MS06H. [Siemens S210 #08] Servo Torque Reduction, Torque Range (F07900 Alarm), Torque Limiting 

Electrical Automation Hands-On
Подписаться 22 тыс.
Просмотров 4,5 тыс.
50% 1

#siemens #s210 #motioncontrol
Before: [S210 #7] Motion Control Function Block Programming • MS06G. [Siemens S210 #...
Next: [S210 #09] STO Safe Torque Off and SS1 Safe Stop • MS06I. [Siemens S210 #...
Siemens Control Playlist: • Siemens Controls
Motion Control Playlist: • Motion Control
Chapter:
00:00 Introduction
04:00 Torque Data Telegram 750
10:15 Read Act Torque Value
11:10 MC_TorqueRange
12:20 Notice of using Torque Reduction
15:00 Issue of Velocity with Position Controlled
17:30 Fault F07900 Alarm (P2175)
22:00 Torque Reduction Demonstration
30:00 Control Bits Analysis
33:00 MC_TorqueLimiting
38:00 Torque Reduction Demonstration
44:50 Comparision between "TorqueRange" and "TorqueLimiting"
I appreciate you could buy me a coffee via the PayPal link below:
www.paypal.com/donate?hosted_...
MS06J. [Siemens S210 #10] Servo Drive SLS Safely-Limited Speed
• MS06J. [Siemens S210 #...
MS06I. [Siemens S210 #09] STO Safe Torque Off and SS1 Safe Stop
• MS06I. [Siemens S210 #...
MS06H. [Siemens S210 #08] Servo Torque Reduction Torque Limiting
• MS06H. [Siemens S210 #...
MS06G. [Siemens S210 #7] Motion Control Function Block Programming and Live Test
• MS06G. [Siemens S210 #...
MS06F-2. [Siemens S210 #06-2] Positioning TO - CPU Stop Troubleshooting and Online Test
• MS06F-2. [Siemens S210...
MS06F-1. [Siemens S210 #06-1] Positioning TO Technology Object in TIA Portal - Configuration
• MS06F-1. [Siemens S210...
MS06E. [Siemens S210 #05] Setup Profinet IRT Communication for S210 Servo Drive (Telegram 105)
• MS06E. [Siemens S210 #...
MS06D. [Siemens S210 #04] Commission S210 Servo Drive using TIA Portal Startdrive
• MS06D. [Siemens S210 #...
MS06C. [Siemens S210 #03] One Button Tuning SINAMICS S210 Servo Drive
• MS06C. [Siemens S210 #...
MS06B. [Siemens S210 #02] Using Webpage to Configure SINAMICS S210 Servo Drive
• MS06B. [Siemens S210 #...
MS06A. [Siemens S210 #01] SINAMICS S210 Servo Drive Hardware Introduction
• MS06A. [Siemens S210 #...

Наука

Опубликовано:

 

7 авг 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 16   
@framos9991
@framos9991 6 месяцев назад
You are the Best teacher I have ever seen .
@electricalautomation
@electricalautomation 5 месяцев назад
Thanks! Welcome!
@BallAndBeam
@BallAndBeam Год назад
Best RU-vidrs on PLCs. Thank you!
@electricalautomation
@electricalautomation Год назад
Thanks Bro
@user-ev3tx3zk5d
@user-ev3tx3zk5d Год назад
Thank you very much for your explicaton.
@electricalautomation
@electricalautomation Год назад
Glad it was helpful!
@bhagyodayasinghjadhav7951
@bhagyodayasinghjadhav7951 Год назад
Thank you sir...
@electricalautomation
@electricalautomation Год назад
All the best
@mohammedrezk8072
@mohammedrezk8072 Год назад
honstly i have learned much from these playlist so Thanks for your Efforts, but i have a question on practical life scenario, i have four v90 drives controlled by S7 1500 cpu and lately i have randomly errors on two of them (HW Limit exceeds) while this is not occured , aslo from where i can know the real cause (is from Drive monitor Error Code or from the Commissioning Tab inside TO or from the PLC CPU diagnostic buffer )
@electricalautomation
@electricalautomation Год назад
If you are not using the HW Limit but it is causing trouble, please check P29300, it could be set = 6. If you are using HW Limit, properly check the sensor flicking.
@maxjuniet
@maxjuniet Год назад
Hello, I hope you can help me. I have an engine BG65S from dunkermotoren that i command with a driver PDC1000 and a PLC S7-1500, thanks to your video i learned how to create the telegram 750 and read the torque value but i got a Word value (that is supposed to be a torque value in Nm but not) and i see that you are using a LReal. How did you get this value ? Did you convert it ? Thank you
@electricalautomation
@electricalautomation Год назад
Once you activate Telegram 750, and download the configuration, your TO can read out the torq value, as shown in video 10:21. But different brand would do slightly different for preparing the data for telegram 750, many be doing % of the fully torque (full torque is your motor full torq, e.g 10.5 Nm), or the actual torque Nm value.
@maxjuniet
@maxjuniet Год назад
@@electricalautomation Hello thank you for your first answer. I verified the unit in the settings of my TO and it should be in Nm. After discussing in the siemens forum, it seems that my word value represent a torque purcentage as you said (so 16383 should be 100% of my available torque). I would like to retrieve a Nm value from it. My engine got a rated torque of 0,53 Nm (maximum 1,7) but there is a reductor of I = 100 so finally i got 38,69 Nm (based of the user manual of the engine), the point is that i'm not sure of the accuracy of this purcentage and i would not like to calculate the value in Nm from it, i am afraid that after too much calculation i will not have a torque value i can trust. If possible the best should be to directly have the value in Nm (LReal) from the telegram to have the best accuracy.
@vorapobautomation9760
@vorapobautomation9760 Год назад
Can use Torque Limiting for unwind and rewind machine ?
@electricalautomation
@electricalautomation Год назад
Yes, torque reduction is a common function while you are using speed to control tension for winders
@vorapobautomation9760
@vorapobautomation9760 Год назад
@@electricalautomation Can you show next video how to use it ?
Далее