The Easiest Way To Pull Large Gauge Electrical Wires Through Conduit 

TipsNNTricks
Подписаться 177 тыс.
Просмотров 311 тыс.
50% 1

Fish Tape Puller 100ft: amzn.to/3fRp3UB
Fish Tape Puller 200ft: amzn.to/3s46UoO
My Gear:
Samsung S20+: amzn.to/3osxztR
GoPro 8: amzn.to/3hYnnqU
Wireless Microphone: amzn.to/2TY03yn
Mic: amzn.to/2x5dcII
DJI Mavic: amzn.to/2v4Icex
-----------------------------
UK Shoppers:
Fish Tape Puller: amzn.to/3d1Yzhh
Camera Gear-
Samsung S20+: amzn.to/3pt8xvZ
GoPro 8: amzn.to/31cdZtS
Wireless Microphone: amzn.to/3aKFQmo
Mic: amzn.to/2x5wnSM
DJI Mavic Drone: amzn.to/2mCBpVN
______________________
India Shoppers
My Gear:
Mic: amzn.to/2vE4IdM
DJI Mavic: amzn.to/2tQZ3lp
Canon DSLR: amzn.to/2tQDjWF
__________________________
Head To:
My vlog videos: / bensbergfilms
______________________
Want to Buy a cup of coffee for me?
Thank you coffee keeps me making great videos:
Bitcoin Send Here: 1LoMfSUF9p9stdxPqHPnzE3EjcGWfodMMN
PayPal Address: Chrisbensberg@yahoo.com
Ripple XRP Here: rPVMhWBsfF9iMXYj3aAzJVkPDTFNSyWdKy
______________________
Instagram: / chrisbensberg
Like Me On Facebook: / cbensberg
Twitter: / chrisbensberg
______________________
Subscribe Here For More Amazing Videos
/ tipsnntricks
______________________
Thanks for watching.
God Bless
Business Only Please: diysavemoney@yahoo.com
______________________
In this video we show you the easiest way to pull electrical wires through conduit when running new wiring through your home, garage or pull barn in this case. These tips in this video will save you time and headaches figuring it out. Thank you for your time and thank you for watching.
DISCLAIMER: This video and description contains affiliate links, which means that if you click on one of the product links, we’ll receive a small commission.
#PullingElectricalWires #Building #Wiring #TipsNNtricks

Хобби

Опубликовано:

 

7 апр 2021

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 154   
@Locky78btcourt
@Locky78btcourt 3 месяца назад
brother man you sound just like Hank Hill for a moment i thought I was watching the real thing 😂😂👊🏽👊🏽
@jimhelling5188
@jimhelling5188 9 месяцев назад
Informative video for weekend warriors looking for some tips, but as someone in the trade for years I would make a few suggestions. First, you unnecessarily started pulling the wire from the main panel, which means you pulled the entire length of the wire that will be going underground to the barn through the house. Start at the outside LB that’s on the house and pull what you need to the house panel, and then pull the remainder over to the barn. Second, you can’t re-identify anything smaller than #4 as a ground. Third, forget the fish and vacuum a pull string through. Much easier and quicker and pull string won’t jam up on you. Fourth, there’s no need to pull the extra 20’ you have through the LB inside the barn up to the panel when you only need 7 or 8 feet. Lastly, use a pulling grip and save time by not having to strip wires to attach to the fish and save yourself a half roll of tape.
@rontodd6061
@rontodd6061 6 месяцев назад
This process for connecting wires worked great for us pulling 4-6awg wires through 150ft of conduit. Thanks for the info!
@KevinCoop1
@KevinCoop1 Год назад
Fact: “Handier than sliced bread”. The first loaf of pre sliced and packaged bread was done in Chillocothe, Missouri. They still have that first loaf at the bakery. Their second bread cutting machine is at the Smithsonian.
@TheFalconJetDriver
@TheFalconJetDriver 11 месяцев назад
When I was a teenager I enrolled in an apprenticeship in electronics at the Norfolk Naval Shipyard while in high school. I pulled a lot of cable my first 6 months. I learned at lot of tricks. I decided to be come a professional pilot and retired from an aviation career! Good video.
@dewaynehanson3751
@dewaynehanson3751 2 года назад
EXCELLENT JOB DUDES ! ! ! ELECTRICAL FISHING 101 I really did enjoy this video... 5 STARS
@randymays6089
@randymays6089 11 месяцев назад
I need to run electric out to a shed and was always curious on what type of wire to use. Video helped a lot thanks
@peterdsf60
@peterdsf60 7 месяцев назад
Very helpful, particularly the tip on clipping wires from the tip to reduce the width of the bundle attached to the fish tape
@jrpritchard1622
@jrpritchard1622 2 года назад
awesome video i wish we at video like this back in the day when i was learning keep the videos rolling
@Imwright720
@Imwright720 2 года назад
I always oversize the conduit and wire. I ran some conduit ahead of the electrician coming. He said I just wasted my money. In my mind it’s future proofing it. It was for a generator and when it goes a bigger one will go in it’s place. The larger wire will meet code. The pvc conduit used to be so cheap why not. The wire wasn’t that much more and I won’t have to buy a larger one again for the same thing.
@thegeekisland
@thegeekisland 23 дня назад
Great job on the video! Thanks for making it
@jesseruiz2337
@jesseruiz2337 5 месяцев назад
His voice reminds me of Hank Hill from that one cartoon King Of The Hill lol. Great video, thanks for sharing.
@jeremyromero9790
@jeremyromero9790 2 года назад
This works good for propane and propane accessories..
@roswald392
@roswald392 2 года назад
You can tell this guy is a professional electrician...just having proper conduit and conduit body fill, GFI breakers in the panel, correctly marking his ground and neutral conductors, using plastic insulating bushings, and explaining sub-panel ground/neutral separation shows his familiarity with the 2020 NEC. It is refreshing watching a video that does NOT have a handful of glaring 2020 NEC violations. If more electrical installation videos were made by qualified tradesmen like yourself, we would all be much safer from electrical hazards and fire.
@beauwoodbury1112
@beauwoodbury1112 Год назад
It’s not even about qualified persons most of the tine just because they come out with a new code every three years doesn’t mean everywhere follows suit most places aren’t even on the 2014 still. I actually haven’t worked in a place besides Kansas City that requires 2017 I imagine it’s probably different in metropolitan areas on the coast but out here in Kansas and Colorado it’s all governed by the county there is no state licensing or regulation I’ve worked in places where it’s only enforcing 2002 NEC
@B_dilly
@B_dilly Год назад
There’s several violations actually lol. I would hope you’re not an electrician yourself 😂
@christophervallejo9838
@christophervallejo9838 Год назад
​@@B_dillyright, couldn't tell if he was being sarcastic or not
@YourAflacGal
@YourAflacGal 2 года назад
GREAT instructions!
@frontiervirtcharter
@frontiervirtcharter 2 года назад
Starting the black tape at the wire rather than the fish tape makes it overlap in a way that won't tear up as much in the conduit .. Think about how fish scales point away from the direction the fish moves
@joshthompson2152
@joshthompson2152 3 года назад
Damnit Bobby!
@al52269
@al52269 2 года назад
Great video Thanks for sharing
@oliverburke
@oliverburke 8 месяцев назад
Nice King of the Hill version 😄. I liked it!
@marksmith5208
@marksmith5208 Год назад
Thanks a lot. Now I know what I'm in for 😊
@ryanwallace4204
@ryanwallace4204 Год назад
What a great video!
@gavinnewscum
@gavinnewscum 2 года назад
Well done guys
@FliesLikeABrick
@FliesLikeABrick Год назад
What size conduit was being used in the video? Apologies if I missed it being said. Looks like maybe 1-1/4"?
@211dabomb
@211dabomb 2 года назад
Love this video
@librealbedrio367
@librealbedrio367 Год назад
Thank you gentlemen. Very helpful. Nothing like experience and the ability to convey what you know as well as do with excellent communication skills. Do you recommend a similar technique when running 2-2-2-4 aluminum SER through 2 inch PVC conduit on an exterior wall to connect to a sub-panel in a garage? Or is it ok tosnake the cable through the separate pieces of PVC build and cement the conduit run around the cable , then install it as a made unit?
@todd5082
@todd5082 6 месяцев назад
I was wondering the same thing with my install, 2-2-2 alum wire through 2” conduit. What did u come up with for your situation?
@gnoswtx
@gnoswtx 2 года назад
heres a tip, buy some wire strippers
@vy10mac9
@vy10mac9 10 месяцев назад
My go-to for making my bay leaders. Haven’t failed me yet.
@sh2697
@sh2697 11 месяцев назад
I am running romex 6 gauge from my main to my tesla outlet. I plan to run through emt first and then it has to go underground, in gray PVC. Can I place the romex in there the entire length from main to my outlet?
@kimandylawrence4199
@kimandylawrence4199 2 года назад
Nice video. The #8 EGC should be either bare, green or green with one or more yellow stripes per NEC 250.119 . It appeared to be black. Tape cannot be used on conductors smaller than #4 per NEC 250.119(A). Also, the fires associated with aluminum wiring occurred because the terminations were not listed for aluminum conductors at the time. Today, most terminations are listed for aluminum or copper so there is little to no risk of fires.
@beauwoodbury1112
@beauwoodbury1112 Год назад
Meh it’s his property out i the middle of nowhere 😂 he is the Authority having Jurisdiction I imagine they probably don’t have any regulation where they are anyways
@supporterofeverythingyouli6255
@supporterofeverythingyouli6255 11 месяцев назад
Also #6 copper is inadequate AF for a 70amp circuit. Dude's old and clueless!
@JesseKlaus
@JesseKlaus Год назад
I like to use a couple courses of bale twine, a rag, and a shop vac 😅
@ranjodhdhindsa1479
@ranjodhdhindsa1479 Год назад
What does JAT mean written on fish box?
@jonathanwells5508
@jonathanwells5508 2 года назад
Best video I've seen on this topic! Thank you.
@crimoney
@crimoney Год назад
what's the size of each wires and the hole of the pipe?
@Rockman05X
@Rockman05X 2 года назад
I like that you got the job done, but pulling string or rope would have helped lots. You wouldn't have needed two fish tapes. Nor would you have to undo the wires from the fish tape after reaching the first LB corner because it would have been made up on the pull string. Untie it and re-tie it to the fish tape. Or is the fish tape is long enough, you can also push it from the beginning, then through each LB and pull the wire through it the same way. Also, i believe you need another grounding rod since it's a separate building.
@Sparkeycarp
@Sparkeycarp 2 года назад
I agree with routing through the LB and avoiding reattaching every time. Saves a lot of time. I use pull string or 1/2' nylon pull tape for this. The pull tape handles better and does not twist up as bad as the jet string. Also you can suck a mouse attached to the jet string through PVC easily with a vacuum.
@ei1209
@ei1209 2 года назад
"handier than sliced bread" god I'm gonna miss this generation when they're gone!
@heyyou9693
@heyyou9693 2 года назад
We are that next generation. We can pass along this information. This is definitely going to help me with my project at work.
@BlackVibeBallsack
@BlackVibeBallsack 2 года назад
Rolling that fish back up isn't very handy....
@morgan79347
@morgan79347 11 дней назад
No expansion relief coming out of the ground?
@benjaminhammell1272
@benjaminhammell1272 Год назад
Hi, how did you affix the PVC conduit to the non-threaded LB? Just insert with the glue and no fittings needed?
@alexagiyants8373
@alexagiyants8373 Год назад
Yes the conduit is able to slide into the LB without any fittings. Make sure to glue for a strong connection.
@lesliewood4069
@lesliewood4069 4 месяца назад
Great job🌹🌷❤️👍🙏🙏🙏
@spelunkerd
@spelunkerd 3 года назад
People talk about not putting two LB fittings back to back, but you did it and it worked great. I guess they are concerned about the radius of the double turn being too tight. I don't see a problem, because you weren't trying to stay inside a thin finished wall. In fact this is the best option, since inside the room you don't want a wide turning elbow.
@stephenvancampen7393
@stephenvancampen7393 2 года назад
but going more then 360 turns isn't to code, is it, or is it that you are not pulling thru more then 360 at a time the reason for the code so that you don't stress the wire with resistance? The radius seems ok because its individual wires (should do the calculation).
@alexjones7845
@alexjones7845 2 года назад
@@stephenvancampen7393 "you are not pulling thru more then 360 at a time" is the limitation in the code because any more turns can quickly become impossible to pull wire through. It's perfectly fine to have greater turns in the whole circuit as long as there are sufficient pull points for each section.
@deaconpladek
@deaconpladek 2 года назад
general question: if I have proper earth ground on main panel, and I run a sub-panel box in garage, do I need to add an additional earth ground? or is the smaller ground connected to main box acceptable?
@chrisruss7863
@chrisruss7863 Год назад
You need a 4 wire feed to all subpanels, and whenever the building is detached, you need 2 ground rods
@deaconpladek
@deaconpladek Год назад
@@chrisruss7863 Hi Russ, OK good with the four wire and separated buildings have a ground rod. Can I assume I can tie the two "ground" wires together in the garage sub-panel since they are both "earth ground" 75 feet from one another?
@chrisruss7863
@chrisruss7863 Год назад
Yes, the 2 ground rods tie into the subpanel at the detached building with a #6 AWG or larger copper conductor.
@jimhelling5188
@jimhelling5188 9 месяцев назад
In addition to my other comment, I always use white tape when I am taping something together to pull it. Black tape leaves that nasty black sticky residue if you need to I tape anything. White or any light color tape doesn’t.
@1hons1
@1hons1 Месяц назад
Omg at 8:10 you start sounding like Hank Hill 😮
@torykarovlogs3463
@torykarovlogs3463 3 года назад
nm b indoor wire can be bury? Or is under ground
@nest1000
@nest1000 2 года назад
Pops is very smart
@Combat556
@Combat556 2 года назад
Your ground was #8 black, no green phase tape ?
@beauwoodbury1112
@beauwoodbury1112 Год назад
He is a master he’s got this
@ricktryder787
@ricktryder787 Год назад
Damn it Bobby.... That boy ain't right.
@SMILEYRLR
@SMILEYRLR Год назад
They make wire jacket stippers that make life easy.
@willcamp6319
@willcamp6319 Год назад
When you use black wire with ground put green tape so you can tell what the ground is or use green wire
@robertplas3947
@robertplas3947 3 месяца назад
70 amp breaker shown on 6 awg??
@taylorjams4845
@taylorjams4845 2 года назад
Always tape towards the head, not away from it. Otherwise It barbs and creates restrictions.
@love2gocamp
@love2gocamp 2 года назад
Just curious. Is it okay to use a smaller wire for the ground? I have to run some 6 gauge wire in my trailer. Thanks.
@robmespeedy
@robmespeedy Год назад
I just got an estimate to install a sub panel in my garage. The electrician said all the wires would be 6 gauge.
@Nick-bh1fy
@Nick-bh1fy Год назад
@@robmespeedy ground can be slightly smaller size wire
@1970jeffreyg
@1970jeffreyg Год назад
@@robmespeedy ground can be next gauge smaller, not a problem
@sparkyjerred419
@sparkyjerred419 Год назад
You could use #10 for the ground
@sparkyjerred419
@sparkyjerred419 Год назад
#10 ground for 25-60 amp, #8 for 65-100 amp.
@CSFitness1
@CSFitness1 2 года назад
Shouldn’t 4AWG be used with a 70A breaker according to the NEC?
@Ryan-ws3rc
@Ryan-ws3rc 2 года назад
6 AWG THWN in a raceway is good for 65A at 75 F. Next standard OCPD is 70A. This is a-ok by NEC. You're probably thinking of NM-B. That would need 4 AWG.
@hankkline7300
@hankkline7300 2 года назад
@Rese Shively NEC requires outside disconnect for outbuilding more that one 20A circuit. Also requires smaller than #4 to be of the correct color. Cannot tape #8 green must be green insulation. (which he didn't do any way). Needs ground rods. He did not need a flex leader for a little run like that, and if you get stuck because you didn't push the PVC 90* all the way into the coupling, you can tie several loops of pulling string on the end of the first fish tape, and then open the hook on the second one and hook it very easily then pull it through.
@Sparkeycarp
@Sparkeycarp 2 года назад
I agree, I would have used #4 for this distance at 70 amps. Especially if the are putting in a car charger or some other constant use device as defined in the code. Yep, missed the exterior disconnect.
@billmonroe8826
@billmonroe8826 Год назад
Any reason why you didn't run the wire before you buried it?
@1ltlbrnc
@1ltlbrnc Год назад
You almost always are pulling wire through a conduit after it is completely installed including buried. Unless you're using the incorrect wire or to small of a conduit it shouldn't be an issue to pull the wires through.
@heypauly2002
@heypauly2002 Год назад
70 AMPS on 6 AWG??
@AM1015-
@AM1015- Год назад
wheres the expansion coupling before the LB's? ground thaw will stress those pvc conduits apart
@phyde1885
@phyde1885 Месяц назад
Yes they will ,I forgot to install 1 in Just a 11.5' vertical and it Banana'd over Time. I Just took care of it though. I didn't have any wire in it yet,have to finish the main side upgrade.
@Anon-bf8zs
@Anon-bf8zs Год назад
That ground needed to be green per NEC. Only ground conductors larger than #6 can be black and taped on the ends.
@AquaTech225
@AquaTech225 Год назад
Who’s gonna check it 😂
@hbparmer9787
@hbparmer9787 2 года назад
great job, Father and Son
@martyflickinger
@martyflickinger Год назад
You forgot the last step: documenting the new breaker on the door label. It's a pet peeve of mine that every house I've ever owned had missing/outdated/vague labels in the load center. Do your future self or electrician a favor and update the labels
@slimsung3971
@slimsung3971 2 года назад
I thought 6 AWG was rated for 65 Amp, you would need 4 AWG to avoid frying the wires on 70A breaker.
@hliz8818
@hliz8818 2 года назад
Yep.. poor dad.. probably read the table wrong by accident..he definitely knows what hes doing.. father is the tradesmen.. still valuable video.. but should downsize breaker thats all.
@thomasmarable6818
@thomasmarable6818 2 года назад
Its a feeder 65 not a standard breaker so you can go up 1 size to a 70 amp
@Pepe-dq2ib
@Pepe-dq2ib Год назад
@@thomasmarable6818 where does it say that?
@johndavies2949
@johndavies2949 7 месяцев назад
No. You can put the # 6 on the 70 amo breaker because there isn't a 65 amp breaker and the code allows you to go to the next size up if this is the case.
@fuzion430journey3
@fuzion430journey3 2 года назад
Wire is un size ,for 70 amp breaker , especially for the run u have
@hliz8818
@hliz8818 2 года назад
Sure is..
@thomasmarable6818
@thomasmarable6818 2 года назад
If he is less then 150 feet and his continuous load is not more then 80% then he is ok. This is a feeder and #6 is good for 65 amps which is not a standard overcurrent device so you can go to next size up 70 amps. Learn the code
@beauwoodbury1112
@beauwoodbury1112 Год назад
Ah but if you remember he was talking about how the wire he was using had a different kind of insulation it’s not thhn so if I had to gues its probably Thwn that he used rated at 90 degrees ambient and technically I wouldn’t even consider that a long pull it’s probably only 100 feet at most not that long
@MattMuckleroy
@MattMuckleroy Год назад
Use 2" conduit with large sweeps and 30" ditch you wouldn't have to go through all of that, would you? I mean with the fishing tape.
@brandoncole6358
@brandoncole6358 2 года назад
I'm pretty young haven't run into that problem yet
@yaboiii9062
@yaboiii9062 2 года назад
Mule tape is what you needed to use . Local 613
@TheFalconJetDriver
@TheFalconJetDriver 11 месяцев назад
The correct terminology is your father removed some of the strands of the conductors so they are thinner in the eyelet! I agree I support local suppliers over big box stores when I can.
@cryptocred5754
@cryptocred5754 2 года назад
Large?
@dondrier1051
@dondrier1051 9 месяцев назад
Stupid question maybe but why can’t you put the conduit on the wire as you’re burying it?
@johndavies2949
@johndavies2949 7 месяцев назад
You could but the code says your conduit system has to be installed as a complete system before you pull wires. But people do it anyway. See nec 300.18 (A). Complete runs.Raceways(conduit) shall be installed complete between outlet,jinction, or splicing points prior to the installation of conductors.
@dondrier1051
@dondrier1051 7 месяцев назад
@@johndavies2949 now I know. Thanks
@jeanettaervin5807
@jeanettaervin5807 3 года назад
Hello Chris
@TipsNNTricks
@TipsNNTricks 3 года назад
Hello Jeanetta:) I hope your doing amazing:)
@mrindependent1
@mrindependent1 Месяц назад
Should have left the flex lead on the wire and and disconnected it from the fish tape Then pushed the fish tape and reattached the flex lead
@jamesonsonoma748
@jamesonsonoma748 3 месяца назад
You can’t put 6 gauge on a 70 amp breaker
@badgthom
@badgthom 5 дней назад
Why not? You can oversize your wire, but you can't undersize your wire to your breaker ampacity, meaning your breaker ampacity can be lower than the wire ampacity that it is fedding, but you can't have a larger breaker ampacity feeding a wire with a lower ampacity.
@joer3089
@joer3089 2 года назад
is this Hank Hill? lol
@liyoung7149
@liyoung7149 Год назад
wire stripper not available?
@mistervacation23
@mistervacation23 2 года назад
No wonder the water don't work those pipes are all clogged up with wire.
@shad0wrealms116
@shad0wrealms116 2 месяца назад
Great 3 stooges reference 😂
@mistervacation23
@mistervacation23 2 месяца назад
@@shad0wrealms116 Classic
@armorstef
@armorstef Год назад
Start in middle of run easy 1/2 runs Instead a full run???
@thecopperiris
@thecopperiris Год назад
Why didn't you color code the wires? I get that they're both hot, but as a general rule, you always mark the different phases..
@edgarzamora1996
@edgarzamora1996 Год назад
Is the same phase
@chaser9363
@chaser9363 Год назад
With all due respect. WTH is a cepticle?
@clintonr362
@clintonr362 Год назад
Sounds like Hank Hill
@jimcook8241
@jimcook8241 2 года назад
Large gauge? Im using mule tape and rope to pull with. Large gauge I assume is 3/0 and up.
@beauwoodbury1112
@beauwoodbury1112 Год назад
Yeah # 6 through two in is a piece of cake compared to a 3/0 service entrance pull
@rudyardgomeas6042
@rudyardgomeas6042 Год назад
It's odd you say aluminum is "dangerous" for houses, yet the large wires that come from poles; aren't they aluminum?
@edbouhl3100
@edbouhl3100 8 месяцев назад
The hardware has to be designed for aluminum, or both aluminum/copper. Aluminum wire expands and contracts more with temperature than does copper. Aluminum wire in a copper only fitting can work itself loose and cause arcing and possibly fire. Aluminum in contact with copper also corrodes, so a protective paste is needed for those connections.
@dorkman112
@dorkman112 2 года назад
That is the whackest tape job I've ever seen, and the fact that a veteran sparky is doing it blows my mind.
@BlackVibeBallsack
@BlackVibeBallsack 2 года назад
Well...he was using a 1" pipe so...it worked..
@Kerem-qh1jm
@Kerem-qh1jm Год назад
that conduit is so thick you don't really need any special instruction at all.
@KevinCoop1
@KevinCoop1 Год назад
I can tell your father is an electrician! All the cut off crap is thrown on the floor. Laborers job! I’m a retired electrical design engineer. I see an issue that is important. Article 225 Outside Branch Circuits and Feeders has a requirement for a means of disconnect when you feed a detached building from another. Often missed because most do not read 225. You are supposed to be able to disconnect at one point at or near where the feeder enters the building. So, a main circuit breaker or a Safety Switch are needed to meet NEC. Going to try to find the next video for something else possible but will not know until completed install. My purpose is only Safety, not just pointing out errors.
@joewebb4836
@joewebb4836 7 месяцев назад
I would have fished from garage, then into house....no removing wire. Smarter not harder...I beg to differ !
@hliz8818
@hliz8818 2 года назад
Wait what..??!!! 6awg wire for 70 amp breaker.. ??
@hliz8818
@hliz8818 2 года назад
That should be number 4 wire.. for 70 amp breaker... 🤦🏻‍♂️
@thomasmarable6818
@thomasmarable6818 2 года назад
On feeders if it just under a standard over current device you can go up next size. #6 good for 65 amps so you can go up next standard size which is 70 amps
@doobeone
@doobeone 2 года назад
Hank hill?
@brianshaw6072
@brianshaw6072 2 года назад
Hank hill. Is that you doing electrical work?
@SB-vl4rh
@SB-vl4rh Год назад
Ibew electrician here, they are called fish tapes, not fish tape “pullers” never pull your cable with your fish tape. Use a PULL string:
@johndavies2949
@johndavies2949 7 месяцев назад
Bullshit!
@michaelfasciani537
@michaelfasciani537 Год назад
🤣
@stevenreeves4766
@stevenreeves4766 Год назад
appreciate the video but #8 wire is not large gauge. I have to pull 1/0 wire.
@mitchellhardy8053
@mitchellhardy8053 7 месяцев назад
Friends don’t let friends use Commercial Electric tape. 😑
@supporterofeverythingyouli6255
@supporterofeverythingyouli6255 11 месяцев назад
Number 6 wire on a 70amp circuit? 😂😂😂 it doesn't cost to hire professional it pays....😂😂😂
@stevenreeves4766
@stevenreeves4766 Год назад
That wire is not large Guage wire. Try pulling 1/0
@gsibert1
@gsibert1 Год назад
Everything is relative, 1/0 is on the small end of the spectrum where I work. Try pulling 1000 MCM copper 1000' thru 6 -90's and then vertically 18 stories Reply
@stevenreeves4766
@stevenreeves4766 Год назад
@@gsibert1 I hear you, I was just trying to say that I consider pulling #8 wire fairly easy but you start getting into #1 and larger is gets to be a pain. I can only imagine that larger stuff you mentioned.
@wvcaver774
@wvcaver774 6 месяцев назад
hahaha try 750 MCM
@thomasmarable6818
@thomasmarable6818 2 года назад
Glad I wasn't pulling that wire, what a messy head.
@peterturner5073
@peterturner5073 2 месяца назад
I thought this was for large gauge. I'm trying to bend 150 amp cable through a two inch conduit and these guys are minor league.
@dannydee9919
@dannydee9919 Год назад
Cot damn does he talk too much. Just pull the freakin wire!!!!
@thomasheyman2524
@thomasheyman2524 2 года назад
Ok sure. Terrible wire stripping technique. Painful to watch. Also, why would you tape the fish tape like that?? Adds friction to the pull.
@TheFalconJetDriver
@TheFalconJetDriver 11 месяцев назад
Why would anyone have a hot water heater? I have a cold water heater! 😁🛫 dang Kidd’s today!
@pinkiepie1656
@pinkiepie1656 10 месяцев назад
Nah. When the element kicks on, the water is still technically 'hot'. So it is a hot water heater:)
@jamesrockford6700
@jamesrockford6700 Год назад
dish washing soap and water works just as well for a lubricate
@eltoroturcoenbahamas7083
@eltoroturcoenbahamas7083 2 года назад
nice job guys
@dickcheesewiz
@dickcheesewiz Год назад
Instead of pulling the 2nd fish back through just pull some nylon string.
Далее
POLI зовет Газана
00:12
Просмотров 273 тыс.
How NOT to Wire Light Switches in 2024 (New Rules)
15:21
How to Pull Heavy Gauge Wire with a 10,000 lb Winch
14:15
DIY Pulling Buriable Electrical through PVC
5:29
Просмотров 1,1 млн
Wire Pulling - The Basics
6:44
Просмотров 200 тыс.
деревня.лето.юность.эх
1:01
Просмотров 20 млн