Push-Pull Chiller Recovery & Charging 

HVACTIME
Подписаться 44 тыс.
Просмотров 9 тыс.
50% 1

Push-pull refrigerant recovery is a popular method for transferring large volumes of liquid refrigerant from one system to another. It is relatively fast and efficient, and it can be used to recover refrigerant from a variety of different types of systems.
In this video, we will discuss the strengths and weaknesses of push-pull refrigerant recovery, and we will provide a step-by-step guide on how to perform this process safely and efficiently. This is an extremely effective method for chiller technician. This method can be used for air cooled chillers, and water cooled Centrifugal chillers.
Troubleshooting Guides at hvactime.shop
Get 8% off at TruTech Tools with promo HVACTIME
www.trutechtools.com/?ApplyPr...
techsupport@hvactimetx.com
hvactime@hvactimetx.com

Опубликовано:

 

10 июл 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 25   
@BruceEatons
@BruceEatons День назад
Great video,explained perfect...push pull charging 250 lbs,tommorow.. thank you
@jskipperddg80
@jskipperddg80 Месяц назад
Really looking forward to doing your hvac training chiller class soon.
@HVACTIME
@HVACTIME Месяц назад
Looking forward to seeing you there, utilize the chiller community in the academy to get great support.
@jskipperddg80
@jskipperddg80 Месяц назад
@@HVACTIME will do thank you
@TheMinecraftACMan
@TheMinecraftACMan Год назад
So if you're going to get a recovery machine involved in charging, I recommend what I call a pull-push. This is most effective on charges in the 30-200 pound range. The main advantage over a push-pull is that it's significantly easier to switch over to a regular recovery-machine charging once all the liquid is out of the tank. It's a bit slower than a push-pull because the recovery machine has to pump the liquid directly instead of inducing a siphon, so above a couple hundred pounds it stops being worth it. Instead of using the recovery machine to pump vapor out of the system back to the tank, I use it to pump refrigerant out of the tank into the system. It's similar to a direct liquid charge, but I add a hose hose from the vapor port to the low side of the system. This prevents the tank pressure from dropping and making the refrigerant boil off as it goes in, while maintaining a setup that's super easy to switch over to standard charging once you have all the liquid out. Once all the liquid is out, all you have to do at that point is close the vapor port on the tank and it'll start pulling the vapor out. The minimal setup rearrangement gives it a niche role in the 30-200 pound range. Under 30, you're better off just letting the vacuum suck it into the liquid then charging the rest into the suction. Over 200ish you'll probably save more time doing a regular push-pull because then the liquid flow rate isn't being hampered by having to go through the machine itself.
@sjc87
@sjc87 Год назад
I did a push pull on 2 units in jan @750lb per circuit and 2 circuits per unit. Was the first time every doing it and was nerve-racking for the first unit. R134 using a chiller recovery machine and 4-1k cylinders. Super cool and educational but took about 80+ hours especially since they shut off the power to the first unit before we could stack all the refrigerant.
@HVACRTECH-83
@HVACRTECH-83 Год назад
Thx buddy, this cleared up alot
@Voxus77
@Voxus77 11 месяцев назад
Great video my friend!
@cecilchristopher2996
@cecilchristopher2996 10 месяцев назад
Thanks for the video 🔥
@bonexsher
@bonexsher Год назад
good job😀
@adrianmoran1041
@adrianmoran1041 Год назад
Thank you
@user-dd6eb9bo8r
@user-dd6eb9bo8r 10 месяцев назад
So wonderful
@reyrodriguez1005
@reyrodriguez1005 Год назад
Damn good explanation
@ChrsDunaway
@ChrsDunaway Год назад
I work primarily on large chillers. Push pull saves time, it sucks when I cant push pull because I am tying to distill the refrigerant from the oil because someone added oil to the unit when they shouldn't have.
@mexicant777
@mexicant777 11 месяцев назад
That’s awesome
@garypoplin4599
@garypoplin4599 10 месяцев назад
9:20 - Do you know if the Fieldpiece MR45 RM can handle what you’re talking about here?
@cdoleoj1
@cdoleoj1 10 месяцев назад
NEVER EVER run liquid thru a recovery machine, yes they might be able to "take" it for a bit but you are stressing or risking your tools without need, a properly set up push pull on recovery or charging, the recovery machine will never "see" liquid refrigerant. on liquid charging you are pulling vapor from the chiller thru your recovery machine, discharging to the recovery tank and "pushing" the liquid inside the tank out the liquid valve directly into the chiller, your recovery machine NEVER pumps anything but vapor. On these chillers there is a service valve right after the EEV/EXV (some older models the TXV) and before the evap, once you have enough charge where you can run the compressor manually unloaded, you can charge liquid via that valve no problems, it will pull the liquid so fast, charging liquid using the recovery machine becomes the slow method. I have never in 20+ years had to push pull into air cooled chillers
@chillagorilla
@chillagorilla Год назад
Any situations where you have had to block of the fan of the recovery unit?
@pjd4177
@pjd4177 11 месяцев назад
Is the type of expansion valve not a big part of it especially with an EEV.
@TheBTraiin
@TheBTraiin Год назад
Chiller charge recovery through a gauge line 😂 All while talking seriously into the camera.
@tarpontime7562
@tarpontime7562 19 дней назад
And with 1/4” hoses
@rmalanis13
@rmalanis13 11 месяцев назад
Quick question. On air cooled chillers when we charged the system. I was told to put vapor first until above freezing. Your method of charging liquid first, wouldn’t this cause the system to possibly freeze up internally? Thanks in advance
@tarpontime7562
@tarpontime7562 19 дней назад
Yes your correct. But if you have water flow you can charge liquid first. Good practice to break vacuum with vapor tho.
@Bdpjev
@Bdpjev 11 месяцев назад
Olin a push pull charging scenario, going through your recovery machine, aren't you worried about cross contamination of refrigerant oils? I pull everything through my recovery machine. Are you Flushing out the machine
@drodriguez394
@drodriguez394 10 месяцев назад
I’m pretty sure g5 twin does not have a compressor, it does not have a condenser coil. It’s a motor with a liquid pump. Similar to an oil burner oil pump and motor.
Далее
This LOST 1300lb of refrigerant in Chiller
21:13
Просмотров 23 тыс.
🎙ПЕСНИ ВЖИВУЮ от КВАШЕНОЙ🌹
3:09:38
HVAC Chiller Approach Explained
15:21
Просмотров 46 тыс.
Low Pressure Recovery Trane Centrifugal Chiller
8:36
Просмотров 3,3 тыс.
AHU Maintenance
6:44
Просмотров 67 тыс.
push pull recovery method on an air cooled chiller
2:40
HVAC 128 Recovery most used but slowest
10:43
Просмотров 71 тыс.
Commercial Refrigeration Push Pull Liquid Recovery
3:22
YK Surge Troubleshooting: Chiller Training
13:56
Просмотров 1 тыс.