thanks man! can you do a video with an example with a sepam relay configuration! cut I'm not sure (I get confused about the time parameters that we should inter in the relay...(time and pickup)
It seems current values in Load Flow are not correct right.... Transformer is rated @12.5 MVA 110/11 kv then FLC shall be 65.61 and 656.1A respectively and in addition to that there will be something from the upstream impedance and downstream impedance then current expected to be more than these values right...how come it shows 7 and 70.2A only