No AC Service Call. Compressor with open windings 

HughesMan HVAC
Подписаться 9 тыс.
Просмотров 7 тыс.
50% 1

No AC Service Call. Compressor with open windings, what caused this compressor to act the way it did and things to check on a commercial RTU.
Hit me up at hughesmanhvac@gmail.com

Опубликовано:

 

26 май 2021

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 85   
@bentleyjarrard885
@bentleyjarrard885 3 года назад
I'm always amazed by this type of issue, how are these guys passing the interview process and getting hired? I had a situation where we installed thirteen, 20 Ton, 2 stage package units on a warehouse and 3 of them didn't start up properly. One had zero refrigerant, one had a bad transformer and one the blower didn't work. The technician said the blower motor was seized up and needed to be replaced. So being the pain in the ass Project Manager I am, went up on the roof myself only to discover 2 of the 3 blower motor spade connectors had come off the bulkhead connector due to shipping vibration or just a factory screw up. I spun the blower motor by hand to verify it wasn't frozen and with the wires reconnected that unit worked perfectly. I also took the good transformer from the unit with no refrigerant and replaced the bad transformer on the other one so now there was only 1 unit needing service. For anyone reading this thinking I shouldn't have touched anything that is under warranty here is my response. Then don't do such a shitty job that the customer CAN find your mistakes!!
@EverythingHVACR
@EverythingHVACR 3 года назад
The installers strike again! Seen this too many times. Start up consist of flipping the disconnect and running the other way. Great work!
@HughesManHVAC
@HughesManHVAC 3 года назад
Yeah, luckily we didn't install these units.
@miketkac8875
@miketkac8875 3 года назад
Sounds great to me 25 years like the way you do your job
@HughesManHVAC
@HughesManHVAC 3 года назад
Thanks
@vidacooltvcarloslesvia2582
@vidacooltvcarloslesvia2582 Год назад
Good job 👍🏽
@HughesManHVAC
@HughesManHVAC Год назад
Thanks for watching
@jackbrennan8476
@jackbrennan8476 11 месяцев назад
Good video
@HughesManHVAC
@HughesManHVAC 10 месяцев назад
Thanks
@HVACRSurvival
@HVACRSurvival 3 года назад
Good video, you got to love them calls. I had a breaker off call today😅
@HughesManHVAC
@HughesManHVAC 3 года назад
I have an account that we get multiple calls to each year for breaker off, they stack boxes right in front of the panel and always bump with boxes.....it all pays the same!
@MRICE-qe4sv
@MRICE-qe4sv 3 года назад
Lol I get this often for walk in freezers. Employees don’t want to be in the box with the fans running so they’ll kill the disconnect and clock out. Next shift shows up and I get a call. 🤦‍♂️
@scottk0623
@scottk0623 3 года назад
Nice find, makes you wonder what they did on start up🤔
@HughesManHVAC
@HughesManHVAC 3 года назад
Probably just ran the heat
@gregbowman3598
@gregbowman3598 3 года назад
Good video Ryan Have a good memorial weekend
@HughesManHVAC
@HughesManHVAC 3 года назад
Thanks Greg! Enjoy your Memorial Day also!
@mrgreen9086
@mrgreen9086 3 года назад
Good find on the compressor keep it up.
@HughesManHVAC
@HughesManHVAC 3 года назад
Thank you Mr Green
@716applianceguy2
@716applianceguy2 3 года назад
Nice video Ryan hope your doing well
@HughesManHVAC
@HughesManHVAC 3 года назад
Thanks man! Have a good memorial day weekend!
@williampagan4489
@williampagan4489 3 года назад
As always Nice Video, Have a nice Memorial Day Weekend....Be Safe and Be Blessed
@HughesManHVAC
@HughesManHVAC 3 года назад
Thank you William, Have a nice Memorial Day weekend as well.
@refrigerationconfidential4376
@refrigerationconfidential4376 3 года назад
HughesMan on the scene 🤙🏽
@HughesManHVAC
@HughesManHVAC 3 года назад
Have a good weekend man! Hopefully you're not oncall
@sledgehammer4647
@sledgehammer4647 3 года назад
Great video. Have a great weekend
@HughesManHVAC
@HughesManHVAC 3 года назад
You too man
@lizards7777
@lizards7777 3 года назад
Oh how I have waisted frozen water bottles cooling compressors, is that a billable part..
@karlschoen7297
@karlschoen7297 3 года назад
👍 must have been installed 3: 15 pm Fri
@HughesManHVAC
@HughesManHVAC 3 года назад
Probably Karl! Your not from Findley Ohio are you?
@karlschoen7297
@karlschoen7297 3 года назад
@@HughesManHVAC nope Marine city Mi
@HughesManHVAC
@HughesManHVAC 3 года назад
Thought you might have been a different Karl I worked with a long time ago. I appreciate you watching the videos man! Thanks
@karlschoen7297
@karlschoen7297 3 года назад
@@HughesManHVAC always learning must keep an open mind. And I worked around the Detroit metro area a lot of taco bell , Mac D's little caesars. Now trying to stay with residential
@winstonwright3613
@winstonwright3613 3 года назад
I've heard of bad start-up and commissioning, but these guys must not have even stood there for one single second after turning power on to the unit in order to miss something like that. That's ridiculous. Great video tho!
@HughesManHVAC
@HughesManHVAC 3 года назад
Probably installed in the fall
@manuelponce3715
@manuelponce3715 2 года назад
Great Stuff Brother.
@HughesManHVAC
@HughesManHVAC 2 года назад
Thanks for watching!
@michaelcostello6991
@michaelcostello6991 3 года назад
You jumped G to R to bypass the thermostat. I am a newbie. Is G just to power the blower relay ? How does Y get power for the compressor contactor ? I wish you had referenced the wiring diagram for this important point so everyone could follow. Thanks for a great video
@HughesManHVAC
@HughesManHVAC 3 года назад
24v feeds down to the thermostat from the transformer, the tstat is basically a switch that sends power back to the unit depending on what you want it to do. if you want ac it sends 24v to y and g. if you want heat it send 24v to w. in the old days the 24v would go back to a series of relays but now it goes to the main control board and the board will then send power to the contactors to bring on the bower and compressors or start the heating process by bringing on the inducer. sorry im late with the reply.
@carmeloepps991
@carmeloepps991 Год назад
Do you know how to fix air conditioner
@bmillwood6666
@bmillwood6666 3 года назад
Get with the customer and check all the units for correct phasing.
@HughesManHVAC
@HughesManHVAC 3 года назад
I did, checked all units before I left. Thanks for watching
@hkhsm359
@hkhsm359 3 года назад
Nice job. Seems like installer didn't check well or just check if blover was running right way they thought it is right way for compressor too but was not. How I know it: because I made same mistake before. Thanks for sharing. Have a great weekend and memorial day
@HughesManHVAC
@HughesManHVAC 3 года назад
Thanks for watching man!
@TheGgin
@TheGgin 3 года назад
@@HughesManHVAC Nice find and simple fix! Looks like the Indoor blower on this one was PSC, so the installer assumed if it was correctly phased, so the 3-Phase compressor was too! Not! Have a safe Memorial Day!
@HughesManHVAC
@HughesManHVAC 3 года назад
@@TheGgin yeah I figured that out while I was editing...lol. thanks for watching my video man!
@chrism6874
@chrism6874 3 года назад
Well done video!!
@HughesManHVAC
@HughesManHVAC 3 года назад
Thanks!
@BRBexotics
@BRBexotics 3 года назад
Put a 13/16 wrench in the bag for those latches.
@HughesManHVAC
@HughesManHVAC 3 года назад
Mr know it all here
@HughesManHVAC
@HughesManHVAC 3 года назад
😂😆😂
@BRBexotics
@BRBexotics 3 года назад
Speaking from experience and frustration doing PMs on them lol.
@juan251100
@juan251100 3 года назад
Blower looked like single phase
@HughesManHVAC
@HughesManHVAC 3 года назад
It is, slight oversight on my part. Was kind of in a hurry with a ton of other calls. Realized it while editing the footage. Probably why the compressor phasing was overlooked In The first place. Thanks for watching!
@renecuevas4128
@renecuevas4128 3 года назад
Compressor Monitors on sale. 3.99 each at Walmart. Kidding😏
@natepeterson7145
@natepeterson7145 3 года назад
You need to invest in the coolpressor by supco so you don't have to hold that hose on that compressor.
@HughesManHVAC
@HughesManHVAC 3 года назад
Yes, I was thinking of that while I was holding that hose
@jonnymac31
@jonnymac31 3 года назад
Sweet
@HughesManHVAC
@HughesManHVAC 3 года назад
Thanks John
@sknight0391
@sknight0391 3 года назад
Dang! Hughey's running backward 😲😲😲
@HughesManHVAC
@HughesManHVAC 3 года назад
😂 thanks for checking it out Shannon 🤠
@wtfman5313
@wtfman5313 3 года назад
Wow... running backwards right out of the box... I guess they connected main power and called it a day.
@HughesManHVAC
@HughesManHVAC 3 года назад
Exactly
@invisibles362
@invisibles362 3 месяца назад
It's a LG compressor, that's a problem...
@jimmyjackson9090HVAC
@jimmyjackson9090HVAC 3 года назад
Isnt there phase protection on those
@HughesManHVAC
@HughesManHVAC 3 года назад
No
@renecuevas4128
@renecuevas4128 3 года назад
Compressor Monitor Anyone😁
@abdullah_q8171
@abdullah_q8171 3 года назад
LG compressor ist butter than copland ?
@HughesManHVAC
@HughesManHVAC 3 года назад
I haven't work on slot of LG but it did hold up not being phased correctly
@steveblake8766
@steveblake8766 3 года назад
#94 thumbs uP
@HughesManHVAC
@HughesManHVAC 3 года назад
I can always count on Steve! Thanks man!
@enriquesiquina
@enriquesiquina Год назад
Can this happen on 240 v?
@tedhicks5431
@tedhicks5431 2 года назад
Obviously blower and cond motor is 1phase
@HughesManHVAC
@HughesManHVAC 2 года назад
Exactly, they probably installed in a cooler month and didn’t check the compressor
@leifhoganson6996
@leifhoganson6996 3 года назад
Dude the blower is a single phase blower
@HughesManHVAC
@HughesManHVAC 3 года назад
Sure is, so phasing didn’t matter for the blower and was probably why this compressor was overlooked. An oversight on my part also when I recorded this but we aren’t all perfect, well I’m not at least… not sure you might be though
@HermesVintage
@HermesVintage 3 года назад
I heard the core max tool is like $500
@HughesManHVAC
@HughesManHVAC 3 года назад
That sounds about right
@joekonopka5161
@joekonopka5161 3 года назад
Local 449?
@HughesManHVAC
@HughesManHVAC 3 года назад
No, another local
@Brutis-1983
@Brutis-1983 3 года назад
Somebody failed the start up.
@HughesManHVAC
@HughesManHVAC 3 года назад
Indeed
@Brutis-1983
@Brutis-1983 3 года назад
@@HughesManHVAC good find, wonder if others on the roof are that way?
@HughesManHVAC
@HughesManHVAC 3 года назад
No, I looked at all the other units to gather data plate info and pushed compressor contactors in just to make sure
@daddygc5814
@daddygc5814 3 года назад
I dont understand when your standing pressure is so good that you spend so much time looking for leaks ,even before you properly check out compressor.its a wast of time.
@HughesManHVAC
@HughesManHVAC 3 года назад
I spent 5 min checking those fittings
Далее
No AC Service Call
15:08
Просмотров 13 тыс.
HVAC No Cooling Service Call with LOTS of ISSUES
16:19
No AC Service Call
14:09
Просмотров 2,9 тыс.
Carrier rtu AC not cooling
18:08
Просмотров 19 тыс.
Locked Compressors
20:13
Просмотров 111 тыс.
HVAC No Cooling Call
13:10
Просмотров 17 тыс.
Diagnosing a Locked Compressor 3D
10:02
Просмотров 55 тыс.
HVAC Service Call: Smoke in Store.
25:55
Просмотров 6 тыс.
Two No Cooling Calls
13:19
Просмотров 11 тыс.
No AC Service Call | Residential Split System
13:59
Просмотров 2,1 тыс.