Тёмный

Taco 571 Zone Valve Explained 

Scott Taylor
Подписаться 1 тыс.
Просмотров 10 тыс.
50% 1

How the Taco 571 Zone Valve Explained & How to Wire

Опубликовано:

 

7 сен 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 18   
@goldenhuskylabs4537
@goldenhuskylabs4537 7 месяцев назад
Thank you so much! I switched out an oil boiler with a propane combi. After the switch over one of the zone was barely heating. After watching your video I figured the valve head was twisted a bit and seated it properly. Now I have heat in all zones. Great Video! Thank you again!!!
@pjdecoste4636
@pjdecoste4636 7 месяцев назад
I popped in to see if I could manually open the valve to test if it were bad. You end the video with "I hope this helped." it did. Super informative and I learned a lot. Love the expanding wax liner drive. That is slick.
@gm0826715
@gm0826715 8 месяцев назад
Best explanation ever😊
@tomfrantz
@tomfrantz 9 месяцев назад
THANK YOU> You are the BEST describer of things. LOVE this video.
@cjhuff4453
@cjhuff4453 7 месяцев назад
Thank you !
@cosmiclion6765
@cosmiclion6765 8 месяцев назад
Excellent description what I have been noticing with a valve head I’m working on, same exact model. The actuator lever is very difficult to move even with 24 V at the valve. I had to kind of force it into the manual position to get heat. I will be replacing the valve head, I’m under the impression when the valve is energized, and the actuator drives the piston, the lever should move freely indicating the valve is fully opened. Unless I’m mistaken?
@scotttaylor3049
@scotttaylor3049 8 месяцев назад
The lever should move freely when the valve is open. If it doesn’t move freely then the valve body is sticking or the lever itself has an issue.
@tomfrantz
@tomfrantz 9 месяцев назад
Than, you for "Date code" location. Afraid to look at mine. Might be from the 1800's.
@nomasde1
@nomasde1 10 месяцев назад
Thank you for the information.
@KyleGagen
@KyleGagen 10 месяцев назад
If the power head isn’t fully flush to the base, in other words the pins aren’t fully in will it not work?? Was not getting heat on second floor and noticed the he power head has a gap between the head and base. Pin wasn’t fully in the hole so took off and put on fully. Now have heat, could it have been that simple?
@scotttaylor3049
@scotttaylor3049 10 месяцев назад
Possibly, the powerhead has a plunger that pushes into the valve body to open the valve. If the head is not anchored, it will just push the head away instead of opening the valve. If you have heat, that was obviously the problem sometimes though the heads, will loosen and unhook themselves, I know that sounds strange, but it does happen. if it happens again, you will have to replace the powerhead.
@Karnol428
@Karnol428 7 месяцев назад
So where I’m lost is if you have a 40va transformer feeding thermostat and R 24 v to terminal 1 and terminal 2 is common. 3 is apart of TT but that diagram looks like TT and the 40 VA transformer cross. I thought that would be like crossing two transformers then?
@scotttaylor3049
@scotttaylor3049 7 месяцев назад
Those wires are after the load so it doesn’t effect the voltage. Its similar to connecting all the white wires (common wires) together in your house wiring together. USA 120 volt AC.
@jl901645
@jl901645 10 месяцев назад
IF THE LEVER MOVES FREELY NO RESISTANCE???
@scotttaylor3049
@scotttaylor3049 10 месяцев назад
Normally if the lever moves freely then the thermostat is calling and the zone valve is open. You can test this by putting a voltmeter on terminal one and two and you should read 24 V. Or turn down your thermostat and after a few minutes check to see if the lever only goes about halfway and then you feel resistance, then you know the valve is closed. It is possible the zone valve body is stuck open. it would be extremely rare but it could happen.
@jl901645
@jl901645 10 месяцев назад
@@scotttaylor3049 valve body stuck in the open position sprayed some w40 hit with hammer and started working thank you
@Fireneedsair
@Fireneedsair 9 месяцев назад
If you open the valve manually by pushing it to the left against the resistance . Can you then turn it off my moving it back to the right?
@scotttaylor3049
@scotttaylor3049 9 месяцев назад
@@Fireneedsair yes as long as the thermostat is not calling
Далее
Zone Valve Wiring Explained For Beginners (Honeywell)
10:49
🎙А не СПЕТЬ ли мне ПЕСНЮ?🍂
3:04:50
Я ж идеальный?😂
00:32
Просмотров 96 тыс.
Taco zone valve power head replacement
9:04
Просмотров 25 тыс.
4 Wire Honeywell zone valve overview
16:10
Просмотров 1 тыс.
TACO ZONE VALVE REPLACEMENT ATTENCHION PROPRESS QUEENS
22:19
Replacing Honeywell 2 port motorized valve
5:24
Просмотров 4,1 тыс.
3 wire taco zone valve operation explained
8:45
Просмотров 266 тыс.