POWER MONITOR, Measure Real Power with power factor. Using a 100 Amp Power monitor from Banggood 

Pierre's Garage
Подписаться 20 тыс.
Просмотров 9 тыс.
50% 1

Here I’ll be installing a 100 Amps Power Monitor on my roto-phase converter setup, since those loads are mostly inductive, this monitor will give me a real power figure taking into account the electrical power factor.
Most of us will measure power with an ammeter, using the formula where you multiply current by amps, for real power measurements mostly with loads other than purely resistive loads you need to take into account the Power Factor in order to get exact measurements. Since the Power factor will vary according to the load and the nature of the componants, this inexpensive monitor ordered from Banggood will make it easy to install a permanent monitoring system, for a very decent price the accuracy of this unit is quite impressive…
==============================================================================
DISCLAIMER:
The 100 Amps Power Monitor referenced in this video was purchased from Banggood and fully paid by myself, I always try to make the most honest and impartial evaluation possible, but, since I’m only human, you, the customer always have the final word on your decisions… 😉
==============================================================================
Here are the links to reach the tools demonstrated in the video
Be sure to look out for discount coupons or any special offer at different time of the year…
100A Digital LED Panel Power Monitor Power Energy Voltmeter Ammeter Meter Tester
goo.gl/WWb5sT
5pcs Triangle Shank Imperial Pagoda Step Drill Set
goo.gl/xqdAiY
=========================================================================
Philippe’s RU-vid Channel:
Phil’s Projects
/ phildesjardins1
Thank you for watching and I hope you like this type of video…
Thumbs up, a comment and even better a subscription is always a great way to say you appreciate the efforts I put in the making of those videos… 😉
Pierre Beaudry
wledpierre@gmail.com

Опубликовано:

 

22 окт 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 80   
@fearlessphilshiver
@fearlessphilshiver 2 года назад
Great video! Note there is a 3% loss in efficiency (i.e. wattage increase) for each conversion, so about 6% total in this example. If a machine is run nearly continuously it may be worth the invesment to replace the three phase motor with a 240V single phase (and selling the old one), or having the power service upgraded to provide 3-phase "from the pole." I appreciate that this double conversion example makes perfect sense if the end equipment was acquired at little cost, it is used intermittently, or this is a home garage with no possibility of getting 3-phase power from the utility. Cheers!
@pierresgarage2687
@pierresgarage2687 2 года назад
Since those machines were acquired used at much lower cost than brand new machines and were operated at 600 volts 3 phases, it made sense to keep them in original configuration. The lathe has a 2 speeds 7.5 HP and the milling has three 600 volts motors, this would be lots of fitting and fidling to replace. And, one important factor in favor of keeping the 3 phases motors is the extra torque available from a three phases motor compared to a single phase unit. Getting 3 phases from the pole would probably be possible since three phases wiring is installed just on my front yard, the drawback is the cost, I estimate from at least $10k to possibly over $20k to get a complete installation.... 😱 $$$$ The total cost of the electric bill is less than $2k per year for the house and the shop, it would take at least ten lifetimes to get even and more to start saving money... Being retired and only using the shop very partially now, it's quite more reasonnable to keep on using this setup, as a bonus, the extra consumption from the phase converter is used to heat the shop during the cooler part of the year. Thanks for your comment, Pierre
@brucejohansen5933
@brucejohansen5933 6 лет назад
j'ai toujours cru qu'il fallait se coucher moins naiseux qu'on sé lever. Ton emission m'a aider a accomplir mon objectif. merci monsieur (TRANSLATION) i always believed that it is better to go to sleep not as dumb as i woke up. thank you sir for helping me accomplish this.
@pierresgarage2687
@pierresgarage2687 6 лет назад
Nice reward to hear from viewers that the material is helping someone get better sleep that night... I do the same on some other good channels.... ;) Thanks for comment, Pierre
@EverettsWorkshop
@EverettsWorkshop 6 лет назад
Very cool, your explanation of the test you were performing was well done - I've never dealt with 3-phase equipment in my shop, and the numbers made sense once you worked the math out. I was surprised how much horsepower was required to dig a .200" cut, no wonder my little 1.5 hp motor grunts at half of that in good steel! Thank you for doing this one, It was very informative.
@pierresgarage2687
@pierresgarage2687 6 лет назад
Hi Everett, the bigger machines have a definite advantage in heavier removal, this is where we realise that steel is quite hard... ;) Don't hear much from you lately, hope you're doing good.... Cheers, Pierre
@brucewilliams6292
@brucewilliams6292 4 года назад
Hi Pierre, Thanks for the video. I was looking for this very thing for a project I had and you always do a great job of explaining what is happening. Thank you.
@pierresgarage2687
@pierresgarage2687 4 года назад
Glad I could help...!!! Thanks for viewing and taking a moment to leave a nice comment, Pierre
@AmateurRedneckWorkshop
@AmateurRedneckWorkshop 6 лет назад
Very professionally done.
@pierresgarage2687
@pierresgarage2687 6 лет назад
Hi Harold, This took me quite a while to get it right... ;) Nice of you to notice and mentionneing it. Sun is really shining this weekend, just that tha neighbors got out everything that make noise, leaf blower, pressure washer, guess we can't have it all perfect at once... lol Take care, Pierre
@jonmixer6142
@jonmixer6142 5 лет назад
inductive loads have a lagging current sine wave. Your diagram showed the inductive load to be leading.
@pierresgarage2687
@pierresgarage2687 5 лет назад
Sorry about the inversion, my electronic knowledge is some years ago, my memory might also be lagging behind... 🙂🙄
@PhilsProjects
@PhilsProjects 6 лет назад
Gezzzz i am unable to go to your place for a few weeks and all the sudden you start making holes in the furniture, VACCUMING!!!! and marking the walls with crayons.. Pierre, i need to set you straight again. lol I must come up with a production run to keep you busy and away from that destructive behavior. Informative, nicely done
@pierresgarage2687
@pierresgarage2687 6 лет назад
You're getting to sound just like Keld, Lucky he's on the other side of the pound... lol Guess we need to get back making Monkeys of ourselves, issues are getting slowly resolved, at least for the moment... ;) See ya soon...!!!
@RRINTHESHOP
@RRINTHESHOP 6 лет назад
Good explanation. Good video.
@pierresgarage2687
@pierresgarage2687 6 лет назад
Hi Randy, And for the price that little device is quite accurate, not for lab use but great for a small shop... ;) Cheers, Pierre
@nowayjerk8064
@nowayjerk8064 6 лет назад
this one time at band camp i took 2 extension cords on different breakers and ran a 240v air compressor , but only cos i dont know better . just enough to be dangerous thats me :)good to see ya thanks for sharing !!
@somebodyelse6673
@somebodyelse6673 6 лет назад
Did anyone ever figure out why the band camp burned down?
@billsmini10
@billsmini10 6 лет назад
Why didn't you remove the switches in the door, then remove the door from the panel? Then you would prevent getting metal chips inside the box from drilling/cutting. Stan recently did an electrical box cutting, but there were no electrical components installed inside it until after he made the hole for the display.
@pierresgarage2687
@pierresgarage2687 6 лет назад
I've seen Stan's job, quite neat on brand new box, I didn't feel like like undoing all of the already installed switches, the job needed to quick and dirty... ;) Thanks for comment, Pierre
@stephenwagar2663
@stephenwagar2663 6 лет назад
Phil's Comment Made Me Laugh , And Hobby Dentistry . Boy Howdy , How Much Fun Are We Allowed To Have ? I Enjoyed The Video And Learned Alot As I Have Not Much Experence With Electricity ... Best Regards
@pierresgarage2687
@pierresgarage2687 6 лет назад
There is not limit as how much fun is allowed, as long as no one has to suffer from it... Fun is for everyone... One former career was in electronics, until 1991 for the Canadian Broadcasting Corp, for 20 years. Cheers, Pierre
@stephenwagar2663
@stephenwagar2663 6 лет назад
Impressive ! I'm Aware That You Know Quite ALot About A Great Mamy Things , It Shows In All Your Videos . I Am A Retired Land Surveyor Best Regards Again
@barrygerbracht5077
@barrygerbracht5077 6 лет назад
Great explanation of power factor (assuming what I understood is correct at any rate). Does the drag under load reduce the phase discrepancy from the inductive side to produce the increase in power factor?
@pierresgarage2687
@pierresgarage2687 6 лет назад
Hi Barry, Sounds like your understanding is right, it won't reach 1 but it will get closer as load increases. In industrial areas utility companies have to correct the shift caused by users that have lots of machinery with big heavy motors, they do this in order to keep the rest of the network to be out of phase, this could cause some pretty high uncontroled surges. Cheers, Pierre
@docpedersen7582
@docpedersen7582 6 лет назад
Well done Pierre.
@pierresgarage2687
@pierresgarage2687 6 лет назад
Good morning and thanks for comment, Pierre
@jairoalcidesvillamarin8665
@jairoalcidesvillamarin8665 4 года назад
Grate and entertaine vídeo, Desde Colombia, gracias
@pierresgarage2687
@pierresgarage2687 4 года назад
Thank you for watching and for your comment, Pierre
@asadulhuq
@asadulhuq 4 года назад
Another excellent presentation. Thanks a lot. Now, I have 2 questions. 1. Does the monitoring device show Apparent or Real power? 2. Does the monitor display viewing angle and brightness are good to view the readings? Thanks again.
@pierresgarage2687
@pierresgarage2687 4 года назад
To your first question, the device shows the real power drawn on the power line, also the cumulative reading is adjusted after calculating the power factor. As shown in the video, the apparent power drawn would be (volts X amps ) 244 X 26.4 = 6441 watts, there the device shows actual power draw of 1.09 kw with a power factor of 0.16. The cumulative part is also adjusted. The display is installed some distance above my view and it's still easy to read even though the angle is something like 45 degrees or just about... Thanks for viewing, I hope this is what you needed to know, Pierre
@asadulhuq
@asadulhuq 4 года назад
@@pierresgarage2687 Thanks. You are a great man. You presentations are excellent and responses are very quick. Asadul, Dhaka, Bangladesh.
@miltonhooper6658
@miltonhooper6658 6 лет назад
Excellent video. Great narrative.
@pierresgarage2687
@pierresgarage2687 6 лет назад
Thank you for nice comment, Pierre
@JonathanVaucher
@JonathanVaucher 3 года назад
Crois tu que je peux utiliser ces power monitor (deux moniteurs, un sur chaque phase) pour mesurer ma consomation sur mon paneau électrique de maison de 200A (100A sur chaque phase) ?
@pierresgarage2687
@pierresgarage2687 3 года назад
Si tu te trouves en Amérique du Nord, la réponse est oui. En fait tu te trouveras à mesurer chacune des branches de 120 volts, tu additionnes chacune des ces branches et tu auras la puissance totale utilisée, par contre pour les circuits à 240 volts qui n'utilisent pas de neutre tu devras les isoler et les mesurer indépendamment. Dans ce cas une des deux branches seulement a besoin d'être monitorée.
@iamGomer
@iamGomer 6 лет назад
Can't say I've seen a PF that low before. But, I love how 'cheap' the meters are. For piece of mind, I do fuse them. Doubt that would do much. Keep up the good videos sir.
@pierresgarage2687
@pierresgarage2687 6 лет назад
Quite a while go I had access to an costly metering device, and the present results match real closely to that costly meeter... Hard to beat under $15, the other unit was closer to $4000... !!! Thanks for comment, Pierre
@cpcoark
@cpcoark 6 лет назад
Pierre, I can't believe those numbers. Current is way too high or your RPC is very large. I just measured mine and it idled around 8 amps. Mine is a 10hp size driving a 5hp lathe. Is your display on the correct scale for the coil pickup?
@pierresgarage2687
@pierresgarage2687 6 лет назад
It is very close, a couple of years ago I measured with a real costly pro unit and the resuls were within 5% of this, I'm looking for some capacitors at a reasonnable price to try brigning the ration to a much better figure. The high shifting of the phase is due to the 20 HP RPC, connected to a 30Kva stepup transformer and finally a 7.5 hp motor on the lathe, this is a lot of inductance in the way... ;)
@bernardpeter4178
@bernardpeter4178 5 лет назад
Good explanation. Good video.keep it up sir.
@pierresgarage2687
@pierresgarage2687 5 лет назад
Thank you for comment, Pierre
@moox64
@moox64 5 лет назад
on screen on the total cumulate " KWh "does include PF ? or do I have to add the PF % to know the total ( the electricity bill paid)
@pierresgarage2687
@pierresgarage2687 5 лет назад
It reflect the "Actual" corrected power consumption, I kinda quickly checked it out to make sure... ;)
@MaturePatriot
@MaturePatriot 6 лет назад
Are the caps drained automatically? What type lathe are you using that you need 600vac? Does it really pull 45 amps under load? Electrical education point #1: It can kill you!!!! Learned that in the late '50s when my dad almost died from electrical shock and burns. I don't fear it, I do all my own wiring, but I do respect it. Currently finishing the build on my RPC. Very good demo video.
@MaturePatriot
@MaturePatriot 6 лет назад
By the way I was about to order a 3 piece Cobalt HHS step drill set, you saved me money, plus 2 more bits. SWEET!
@pierresgarage2687
@pierresgarage2687 6 лет назад
Those drills are quite surprising in quality... Electricity is an element that deserves respect, or like you mention you could get seriously injured, up until 1991 I used to works in electronics, and sometimes had to repair vacuum tube monitors, 25 Kvo;s was a harsh shock to be served, since it always happened during a career.... Not a pleasing memory, though... Wiring electricity, in my books, requires some basic knowledge of electricity laws and construction code in order to avoid burning the house... Better be safer than sorry. Thanks for viewing anf for your comment, Pierre
@MaturePatriot
@MaturePatriot 6 лет назад
My brother and I wired the first house I built, It passed on first inspection.
@pierresgarage2687
@pierresgarage2687 6 лет назад
Shows good knowledge... ;)
@6969smurfy
@6969smurfy 6 лет назад
I need to read power factor @ 3,000amp, 3 phase... Any suggestions?
@pierresgarage2687
@pierresgarage2687 6 лет назад
The only measuring tools I've used to do this on 3 phases are quite costly, not tried yet anything in th lower priced Asian devices, not sure how they would do what's requested or the accuracy. At 3000amps. you would need to insltall proper coils in order to be able to match the wire size and current flow... I suspect those tools are in the high thousand of $$$$.
@outsidescrewball
@outsidescrewball 6 лет назад
you lost me when you opened the power box...yikes, this is something I avoid....lol, enjoyed the vid
@pierresgarage2687
@pierresgarage2687 6 лет назад
Hi Chuck, It's not that bad once you understand electricity a little, just keep your fingers out of live contacts, though... lol And, if you don't the first time, it doesn't take many lessons to learn...... ;) Cheers, Pierre
@unitepak
@unitepak 5 лет назад
INPUT & OUTPUT NATURAL LINE =3 ,N INPUT & OUTPUT LIVE WIRE 4 ,L AND CROSS LIVE WIRE ?
@pakrattuk1562
@pakrattuk1562 6 лет назад
Hi i Phil, my understanding of power factor is limited but basically, in an inductive load, you use more power (not less) for the same amount of work done i.e 1kW of input power will only give you less than 1kW of useful power, depending on the power factor (or to put it another way, if you use 1kW of power, you will be charged for more than 1kW) Also, your power factor of 0.16 is terrible, meaning that for every kW of power you are paying for, you are only getting 0.16kW ish of useful power. I know phase converters will use some power but didn't think that should be as bad as it looks. Hope this sort of makes sense.
@pakrattuk1562
@pakrattuk1562 6 лет назад
Sorry, meant Pierre
@pierresgarage2687
@pierresgarage2687 6 лет назад
No offence about the name... ;) When I get some spare time, ( Sigh...!!! ) it wouls be interenting to see how this situation could be corrected by use of capacitors, mostly trying to keep the rotophase in balance... To be continued...!!! Thanks for your input, Pierre
@JoginderSingh-dr8dx
@JoginderSingh-dr8dx 3 года назад
Two power factor relay and two. Panel. Two. C't connection
@pauldevey8628
@pauldevey8628 6 лет назад
I wonder why hobby dentistry is not more popular?
@pierresgarage2687
@pierresgarage2687 6 лет назад
Enough of the real ones, you get there, they torture you and even get you to pay a hefty price for it... lol Cheers, Pierre
@SimpleEnough2k9
@SimpleEnough2k9 5 лет назад
I have to admit that this thing got a really bad power factor. Even if you're not paying extra for your electric bill, it would be wise to add capacitance in order to improve the power factor and lower the current flow in your wiring.
@pierresgarage2687
@pierresgarage2687 5 лет назад
Agreed that some experimentation would be a plus, I would have to get myself some good quality oil filled capacitors and testing for loaded and unloaded situation, it would probably improve the transfer on the transformer itself...
@SimpleEnough2k9
@SimpleEnough2k9 5 лет назад
@@pierresgarage2687 Based on some quick calculation a 470uF capacitor would bring the power factor in the .90's. Of course, it's voltage rating would be in the same range as the ones used for the HVAC central units. When dealing with mains voltage and above, we can't take anything for granted. Extreme care is mandatory!!!
@pierresgarage2687
@pierresgarage2687 5 лет назад
Would you install the capacitor directly shunted on the 240volts input line right after the switch, is a run capacitor the one to use in this case...? Or on the phases after the step-up transformer where the voltage is then 600 volts 3 phases, there would be a need to install one on each phase I guess...< Yah...!!! This scares me a little...!!!
@SimpleEnough2k9
@SimpleEnough2k9 5 лет назад
@@pierresgarage2687 The capacitor would be in parallel with the input of your "1 to 3 phases converter". The "start" and "run" capacitor naming convention is basically to ease the understanding as to where the capacitor is used. The only difference is in fact the capacity. Internally they're the same. They could be interchanged as long as the capacity is within specs. For the 1 to 3 phases unit you could benefit with the use of capacitors on each phase. The last element you have is actually a transformer that step up the voltage to 600V, isn't it ? Personally I'd go only with the capacitor on the 1 to 3 phases converter and evaluate the situation from there. If you have a spare meter, you could consider measuring the current and power factor on each phase and determine if correcting the power factor at the input of the 1 to 3 phases converter is really beneficial. Don't forget, the caps voltage rating is based on "peak" values, not RMS.
@pierresgarage2687
@pierresgarage2687 5 лет назад
I know a place where they got some caps at reasonable prices, I'll try to get an assortment of values in order to tweek the result... Thanks for the hints, useful to get started.....
@jeffbrown7246
@jeffbrown7246 Год назад
Need some capacitors pal so your not just circulating and paying for 30a that you’re not using!!! 🤦🏼‍♂️
@pierresgarage2687
@pierresgarage2687 Год назад
Any suggestion on what values and type that could be appropriate to correct and bring the factor to near 1...?
@jeffbrown7246
@jeffbrown7246 Год назад
@@pierresgarage2687 I’ll look at the video again
@tompas11A3n52KkX
@tompas11A3n52KkX 6 лет назад
Why do you need a power monitor? How will a power monitor get you a better machinist? I just can't get it...
@pierresgarage2687
@pierresgarage2687 6 лет назад
This is some kinda response to some guys that try to make comparative testing on machinery, they used the regular power formula that didn't take into account the Power Factor element, in my books their results were pretty far from reality. Exemple testing metal removat using different lubricants, or any other comparison you may imagine... ;) As a benefit you get a cumulative count for power consumption, this will be useful to me to figure how much electricity is used to charge my Chevrolet Volt. Like you say, I'm not addressing only machinists, but this could be of use to people in other trades that need a real reading of power, thanks for viewing and comment, Pierre
@tompas11A3n52KkX
@tompas11A3n52KkX 6 лет назад
OK I get your point Pierre, have a nice...
@somebodyelse6673
@somebodyelse6673 6 лет назад
Pierre, maybe you could use your power meter to compare how tool geometry affects the power required to make a cut? Those of us with benchtop lathes might like to see what positive, neutral, and negative rake does for staying within the capability of smaller lathe motors.
@pierresgarage2687
@pierresgarage2687 6 лет назад
You've got an excellent idea, this is important mostly when power is very limited or to optimize a process... ;)
@bcbloc02
@bcbloc02 6 лет назад
SO you built a lathe dyno of sorts. :-)
@saqibiqbal7667
@saqibiqbal7667 3 года назад
Long video so " REAL WASTE OF "
@pierresgarage2687
@pierresgarage2687 3 года назад
If you have something positive to help me improve the content and the way it's produced, You're more than welcome, I'm more knowledgeable in machining and installing than video production, so.....
Далее
DIY Home Energy Monitor & CT sensors explained
6:54
Просмотров 147 тыс.
Handsoms😍💕
00:15
Просмотров 6 млн
How to get skins for FREE? #standoff #skins #coins
00:34
Как не носить с собой вещи
00:31
How Regenerative Braking Works.
23:01
Просмотров 286 тыс.
Electricians Tricked into Live Working ⚡️
10:59
Просмотров 34 тыс.
How 3 Phase Transformers Work - why we need them
24:24
Просмотров 891 тыс.
Millions of people don't know about this homemade tool
10:10
Handsoms😍💕
00:15
Просмотров 6 млн