What is IO-Link? 

RealPars
Подписаться 1,1 млн
Просмотров 272 тыс.
50% 1

▶ C'mon over to realpars.com where you can learn PLC programming faster and easier than you ever thought possible!
=============================
▶ Check out the full blog post over at
realpars.com/io-link/
=============================
In this video, we’re going to learn about IO-Link. IO-Link is a communications protocol that works point-to-point.
A point-to-point communication connection is a communications connection between two separate endpoints or nodes.
IO-Link is bi-directional meaning it works two ways and works over a short distance.
It is primarily used to communicate with sensors and actuators in plant or factory automation processes.
Sensors and actuators are usually connected via Fieldbus connections, allowing them to be in remote locations.
With IO-Link, the field devices, such as actuators or sensors, connect to a ‘Master’ device that communicates to a controller, usually a PLC, or Programmable Logic Controller.
The connection between the IO-Link Master and the field device is established via an unscreened 3 wire cable, no more than 20 meters long.
The IO-Link master is capable of processing digital signals and analog values.
Its versatility means it is capable of integrating into existing systems and can communicate using the industry-recognized Profinet, Profibus, and Modbus, to name a few.
An IO-Link master can have several IO-Link ports or channels.
An IO-Link device can be connected to each port, meaning IO-Link is a point to point communication and not a Fieldbus.
The IO-Link protocol allows an IO-Link port to be operated in one of four different operating modes.
The first mode is the IO-Link mode. This means that the port is used for IO-Link communication.
The second mode is the DI mode. This means that the port acts in the same way as a digital input device.
The third mode is the DQ mode. This means that the port acts in the same way as a digital output device.
The fourth mode is Deactivated. This means that the port is not assigned to any other modes and is reserved for when the port is unused.
IO-Link is a very robust communication system That operates using 24 volts.
Transmission errors can occur for a number of reasons, in general, a cable fault or a power surge can temporarily interfere with transmissions.
An IO-Link device has 4 types of transmission. “Process Data”, “Value Status”, “Device Data”, and “Events”.
The Process Data is considered as the latest state of the sensor or actuator, such as speed. Process Data is transmitted cyclically, which means automatically, at regularly defined intervals.
Up to 32 bytes of process data can be processed, and it’s defined by the high-level controller.
The Value Status indicates whether the Process Data is valid or invalid and is transmitted along with the Process Data cyclically.
The Device Data holds detailed information about a device.
Device Data is transmitted acyclically, at the request of the IO-Link master. Device Data can be read from the device, but also written to.
A device is able to trigger an event, which in turn signals the presence of an Event to the IO-Link Master. An example of an event is an error or warning message, for example, a short circuit, or a device that is overheating.
This information can be used to display indicators or messages on HMI devices, such as error messages signaling a wire break or a communication failure.
An IO-Link device transmits Process Data and Value Status periodically, at a regular defined interval. This is called cyclic transmission.
Device Data, such as diagnostics and Events are transmitted when they are needed. This is called acyclic transmission.
Getting the set up of the IO-Link configuration correct is heavily dependant on the device that is being communicated with, so checking the field devices' instructions is a necessity to be able to communicate correctly.
Don’t worry though, once it is set up, they are very easy to maintain, and often work seamlessly with no additional work required.
=============================
Missed our most recent videos? Watch them here:
realpars.com/plcnext/
realpars.com/spool-valve-sche...
realpars.com/dcs-vs-scada/
=============================
To stay up to date with our last videos and more lessons, make sure to subscribe to this RU-vid channel:
goo.gl/Y6DRiN
=============================
TWEET THIS VIDEO ctt.ac/U71p6
=============================
Like us on Facebook: / therealpars
Follow us on Twitter: / realpars
Follow us on LinkedIn / realpars
Follow us on Instagram / realparsdotcom
#RealPars #Automation #IO-Link

Опубликовано:

 

11 июл 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 166   
@walidben8264
@walidben8264 4 года назад
Thanks a lot, im an automation technician, and i learned a lot of thing, the simplicity of this videos are great, dont give up guys we support you.
@realpars
@realpars 4 года назад
Great to hear that, Walid!
@ricardosolanofadul2541
@ricardosolanofadul2541 Год назад
One of the best and concentrated explanations i could find about iolink, thanks.
@realpars
@realpars Год назад
That's amazing, thank you for sharing, Ricardo!
@Jarito1903
@Jarito1903 4 года назад
This channel ist fantastic, Thank you so much
@realpars
@realpars 4 года назад
Great to hear that! Thanks for sharing that with us!
@billigerfusel
@billigerfusel 4 года назад
Worked with io-link already. Couldn't complain so far.
@ratnesh12100
@ratnesh12100 3 года назад
REALPar is boosting my knowledge.. Thanks a lot boss..
@realpars
@realpars 3 года назад
That's amazing! Thanks for sharing.
@johanburger4454
@johanburger4454 2 года назад
Loves this channel. Going to subscribe to the courses in the next few weeks. I'm hoping once i complete everything on their website and obtain all the certificates then i can get a job in automation. ♥️
@realpars
@realpars 2 года назад
We're very happy to hear that, Johan! If you have any questions or concerns in the meantime, please do not hesitate to contact us at any time - we're more than happy to help!
@jeyhop
@jeyhop 4 года назад
thank u a lot for the information :D i like ur channel cuz u listen to ur followers ^^ keep up the good work
@realpars
@realpars 4 года назад
Thanks for your kind support, Khadir! Let us know if you have any questions along the way.
@sonubawa100
@sonubawa100 4 года назад
A must channel for every automation person
@realpars
@realpars 4 года назад
Thanks for your support, Kapoor!
@mubarishussain3696
@mubarishussain3696 4 года назад
Fantastic videos. Really appreciate it .
@realpars
@realpars 4 года назад
Thanks for your support, Mubaris!
@hichemchawi4498
@hichemchawi4498 4 года назад
It's amazing tutorial , thank you so much
@realpars
@realpars 4 года назад
Thanks a lot!
@lukassinning7062
@lukassinning7062 4 года назад
Thank you for explaining 👌
@realpars
@realpars 4 года назад
You are very welcome, Lukas! Let us know if you have any questions!
@chavanrahul5418
@chavanrahul5418 4 года назад
Great animation Thank you 😊
@realpars
@realpars 4 года назад
Thanks a lot, Chavan!
@takuratobias1592
@takuratobias1592 4 года назад
thank you for the wonderful information.
@realpars
@realpars 4 года назад
You are very welcome, Takura!
@frontiermarvin71
@frontiermarvin71 3 года назад
Im new on this stuff !! Love to learn thank you !
@realpars
@realpars 3 года назад
Great to hear that!
@migza.4750
@migza.4750 4 года назад
Nice Sir! Line maintenance here love your videos more power....Godblez!
@realpars
@realpars 4 года назад
Great to hear that! Thanks for sharing your positive feedback with us!
@akeelekram
@akeelekram 4 года назад
I really like it , much appreciated.
@realpars
@realpars 4 года назад
Happy to hear that, Akeel! Thank you!
@timryder4036
@timryder4036 2 года назад
Very helpful! Thank you
@realpars
@realpars 2 года назад
Glad it was helpful!
@dotex2809
@dotex2809 2 года назад
Thanks a lot
@realpars
@realpars 2 года назад
Thanks for being with us for so long! We appreciate that
@bendixersoftwares6434
@bendixersoftwares6434 3 года назад
Super helpful! Subscribed
@realpars
@realpars 3 года назад
Awesome, thank you!
@jimbass924
@jimbass924 3 года назад
Great video!!!
@KevinNguyen-tw5ml
@KevinNguyen-tw5ml 11 месяцев назад
Thank you very much!
@realpars
@realpars 11 месяцев назад
You're very welcome, happy learning!
@orhirshfeld
@orhirshfeld 4 года назад
Thanks, great video
@realpars
@realpars 4 года назад
Thanks a lot, Hirshfeld!
@javisebille6725
@javisebille6725 Год назад
¡Siempre impecable!
@realpars
@realpars Год назад
Gracias, Javi!
@atibar854
@atibar854 3 месяца назад
Thank you presedent
@abdulmoueenatia5438
@abdulmoueenatia5438 4 года назад
Thanks a lot good job
@realpars
@realpars 4 года назад
You are very welcome! Happy to hear that.
@johngaleleo3273
@johngaleleo3273 Год назад
thank you sir.
@realpars
@realpars Год назад
You're very welcome, John!
@eddahbieddahbi1088
@eddahbieddahbi1088 3 года назад
We need more vedios like this one
@realpars
@realpars 3 года назад
Thanks for your kind support!
@eddahbieddahbi1088
@eddahbieddahbi1088 3 года назад
Well done
@ardentdfender4116
@ardentdfender4116 3 года назад
Really interesting. I've never seen these in the field in process plants. Though there were probably there when I worked in Pharmaceutical Plants on the Manufacturing Lines which had many subsystem PLCs locally and sensors. But at that time I didn't work in Automations just Process Controls at the time. Still very interesting as I didn't know this was a protocol either. I do think i can use one of these for my local PLC Test Bench setup at the office though.
@johanburger4454
@johanburger4454 2 года назад
You will be suprised how many there are of these. I was stunned when i first saw them. Then did my research and found out what they were. But ya that always happens, u tend to panic lol
@AbdoMohamed-ce2uz
@AbdoMohamed-ce2uz 4 года назад
Thanks for making this video Can you make video about Safety integrity Level (SIL)?
@realpars
@realpars 4 года назад
Hey Abdo! Thanks for your comment and your suggestion. I will pass this on to our course developers! Thanks for sharing and happy learning!
@jailsonnascimento8703
@jailsonnascimento8703 4 года назад
Bom vídeo!!!
@realpars
@realpars 4 года назад
Thank you!
@user-wr8he6be3t
@user-wr8he6be3t 3 года назад
Hey i do like that video . Thank you for your channel .. allways improving the level. I am from the crane indestry and i wonder if there is any possibility that your team will make a video about an old method ,ward Leonard system.. i couldn't find any simple info for that.. hopping that maybe you can recommend for some info across the net.
@sareeshkumarsivankutty6904
@sareeshkumarsivankutty6904 4 года назад
Thank you...
@realpars
@realpars 4 года назад
You are very welcome, Sareesh!
@cranelifetv29
@cranelifetv29 Год назад
Very helful vedio, im towercrane technician but i need more information ang learn more about plc, you vedio is very helpfull to me, thank you very much
@realpars
@realpars Год назад
Glad to hear that, happy learning!
@nyinyikyaw
@nyinyikyaw Год назад
nice,thanks
@realpars
@realpars Год назад
Most welcome!
@darbarisid
@darbarisid 4 года назад
Very nice 👍👍👍
@realpars
@realpars 4 года назад
Thanks a lot!
@Olavotemrazaodenovo
@Olavotemrazaodenovo 4 года назад
Excellent
@realpars
@realpars 4 года назад
Thank you, Glaucio!
@CapitanGen
@CapitanGen 2 года назад
You should make a video about OPC UA. I made some proyects to connect Raspberry PI with others embedded devices, sensors, actuators and linked to a DB remotely... but still not with PLC (I don't have but want to buy one). I think it can be a great addition to the channel. Greetings
@realpars
@realpars 2 года назад
Hi Jose! Thanks for your comment and your suggestion. I will pass this on to our course developers! Thanks for sharing and happy learning!
@eddahbieddahbi1088
@eddahbieddahbi1088 3 года назад
Thanks
@bruskqadir6208
@bruskqadir6208 4 года назад
Thanks for making this video. I have a question: do the sensors and actuators need to be specifically designed to work with IO masters or normal sensors and actuators can also be linked to it? thanks in advance
@realpars
@realpars 4 года назад
The sensors and actuators used in any I/O strategy need to have the required interfaces built into the sensor or actuator to be able to use the specified I/O hardware protocol. For example, in the video, the sensors and actuators each had IO Link capability built into the devices. They were then able to connect easily to an "I/O block" that "speaks" IO Link on the field side and Profinet on the PLC network side. To answer your question, "normal" 24VDC or 4-20ma sensors and actuators cannot be connected to IO Link blocks, Profinet interfaces or Profibus interfaces because the sensors and actuators do not have the memory or communication structures embedded to provide the data required by these advanced protocols.
@mashudumawela6992
@mashudumawela6992 4 года назад
Thank you for your videos they are awesome, Sir can you please also elaborate Pepperl + Fuchs AS-Interface Module
@realpars
@realpars 4 года назад
Hey! Thanks for your kind comment and for your topic suggestion. I will pass this on to our course developers! Thanks for sharing and happy learning!
@DrivewayWorkshop
@DrivewayWorkshop 4 года назад
Mashudu, I am an applications engineer for Pepperl + Fuchs USA, if you let me know what you need I can get someone local to talk to you.
@alexsopo9917
@alexsopo9917 4 года назад
we are using IO link almost in every project.
@senkuraj
@senkuraj 4 года назад
Dear Admin, Thanks for wonderful animated video. I want to know the difference between Profibus, Profinet and Modbus. Can you pls post a session on this topic.?
@realpars
@realpars 4 года назад
Hi Senthi! Thanks for your comment and your suggestion. I will pass this on to our course developers! Thanks for sharing and happy learning!
@ratnesh12100
@ratnesh12100 3 года назад
Nice explanation.. Please make video on IEC101
@realpars
@realpars 3 года назад
Hi Ratnesh, Thanks for the topic suggestion, I will definitely go ahead and forward this to our creator team. Happy learning!
@marcogr87
@marcogr87 4 года назад
What about if I have an optical sensor value that I need to detect soon as happen, can I use I/o Link to manage that signal or it is better to connect directly the signal like digital out. Thank you!
@michaelhellen7898
@michaelhellen7898 7 месяцев назад
Seems like a great cost reduction option for customers. Only limiting factor would be the 20m max distance for the M12 cables. Depending where you instruments are located the 20m might not be enougb to get back to the master
@derina.maleek9408
@derina.maleek9408 4 года назад
thanks..
@realpars
@realpars 4 года назад
You're welcome, Derin!
@gerard-nagle
@gerard-nagle 4 года назад
Fantastic videos, just found them. What software is used to create the diagrams etc. Really slick videos, a real credit to the developers
@realpars
@realpars 4 года назад
Hi Gerard, Thanks a lot for your kind comment! Our creator team will be very happy to hear this! Regarding the software that they use, I would honestly not know as this is something our graphic and animation department does. Appreciate your support! Thanks for sharing that with us.
@gerard-nagle
@gerard-nagle 4 года назад
RealPars no problem. Folks are too quick to criticise, and don't take time to recognise excellence. Well done to all
@SusilTech
@SusilTech Год назад
Super video
@realpars
@realpars Год назад
Thanks a lot, Susil!
@SusilTech
@SusilTech Год назад
@@realpars 👍
@eddahbieddahbi1088
@eddahbieddahbi1088 3 года назад
Keep on
@kayan726
@kayan726 11 месяцев назад
Great video. Also please clear doubts also. 1. Is the 3 wire communication represents Tx, Rx & Gnd? 2. Is it possible to communicate btw plc and io link with ethernet? 3. Can I use standard sensors with the IO link?
@realpars
@realpars 11 месяцев назад
Hi there, Thank you for your questions! For question #1, depending on the manufacturer of the sensor will have its own wiring-type spec sheet. Could be 3 or more wires, but you should always use the data sheet of the sensor. The IO master is responsible to get the information from each device to the PLC. For question #2, PROFINET is based on standard Ethernet for its communication medium, which we discussed in the video. For question #3, for the most part, yes, you can use the standard sensor, but depending on the IO link you use in your design. Again, check the data spec sheet. Here is a link for more learning! www.siemens.com/global/en/products/automation/industrial-communication/io-link.html Happy learning!
@optisliprg8571
@optisliprg8571 4 года назад
Excellent video.One question.What is the difference between this system and the Fieldbus protocol or Europan ASi? Thank you to continue like this
@realpars
@realpars 4 года назад
IO-Link is a field instrument-level protocol just like Foundation Fieldbus or Asi. However, it is typical for the IO-Link connection block to convert the IO-Link signals, which are typically "short-haul" signals to Ethernet/IP, ProfiBus or some other "long-haul" protocol that can be run longer distances. In this video, the IO-Link connection "bricks" are joined to the PLC network via ProfiNet.
@optisliprg8571
@optisliprg8571 4 года назад
@@realpars Thanks for aswering from the follower to yours. I expect a next video about ASi or about the characteristics of the Fielbus, Devicenet (US), Asi (EU) and this field protocols that I just discovered
@andyhandyman2118
@andyhandyman2118 2 года назад
love your videos. question. what piece of equipment is above the electric motor on the same orange line before I/O link? tnx good people!!!!
@realpars
@realpars 2 года назад
That is a smart motor starter (like a SIPLUS SIMOCODE). You could also put a small VFD in that position.
@willytv275
@willytv275 2 года назад
What is best way to use an existing 4-20 analog device with an IO link master? Can a signal conditioner be used between the two in order to establish communication?
@realpars
@realpars 2 года назад
There are dozens of devices in the market to do this. This is just one example: www.balluff.com/en/de/products/product-news-overview/product-news/io-link-converter-for-analog-in-and-output-signals/. Do a web search for "4-20ma to IO-Link" to see a whole lot more.
@mostafaseyedan1034
@mostafaseyedan1034 4 года назад
Hi Thanks for this wonderful and informative video. I gotta ask that why maximum cable length of IO links is 20m? I connected series of PICV (Pressure Independent Control Valve) to a Siemens KNX thermostat, and my link is exceeded than 20m. Is it a problem?
@realpars
@realpars 4 года назад
Every protocol as a standard specification. Maximum cable lengths are determined by the type of signal, the speed of communication, and the electronics used, The biggest consideration is power loss along the length of the cable to a point where reliable communication is no longer guaranteed. For Ethernet, CAT5E, the maximum cable length is specified by IEEE 802.3 as 100 meters. For IO-Link, the maximum cable length is specified as 20 meters. Will a longer cable work? Maybe. Maybe not. Following the standard helps guarantee that you will not encounter signal loss issues. Problems are more likely to occur when an IO-Link junction has multiple devices connected where many of the devices have excessively-long cables.
@mostafaseyedan1034
@mostafaseyedan1034 4 года назад
@@realpars Perfect! Thanks
@saedalhabbashi2790
@saedalhabbashi2790 9 месяцев назад
Thank you RealPars! I wonder what make us move to use the I/O link , in other words , what make it better than using normal wires hooked up to I/O cards! Does using the I/O link substitutes the i/O cards , in other words , it replaces the i/o cards
@realpars
@realpars 9 месяцев назад
Hi there, Thank you for your inquiry. Your question is excellent! I'd like to highlight that numerous engineers opt for PLCs and IO links primarily due to cost-effectiveness in terms of parts, reduced labor costs, simplified troubleshooting, and minimized wiring needs. These are just a few of the compelling reasons to utilize IO link devices. For further insights into IO link technology, please visit the following link: io-link.com/en/Technology/what_is_IO-Link.php?thisID=76 Happy learning!
@decletitc2716
@decletitc2716 Год назад
Hello how you guys doing you guys got some awesome videos I don't know how many I have seen but it's a lot. I have one question I have a CNC lathe the drivers are analog AC Servo Motors it's what I was told I look at the papers and it says is analog I bought a new CNC control what do you recommend to change from digital to analog. I would like to use the old drivers is there something like the io link. Some kind of converter from digital to analog if there is what do you recommend thank you keep making good videos
@realpars
@realpars Год назад
Servo motors typically have specialized drivers provided by the manufacturer of the drive. I would check with them to see if there is a way to use a digital interface to their servo using a converter or gateway device. IO-Link would not be used for drive control, but there are many other digital bus systems, such as Profinet and Ethernet/IP that may be able to be used with proper gateway.
@khoatruong9446
@khoatruong9446 3 года назад
Thanks a lot for your video, it's very helpful for me. Could I share it on my website? it's only for translate to my language for more people to touch this knowledge and It will be specifically cited.
@realpars
@realpars 3 года назад
Hi Khoa, Thanks for your comment! You can share our video as long as it remains unmodified, tagged and credited back to us. Unfortunately, translating falls under the 'modifying' category and is therefore against RealPars' company policy. Thanks for checking in with us on that!
@enginerepairguy
@enginerepairguy 4 года назад
Hi. Can you do a video of the function and effensiency of nuclear powerplants Regards
@realpars
@realpars 4 года назад
Hey! Thanks for sharing your suggestion with us! I have sent this over to our course developers. Happy learning!
@johnneenee5847
@johnneenee5847 6 месяцев назад
Please sir, I need video (notification) on how to troubleshoot electric panel containing Siemens vfd, relays etc.thanks & God bless u.
@Madilsharief
@Madilsharief 3 года назад
One question please, and i know you would love to answer this. Kindly let me know how did you make this video? I mean the graphics and editing. I can do that but it would take way too much time in flash and other softwares. Please do let me know how! Especially the animation from start till 50 seconds
@realpars
@realpars 3 года назад
Hi there, Thanks for your kind compliment, glad to hear that you enjoy our graphics! I am actually not sure about this as this is done by our graphic and animation department.
@pelleturuabbai1205
@pelleturuabbai1205 3 года назад
Please make a video about fluid bed dryier,rmg,coating ,compression machines pls
@realpars
@realpars 3 года назад
Hey! Thanks for your comment and your suggestion. I will pass this on to our course developers! Thanks for sharing and happy learning!
@aremumuiz6994
@aremumuiz6994 3 года назад
Hi realpars, what is the name of cable used for sensor to master called (yellow cable), thanks.
@realpars
@realpars 3 года назад
The cable is usually caller an IO-Lin,k Device Cable. This cable is an unshielded, three or five conductor cables, not longer than twenty meters, using a standard four or five-pin M12 connector. The master and device pin assignment is based on the specifications in IEC 60947-5-2
@rdrx100rules9
@rdrx100rules9 Год назад
please make a video related to PAC. As it's has more advantages than plc 😍❣️😇😇😇😇
@realpars
@realpars Год назад
Thanks for sharing your topic suggestion, I will happily go ahead and pass this on to our course developers.
@kavyasaxena5229
@kavyasaxena5229 2 года назад
What’s the name of Siemens io link module that you’ve shown in the video?
@realpars
@realpars 2 года назад
This module is called an I/O Link Master module. There are many types and versions of these modules (new.siemens.com/global/en/products/automation/systems/industrial/io-systems/simatic-et-200al.html). Typical IO-Link masters in a Siemens system are joined to a Profibus or Profinet network, and I/O or other I/O connection modules are connected to the ports of the IO-Link master.
@omkarraikar7395
@omkarraikar7395 3 года назад
What is the major difference between AS Interface and IO links
@georgeward2753
@georgeward2753 4 года назад
In the design, when to choose I/O remote or I/O link ?
@realpars
@realpars 4 года назад
Technically, IO-Link is remote I/O. For "mainline" PLC's like Siemens S7 series or Rockwell Logix, you will need to have a link coupler to tie the IO-Link sensors to the main PLC network (ProfiNet, Profibus, Ethernet/IP, etc).
@georgeward2753
@georgeward2753 4 года назад
@@realpars real parts is a great Channel thank you
@georgeward2753
@georgeward2753 4 года назад
Can you name some functions I/O link preferred to use than remote I/O and why ?
@fengjiang9125
@fengjiang9125 3 года назад
Can you make a video to show the difference between io link and remote io
@realpars
@realpars 3 года назад
Thanks for sharing your suggestion with us! I have sent this over to our course developers. Happy learning!
@khairullatifaziz7142
@khairullatifaziz7142 4 года назад
How to Configuration Adress of each slave from this IO link and How to Device (PLC) know equipment who connected to it correct or wrong slave?
@realpars
@realpars 4 года назад
IO Link works in the way as Profibus PA. The PLC has a card or other built-in hardware that acts as the IO Link Master. The IO Link nodes each have a unique node number on the bus that is added to the hardware configuration in the PLC. The PLC reserves addresses as each node is built in the hardware configuration, and those addresses can be used in the PLC program. There are tools available that allow some of the device configuration and setup to be done via a graphical software interface.
@Ibrahim__123
@Ibrahim__123 4 года назад
Does this means that the IO-Link is like a segment coupler in a Profibus-PA network....?
@realpars
@realpars 4 года назад
The I-O Link Master acts more like a DP/PA link coupler, since I/O Link data is transferred to the CPU over Profinet or ProfibusDP in the example in this video. There are also I/O-Link Master cards that fit into the CPU "rack" that are useful when the I/O is close to the CPU. In this video, use of an I-O Link Master is shown in a remote configuration.
@Ibrahim__123
@Ibrahim__123 4 года назад
@@realpars Thank for the clarification...
@joshymarecheverria1848
@joshymarecheverria1848 Год назад
What about the costs of this technology compared with the traditional or the ASi technology
@realpars
@realpars Год назад
I am doing 2 projects now that are using both technologies. The price for the interface blocks and cabling are about the same. IO-Link can put information onto ethernet locally using IO-Link master blocks in the field which raise the price of the field bricks but eliminate the need for an ASi master at the PLC or DCS. Overall, each is very easy to design, install, and configure. IO-Link has much richer diagnostics and can handle analogs much better than ASi.
@russelagustinuspurba2723
@russelagustinuspurba2723 3 года назад
All of the iolink features except the wiring advantage can be achieved by hart protocol. Right?
@realpars
@realpars 3 года назад
Correct. IOLink is used for digital and analog transmitters and devices, whereas HART is used pretty much for analog transmitters only. HART does have one distinct advantage, in that it can be implemented using existing analog wiring by upgrading the transmitter and install HART capability at the I/O subsystem.
@russelagustinuspurba2723
@russelagustinuspurba2723 3 года назад
@@realpars wow you really respond to each and every question! Bless you and your team. Really appreciate your answer
@realpars
@realpars 3 года назад
@@russelagustinuspurba2723 Our pleasure! We want all of our students to not only learn, but to understand what they are learning. This happens when questions are asked, answered. and discussed. Happy learning!
@juancarlosvr
@juancarlosvr 2 года назад
The voice and the pronunciation is perfect for no natives speakers with good but not perfect level of English. Like me
@realpars
@realpars 2 года назад
Glad to hear that, Juan!
@sandychoudhari7106
@sandychoudhari7106 4 года назад
Is IO link similar to Asi Protocol Network Please make a video on Asi network
@realpars
@realpars 4 года назад
Hey Sandy! Thanks for your comment and your suggestion. I will pass this on to our course developers! Thanks for sharing and happy learning!
@gomathinathan9515
@gomathinathan9515 3 года назад
Is there any address mention in IO link? How to identify the address in IO link to plc?
@realpars
@realpars 3 года назад
IO Link is similar to any other node-based protocol. Each device has a unique node number on the segment and has a device description file that identifies the information available from the device. These node numbers are assigned to a device as part of the device's configuration (or DIP Switch selections). A successful hardware configuration in the PLC will contain the node numbers to be used to communicate with the device.
@aadaminda5717
@aadaminda5717 2 года назад
❤️❤️❤️❤️👍👍👍👍👍👍👏👏👏
@91wado
@91wado 4 года назад
What is different between the i/o link and ET200 slaves??
@realpars
@realpars 4 года назад
ET200M and ET200SP (as well as other ET200 models) are remote I/O hardware platforms that connect to the PLC network via Profibus DP or Profinet communication protocols. IO Link is a communication protocol, not remote I/O hardware. To use IO Link in a remote I/O strategy, you will need to install I/O blocks (as shown in the video) or other interface hardware to connect field I/O to the PLC network using IO Link.
@hasanomar2052
@hasanomar2052 4 года назад
What's the difference between IO link and remote IO?
@91wado
@91wado 4 года назад
Up
@realpars
@realpars 4 года назад
Remote I/O is a general term that is used for a control system architecture where I/O is terminated remotely from (not directly connected to) the CPU rack. IO Link is a specific, simple communication protocol which is for short distance, bi-directional, digital, point-to-point I/O connections. IO Link is an industrial communications protocol that is defined by standard IEC 61131-9. IO Link can be used in a remote I/O architecture for bringing discrete or analog data into the PLC. IO Link requires a communications master and a connection to the PLC network.
@samchikashi2146
@samchikashi2146 4 года назад
am not clear on whether we can connect $-20mA instruments on the IO LINK
@realpars
@realpars 4 года назад
It can be done if you install and interface device that converts 4-20ma to IO Link. Example: IFM DP-1213. 4-20ma devices cannot be directly connected to an I/O Link bus without a protocol converter such as described above.
@samchikashi2146
@samchikashi2146 4 года назад
@@realpars thank you for the reply
@ahilcuts7971
@ahilcuts7971 4 года назад
Please make videos for protection relays
@realpars
@realpars 4 года назад
Hi Ahilan, Thanks for sharing your suggestion with us! I have sent this over to our course developers. Happy learning!
@yacinesafsaf9902
@yacinesafsaf9902 4 года назад
What about the method of addressing io link
@alexsopo9917
@alexsopo9917 4 года назад
what addressing are you talking about? You put the IO master into the PLC software having the starting adresses.
@eddahbieddahbi1088
@eddahbieddahbi1088 3 года назад
Up
@berkotropia
@berkotropia Год назад
😐It is great protocol when it works but a real trouble when it has a fault.
Далее
What is Modbus and How does it Work?
8:58
Просмотров 1,7 млн
ТОП 10 Худших игроков Евро-2024
30:22
Who Can Break Most Walls? Ep.2 | Brawl Stars
00:26
Просмотров 675 тыс.
Learn More about the Integration of IO-Link Technology
24:34
What is AS-Interface?
9:09
Просмотров 123 тыс.
IO-Link Masters from AutomationDirect
4:28
Просмотров 1,7 тыс.
What is DeviceNet?
10:17
Просмотров 204 тыс.
CAN Bus: A Beginners Guide Part 1
37:36
Просмотров 293 тыс.
Demystifying IO-Link Webinar hosted by SICK, Inc.
23:46
ТОП 10 Худших игроков Евро-2024
30:22