mush
@realpars
@realpars 2 года назад
You're welcome!
@tkwhitey488
@tkwhitey488 4 года назад
I ordered and tried to install a new replacement 4wire engine speed sensor AI module - Siemans6ES7 1344GB62-0AB0. The key on the back of the replacement AI module faces at 7oclock, where as the old one faces at 4 oclock. Therefore the base plate will not except the new AI due to the key direction. How can I make this compatible? Is the key direction on the base plate interchangeable? Thanks.
@sabarikrishnan5602
@sabarikrishnan5602 5 лет назад
simple and convenience
@realpars
@realpars 5 лет назад
Great! Happy learning.
@vorapobautomation9760
@vorapobautomation9760 5 лет назад
Thank you Good
@realpars
@realpars 5 лет назад
You are very welcome!
@_Iokanaan_Marusidze_
@_Iokanaan_Marusidze_ Год назад
Thanks 👍
@realpars
@realpars Год назад
You're very welcome!
@tarekmohsen7572
@tarekmohsen7572 2 года назад
Thank you
@realpars
@realpars 2 года назад
You're very welcome!
@nazishkhan3348
@nazishkhan3348 4 года назад
Hey.. Thank you for such a nice. Can you please make a small vedio explaining the difference between ET 200S, ET 200SP, ET 200M etc , I mean all the series. Which explains what is difference, where we need?? Can you please make such vedio.
@realpars
@realpars 4 года назад
Hey Nazish! Thanks for your comment and your suggestion. I will pass this on to our course developers! Thanks for sharing and happy learning!
@bilaliqbal8291
@bilaliqbal8291 5 лет назад
Your videos are nice bro!!! Plz make video on DeltaV Dcs.....
@realpars
@realpars 5 лет назад
Thank you, Bilal! I will forward your topic suggestion to our creator team. Happy learning!
@SantoshPratyangra
@SantoshPratyangra 5 лет назад
Awesome
@realpars
@realpars 5 лет назад
Thank you!
@ThuanAutomation
@ThuanAutomation 4 года назад
It very helpful.
@realpars
@realpars 4 года назад
Great to hear that, Thuan!
@ThuanAutomation
@ThuanAutomation 4 года назад
@@realpars thank you
@bensenoussitahri1327
@bensenoussitahri1327 Год назад
Great and informative video, can you make a videos about the control of the stepper motor modules and servo drive?, specially b&r
@realpars
@realpars Год назад
Thanks for your kind support! I will happily go ahead and forward your topic suggestion to our course developers for possible future video courses. Thank you for sharing, and happy learning!
@southyouths1204
@southyouths1204 4 года назад
@realpars team great work Kindly post video how to configure the ET200SP With CPU.
@realpars
@realpars 4 года назад
Hey! Thanks a lot for your support, great to hear that! I will forward your topic suggestion to our creator team. Thanks for sharing!
@kamakshiprasanth508
@kamakshiprasanth508 4 года назад
thanks for uploading this video. can you make a video on Dnp3 protocol. please..
@realpars
@realpars 4 года назад
Hey Kamakshi! Thanks for your comment and your suggestion. I will pass this on to our course developers! Thanks for sharing and happy learning!
@JuanRodriguez-pv1ym
@JuanRodriguez-pv1ym 5 лет назад
Very good content, thanks for the video!!
@realpars
@realpars 5 лет назад
Happy to hear that, Juan!
@souvikbanerjee9247
@souvikbanerjee9247 5 лет назад
Thanks a lot for the demonstration. Max.how many cards (B0)can be connected at right side with A0?
@realpars
@realpars 5 лет назад
It depends on the power requirements of the B0 units. Most A0 base units can pass no more than 10A to the cards on the right.
@Maxxwellification
@Maxxwellification 5 лет назад
Good Video! Can I use the ET200 also completely standalone? Just in terms of functionality do I have any disadvantages compared to a 1500?
@realpars
@realpars 5 лет назад
The ET200SP family of I/O can be used ins a standalone I/O rack, but a separate PLC CPU unit, like an S7-1500 or S7-300 series PLC is still required. The S7-1500 can be used with an integrated ET200MP series I/O subsystem or, with a Profinet or Profibus-DP link, the ET200SP I/O subsystem can be used as a remote I/O solution.
@IK-qu9hw
@IK-qu9hw 3 года назад
On one white power module how many input output modules can be connected??
@discutiibiblice
@discutiibiblice 2 года назад
lmao, no. ET200 is not a PLC, it's just a Bus Collector. You still need a PLC.
@user-np4pe4ew5q
@user-np4pe4ew5q Год назад
Thanks for the great content. It's always enjoyable to learn from your channel. Just a quick question: By connecting the dark base unit to the light one, do we create a 24VDC power supply on the last row of the dark base unit terminal (red and blue pins)? Is it possible to use them as a power supply for field devices when necessary?
@realpars
@realpars Год назад
Hello Ehsan Vazirinahad, Thank you for your question. Because I don’t know what application you are working on, I am providing for your review and learning two links below from Siemens, which should have all the information you need with your projects. The first link is the ET-200 SP manual, and the second is software in the cloud that Siemens provides for you to create your hardware project for free. You can also download this information to your computer. You might have to create an account with Siemens for free to use their website on some items they allow you to download. Happy learning from RealPars! support.industry.siemens.com/cs/document/59753521/simatic-et-200sp-baseunits?dti=0&lc=en-US www.siemens.com/global/en/products/automation/topic-areas/tia/tia-selection-tool.html
@user-np4pe4ew5q
@user-np4pe4ew5q Год назад
@@realpars Thank you for the provided links . Your channel is incredible.I learnt a lot from it. Keep up the fantastic work.
@fetimisme6873
@fetimisme6873 7 месяцев назад
merciiiiiiiiiiiiiiiiiiiiiiiii
@realpars
@realpars 7 месяцев назад
Our pleasure!
@prataps2341
@prataps2341 4 года назад
Do we have to download any kind of program into the head module or remote I/O unit? How this remote I/O module is instructed to send and receive data from the main controller?
@realpars
@realpars 4 года назад
No. When you add the ET200SP to the hardware configuration from the hardware catalog, the GSD file for the rack is added to the project. This file tells the CPU how to interpret the data string that is returned from the ET200SP and how to format the commands the CPU sends to the remote I/O head module.
@osamanasher2550
@osamanasher2550 Год назад
Dears, I like this vidio too much I need clarification for two points 1 - based on given cpu information Is there limit to connect no of remote I / O.? 2 - for given nos of rote I / O and plcs in different locations how can decide following issues :- Switch specifications, Server specifications and data warehouse specification based on phenomena that I will save whole Data in database for further analysis Thank you in advance for your support and clarifications Warm regards
@realpars
@realpars Год назад
Yes, different CPU models allow for differing number of racks/IO cards/IO points. For your CPU, download the CPU documentation from Siemens. For example, the technical specs for an S7-1214C can be found here: support.industry.siemens.com/cs/pd/255094?pdti=td&dl=en&lc=en-WW. The process image table and output image tables are each 1024 bits (1 kB), so this CPU can have up to 1024 inputs and 1024 outputs. There are limitations to the numbers of nodes that are connected (16 for this CPU, so there are limits for each type of remote I/O node that may limit the total number of I/O available. The only limitation connecting switches, servers, PLCs via Profinet is the cable lengths (
@hardeepreddy6606
@hardeepreddy6606 5 лет назад
Good video, can you please make a video on the ring and chain topologies of PLC's
@realpars
@realpars 5 лет назад
Thanks for the topic suggestion, I will definitely go ahead and forward this to our creator team. Happy learning!
@faezsobry5132
@faezsobry5132 3 года назад
Hi.. Thank you for the video explanation. But i have some concern on the architecture of connecting S71500 an ET200SP. Since all the I/O devices are connected to the ET200SP, all the programs should be done on the ET200SP right? Then why do we still need the S71500??
@realpars
@realpars 3 года назад
It depends on the model of the ET200SP system you purchase. There are ET200SP models that include an IM module and can be a Profibus slave node to an S7-1500 or connect to an S7-1500 Profinet master. An example would be an IM 155-6 PN BA, which supplies a typical remote I/O interface using ET200SP modules. There is also a line of ET20)SP CPU"s, which can be programmed as stand-alone PLC and I/O, combined onto the same ET200SP backplane. ET200SP CPU's have small amounts of program memory (150kb - 750kB) as compared to a larger S7-1500 The ET200SP is essentially a smaller and less expensive S7-1500. A typical model number for an ET200SP CPU si S7-1510SP-1 PN.
@_stardust__
@_stardust__ 3 года назад
hello! Can you please share which software you use to prepare the animations?
@realpars
@realpars 3 года назад
Hi Dipankar, Thanks for your comment! I am actually not sure about this as this is done by our graphic and animation department.
@PHEINER123
@PHEINER123 4 года назад
Great video. Though check narration around 7:20min. "Light modules feed dark modules to the right." but then "Dark modules receive power from light module to the right." Should it be left?
@realpars
@realpars 4 года назад
Yes. Light-colored modules have power connections and pass power to the right. Dark-colored modules accept power from the left.
@ikramantaki
@ikramantaki 5 лет назад
Hi, nice video just like always. What about a SINAMICS course???
@realpars
@realpars 5 лет назад
Hi Rulo, Thanks for your support! Happy to hear that you enjoyed this course video. I will definitely go ahead and forward your suggestion to our creator team. Thanks for sharing that with us. Happy learning!
@yassinal-nuaimee1204
@yassinal-nuaimee1204 11 месяцев назад
great video thanks a lot! How did you make the schematics tho?
@realpars
@realpars 11 месяцев назад
Hi there, Thanks for your comment, regarding your question - I am actually not sure about that, as that is something created by our Graphic and Animation department.
@calvinceogara2088
@calvinceogara2088 4 года назад
Hi, Can the dp et 200m be configured with i/o and then programmed without using cpu?
@realpars
@realpars 4 года назад
You can configure the entire system offline including ET200 and the DP network. However, in order to download the configuration, you will need the CPU installed. The ET200M gets is commands from the CPU and you will not be able to monitor I/O without the CPU in place. This is because a DP network requires a master node, which is always the CPU.
@MicroBitz
@MicroBitz 4 года назад
Hi, i have a problem, i dont have acces to I/O data, i have a dark BU in slot 1 is that a problem if i dont have the AC I/O module or an AI Energy Meter as the first I/O module?
@realpars
@realpars 4 года назад
You will need to have a module to the left of the dark-colored BU's that can pass power to the dark-colored modules. Otherwise, the dark BU's are not powered.
@MicroBitz
@MicroBitz 4 года назад
@@realpars Your video helped me a lot, actually that is what i did, it worked perfectlly! thank you, i want to point out that i had a safety module instaled in the dark colorred one, and it took away the eeprom, i needed to pull it out and put it back on the safety module because i could'nt assign the profisafe name again...
@bramvandenbempt6914
@bramvandenbempt6914 2 года назад
should you be using cable shoes with these terminals or is it better to use bare wire ?
@realpars
@realpars 2 года назад
I like to use wire ferrules (cable shoes) at the ends of stranded wire. That keeps the installation neat and makes it easier to insert the wires into the terminals.
@IK-qu9hw
@IK-qu9hw 3 года назад
Very helpful video. On one white power module how many input output modules can be connected??
@realpars
@realpars 3 года назад
The answer is as many modules as you can add (up to 32 for an ET200SP interface module or 64 for an ET200SP CPU module) and not deplete the power supply. Each module type requires a different amount of current to operate. You would want to add a power module if you need to isolate circuits or use different voltages for the I/O cards (as in separation 24VDC I/O from 120VAC I/O).
@IK-qu9hw
@IK-qu9hw 3 года назад
@@realpars ok so depends on current capacity. Thank you so much for your reply.
@habibuk3024
@habibuk3024 5 лет назад
GREAT
@realpars
@realpars 5 лет назад
Thank you, Habib!
@syedmadani9112
@syedmadani9112 5 лет назад
Informative video.
@MrAmjad0070
@MrAmjad0070 2 года назад
Don't forget to include server module program to the last slot in your configuration. Without it, you will not have successful communication with the device.
@realpars
@realpars 2 года назад
Great addition! Thank you for sharing.
@shubhammatekar1173
@shubhammatekar1173 4 года назад
Can you make videos on Communication protocols like- Foundation Fieldbus, HART, Profibus ?
@realpars
@realpars 4 года назад
Hi Shubham, Thanks for sharing your suggestion with us! I have sent this over to our course developers. Happy learning!
@sandychoudhari7106
@sandychoudhari7106 3 года назад
Great video In one batch processing plant having 250 I/O can I use ET200SP with S7-1200Cpu? Or S7-1200 1415 with traditional I/O cards will be enough. How many exactly I/O ET1200SP supports? S7-1200 1415 support 8 channel I/o only (DI DO AI AO). Which will be more cost-effective? System has some RTD module as well.
@realpars
@realpars 3 года назад
Great question! First, how close are the field sensors and switches from where the PLC is? Many times, the choice of whether to use remote I/O (like ET200SP) or just local I/O depends on the cost of wiring and installation. If your 250 I/O are an average of 100 ft from the PLC, you will need >2500ft of wiring. If you can locate ET200SP "racks" closer to the I/O itself, then there is a substantial cost saving in wiring, conduit, and labor to install these items. As far as the ET200SP is concerned, each ET200SP station can support up to 64 cards. Your S7 PLC model can support up to 8 modules, which indicates you likely will need to use ET200SP I/O to meet your I/O requirements. You can certainly use both. ET200SP is best integrated via Profinet, so you can have many racks of ET200SP located to minimize wiring and installation costs. Both ET200SP and SM12xx modules (used as S7-1200 connected I/O cards) can support the full range of digital and analog signals in your system. I would suggest enlisting the help of a local systems integrator to help you determine the most effective way to proceed.
@sandychoudhari7106
@sandychoudhari7106 3 года назад
@@realpars Thank you so much to RealPars for this detail reply ❤ I got really clear picture now Plant I/Os are situated very near to each other not more than 60ft from DCS/PLC room I will combine S7 1200 with ET200SP to get desired no. Of I/O I will use full 8 channel of S7 1200 including RTD and remaining I will include in ET200SP
@SebastianVJ
@SebastianVJ 4 года назад
Can you please tell what is the difference between the two ports 1L+and 2L+ in this CPU power supply?
@realpars
@realpars 4 года назад
These ports allow for 2 separate 24VDC circuits to be wired. 1L+ and 2L+ are both 24VDC sources, so one circuit can be formed with 1L+ (24VDC+) and common, and the second circuit can be formed with 2L+ (also 24VDC+) and common.
@sebenzilemoloi259
@sebenzilemoloi259 2 года назад
Can you use profibus for comms on the ET200SP or is it only profinet?
@realpars
@realpars 2 года назад
Yes, there is an option for a ProfibusDP communication module. Other fieldbuses are also an option.
@bratnaji196
@bratnaji196 4 года назад
Thank for the vedio.. How many darkcolored module can be powered up by using single light color module??
@realpars
@realpars 4 года назад
Twelve (12) to the right of the light-colored module.
@bratnaji196
@bratnaji196 4 года назад
@@realparsThank you for answer. is that include Digital I/O and analoge I/Os
@mohamedabdulla6483
@mohamedabdulla6483 5 лет назад
Waiting for your VFD third part video Can you please upload a VFD parameter setting video
@realpars
@realpars 5 лет назад
Thanks, Mohamed, I will forward your request to our creator team. Happy learning!
@eliekhananya1551
@eliekhananya1551 5 лет назад
@@realpars this is a much needed video, thanks!
@vishnuganga223
@vishnuganga223 Год назад
Did this remote iI/O need extra enclosure to mount?
@realpars
@realpars Год назад
ET200SP hardware is rated as IP20, so it will require a panel enclosure in any wet or humid environment.
@Mr.JayantaJi
@Mr.JayantaJi 5 лет назад
I have one question why you not use any PM(power module)?
@realpars
@realpars 5 лет назад
The power supply is part of the head module. Power wiring is connected at the lower left of the head module. A separate power module is not required.
@sahilrockstar2008
@sahilrockstar2008 2 года назад
Hi.currently we are using ET 200 SP 4ch, 2A, DO card (18nos.) With Profinet IM module. Everything is working fine the only problem is the heating. When all DOs are turn ON the PLC temperature I checked was 45 to 48 deg. C. Is this a normal? Because even with this temperature my operation is working fine. Load on each module is also less than 5A.
@realpars
@realpars 2 года назад
I have heard of this happening before. There may be a number of causes. Is this ET200SP rack in a closed panel? You may need to ventilate or provide internal panel cooling, especially if the power supply feeding the output circuits is also in the panel. I may also be a grounding issue, as electrical noise can be dissipated as heat. Try grounding the DIN rail on which the ET200SP is mounted, and make sure the power supply is properly grounded. Also, insure that there is at least 20mm clearance above and below the ET200SP rack and at least 10mm on each side. Lastly, ensure the power wires to the CPU are at least 14AWG and that there are no loose connections.
@sahilrockstar2008
@sahilrockstar2008 2 года назад
@@realpars Thank you for your prompt reply. we kept PLC in close panel with Power supply. actually we are supplying IP65 rated panel due to this fans are not provided for ventilation. 45mm empty space we maintain above and below PLC. Earthing we checked it was 0.85ohm. One more question we saw some residual voltage(6.9V) at the DO card when DO was not forced is because PNP?
@RakeshYadav-sx8js
@RakeshYadav-sx8js 5 лет назад
Hello sir I follow your all vedios. Pls share one more What is relationship bwn S71200 and ET200S n ET200SP S71500 and ET200S n ET200SP HOW AND WHEN WE USE AND MAKE THE BILL OF MATERIAL WHAT IS INTERFACE AND HOW WE SELECT IT? POWER MODULE TERMINAL MODULE AND ELECTRICAL MODULE.
@realpars
@realpars 5 лет назад
Hi Rakesh, Thanks for the topic suggestion, I will definitely go ahead and forward this to our creator team. Happy learning!
@user-ji4jj8vg5g
@user-ji4jj8vg5g Год назад
how about et200sp im155-6mf hf, I didn't find it in the library.
@realpars
@realpars Год назад
Hi there, Thank you for your question! You can find more about the Siemens IM155 here: support.industry.siemens.com/cs/start?lc=en-GB Happy learning!
@bartoszri
@bartoszri 2 года назад
When I should use a power module attached to BU ? [6ES7138-4CA01-0AA0]
@realpars
@realpars 2 года назад
The power module (6ES7138-4CA01-0AA0) has been phased out. It was used in the ET200S product line, which has been replaced by ET200SP, as shown in this video. There is one power module available for the ET200SP (6ES7136-6PA00-0BC0) which is used only if a fail-safe power supply with diagnostics is required.
@abinashbhuyan7535
@abinashbhuyan7535 3 года назад
Can we connect an instrument on the light colored base unit??
@realpars
@realpars 3 года назад
Sure, just place an Analog Input card on the first (light-colored) base unit. The difference in the base units is only in how power is distributed between the modules. Each type of base can take any of the I/O card types.
@skripsidcs7671
@skripsidcs7671 3 года назад
question. i'm currently working with this ET200SP and i've found a problem, once the digital output is activated it should be just showing a DC voltage, but its not. i dont know why the output also contain an AC voltage, amount is 6 to 9 V AC in measurement .. can someone help me with that?
@realpars
@realpars 3 года назад
It appears that you have mixed DC and AC cards in the same power section. Whatever voltage/power source you are using to power a light-colored (Type A0) base unit, that same voltage will flow to each dark-colored unit to the right. If another Type A0 unit is installed, it creates another power zone with the voltage connected. This allows DC and AC modules to be located on the same rack. But be careful not to mix DC and AC cards in the same section or power DC cards with AC voltage or vice versa.
@Mltnzle
@Mltnzle 6 месяцев назад
can this I/O module be used only with S7 1500? oder is it also possible with S7 1200?
@realpars
@realpars 6 месяцев назад
Thank you for your inquiry. Indeed, it is possible. Siemens introduced this functionality in version 12, approximately a decade ago. With the latest version, 1200, you have even more capabilities at your disposal. I suggest visiting the Siemens support website to explore the full range of features. Note that in some instances, you may need to register before downloading. support.industry.siemens.com/cs/start?lc=en-US Happy learning!
@Mltnzle
@Mltnzle 6 месяцев назад
@realpars thank you for detailed answer
@carlosvidal8244
@carlosvidal8244 3 года назад
Hey bro, what´s the model ET200SP in your video?
@realpars
@realpars 3 года назад
Hi Carlos, Our apologies for the delay in our response! We are using the following ET200SP, SIMATIC ET 200SP, BaseUnit Type A0 - 6ES7193-6BP00-0BA0. You can find more details about that over here bit.ly/3e40Jxf Hope this helps! If I can be of any further assistance, please let me know - I’m more than happy to help!
@ilyadeykin3915
@ilyadeykin3915 5 лет назад
Those little round things at the base units. What are they for? Some kind of lock?..
@realpars
@realpars 5 лет назад
Yes, those are spring-lock wire connectors. The other type of wire connectors are screw-type. On the base unit, the wiring connections are used for the power connections (24VDC power).
@ilyadeykin3915
@ilyadeykin3915 2 года назад
@@realpars Greatly thanks you for your answer.
@user-ji4jj8vg5g
@user-ji4jj8vg5g Год назад
I want to know that if this et200sp can only be remote io?
@realpars
@realpars Год назад
Hi there, Thank you for your question! The ET200 system has been around from Siemens for a long time. And many improvements have been done to these modules. Here is a link you can review for your learning support.industry.siemens.com/cs/start?lc=en-GB Happy learning
@2574400
@2574400 4 года назад
Can you make videos on Siemens smc 20/30/120 and NCU unit
@realpars
@realpars 4 года назад
Hey Hitanshu! Thanks for your comment and your suggestion. I will pass this on to our course developers! Thanks for sharing and happy learning!
@dennisortozar7320
@dennisortozar7320 5 лет назад
Any other way to send signals from Remote I/O to PLC in that such distance? how about wireless? what device I can use if i want to make wireless from Remote I/O to PLC?
@realpars
@realpars 5 лет назад
There are a number of ways to send Remote I/O signals over a long distance. Wireless, as you mention, is one, but it will be limited by the quality and number of repeaters and gateways that are part of the mesh network. Another way is fiber optics, which can be run for up to 23km. Another way, that is often used for remote metering sites is cellular or RF signal. How far do you need to send the signals in your system?
@dennisortozar7320
@dennisortozar7320 5 лет назад
@@realpars Can i use RF to transmitting signal in 3miles? Can you give a specific devices/brand I can used?
@dennisortozar7320
@dennisortozar7320 5 лет назад
@@realpars can you make a video with a RF signal, range limitation? If you have a Video can I have a link so that I can watch. Thanks RealPars.
@bahurudeen7147
@bahurudeen7147 5 лет назад
Please sir upload the video for new HMI input output installation
@realpars
@realpars 5 лет назад
Thansk for the topic suggestion! I will go ahead and forward this to our creator team.
@apothicaris3770
@apothicaris3770 3 года назад
Hello, Are the ET200S I/O modules compatible with ET200SP ?
@realpars
@realpars 3 года назад
Yes, but each product is different. The ET200SP product features a processor to which ET200SP I/O cards are attached with backplane connectors to form one "rack". ET200S I/O is distributed I/O with no processor in the "rack", and requires an IM card to join the I/O to a Profinet or ProfiBus network.
@apothicaris3770
@apothicaris3770 3 года назад
@@realpars FYI : ET200S modules are not compatible with ET200SP modules. Base units are not the same etc...
@Yosuke94
@Yosuke94 3 года назад
Great vid, but why sensor was plugged to the DQ? :C
@realpars
@realpars 3 года назад
Good catch. The DQ module is a digital output module, to which actuators or other output devices, such as relays, are wired.
@prashantthapa276
@prashantthapa276 3 года назад
How many no's IO modules can be connected with one power module?
@realpars
@realpars 3 года назад
You add modules up to the point where the modules use all available power from the power module. Each type of I/O module requires a different amount of power. Typically, this is 12 - 15 modules.
@TheLukebadger1
@TheLukebadger1 4 года назад
Is this compatible with s7-300?
@realpars
@realpars 4 года назад
Yes, definitely. Check with Siemens on compatibility of version numbers with your CPU, but in general ET200SP is one of the most popular remote I/O series used with S7-300.
Далее
What are PID Tuning Parameters?
7:33
Просмотров 296 тыс.
What is IO-Link?
9:23
Просмотров 274 тыс.
Редакция. News: 128-я неделя
57:33
Просмотров 1,8 млн
Это реально работает?!
00:33
Просмотров 1,3 млн
What is IP Rating? (Ingress Protection Rating)
7:13
Просмотров 255 тыс.
What is the Difference between Profibus and Profinet?
5:28