You did not use busbar for interconnecting the battery cable and ac output, you direct the wire of the slave inverter to the battery terminal of deye master?
@@DeyeInverter_official Thank you. I will buy second SUN-8K-SG01LP1-EU. But I have a problem that it is impossible to get in EU. No e-shop offers the single phase SUN-8K-SG01LP1-EU
Hello Kyle. Can you please confirm wire connection sequence. On internal wires above they are marked and sequenced as Neutral and then Live. But on the silkscreen text below the terminal blocks they are Live Neutral PE. Should external connection be made as L N PE or N L PE ?
Also, if you have parallel inverters, if L and N connections are swapped. Would this cause problems with CT readings when trying to do zero export to CT when all load is connected to load port and only grid supply connected to grid port?
@@robgood9119 Dear, Kyle! We had a problem in the system with limited export to the mains through measuring CT in 5kW hybride inverters. The problem was solved by changing the direction of installation of the current transformer
@@nicof9202 good morning. Thank you for watching and commenting. Yes it is. There are videos on RU-vid that show them with separate batteries. Regarding smart load when in parallel. I don't know the answer to that. I will ask and get back to you. Great questions
Hello, I have a question. The inverter SUN-12K-SG04LP3 has the parallel connection device built in, or do I have to pay extra price and buy this extra feature?
Hi, for Lead acid batteries, the bank need to be connected in parallel also, or can i connect a battery bank independent to each inverter?. I have 3 inverters and the battery voltaje is lower on Slaves inverters, when the master stop charging the slaves do also and the batteries are not charged complete.
Hi, please I will like to learn about the power factor of your hybrid inverters, on the manual it says 0.8 while on the settings page I see some places it says 1, please what is the implication of this setting
Sir, can you explain to me, why the total load not divided equally among the 3 inverters? Example: When I have 3 batteries, if the load need, their output currents are almost equal thanks to
Hi Kyle, I just want to ask. There is a parallel connected Deye Hybrid Inverters. Both are 8 kW Hybrid Inverters. We connected a Over Under Voltage Protection Device so the client can monitor the voltage and current passing through. My question is, the Inverters are running normally and don't have any errors, why is it that there is no current passing through the Grid terminal of Inverter 1? Current is only passing through to Grid terminal of Inverter 2... What could be the reason?
Continuation to the first question, when the client turns OFF the circuit breaker for Grid of Inverter 1, brown out occurs even if circuit breaker for Grid of Inverter 2 is still ON.
@@DeyeInverter_official Hi Deye, No, it did not explode. There is just no current passing through the GRID terminal... Then now, the batteries just became low-battery status (Battery 1: 0%; Battery 2: 12%) and the whole system just shut down. I think this happens every month.