trane unit with bad RTRM board 

Anthony Reardon hvacr
Подписаться 1,7 тыс.
Просмотров 34 тыс.
50% 1

The RTRM was bad. It would cycle the indoor blower motor on/off while in cooling. This caused the unit to freeze up.

Опубликовано:

 

14 авг 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 49   
@gregob-team4642
@gregob-team4642 5 лет назад
Awesome stuff man. My name is Greg Gurule I just finished my first term of hvac school I start my second term in January for the residential part of it. This semester was by far the most mentally challenging for me but its all making sense now and clicking. I go to school in Albuquerque New Mexico @ Central New Mexico Community College. I just recently came across your Channel and you gained a new subscriber can't wait for more videos to learn from to go along with what Ive already learned in school thanks keep them educational videos coming out.
@20antman
@20antman 5 лет назад
Congratulations on getting through your first semester bro! This is really a great trade. I love it. Thank you for subscribing to my channel. I appreciate the support. As your reading a topic in your book maybe try doing a youtube search. possibly someone posted a video on it. Then you can watch the video and get a good understanding of what your reading. just an idea. I'm glad my videos can help. I will try to post some soon. shooting the video in the field is easy. The hard part is editing the video once i get home. lol
@djastram
@djastram 5 лет назад
On Trane units, a decade box on the test terminals really saves time. Thanks for sharing.
@20antman
@20antman 6 лет назад
There was a General contractor that recently redid the duct work. This unit has undersized duct work causing the low suction pressure and super heat. This is why i said there is not much i can do right now.
@coolezum
@coolezum 5 лет назад
Anthony Reardon hvacr leave the filter door or the fresh air wide open😉😜 small fresh air on dat!
@JC-mq3bn
@JC-mq3bn 3 года назад
Had to troubleshoot a board today, compressor fault. Didn’t take long, but was also getting com errors. Didn’t know which board it was. Sense those boards are so hard to troubleshoot luckily there was more than one unit and we swapped a board at the time and the LED7 cleared and it was all good from there.
@Eltico316
@Eltico316 Год назад
That reminds of the Texas de Brazil rooftop down on Alton Rd in Miami Beach.
@20antman
@20antman Год назад
Yep that’s where it is. But these were the ruts that cooled the private ball rooms about 10 -15 years ago. But about 8 years ago Texas de Brazil down sized. These rtu’s now cool private offices for Miami Beach marina. About 15. Years ago I serviced all of the Texas de brazils a/c & refrigeration equipment. I know those accounts pretty good. Do you still service Texas de Brazil?
@Eltico316
@Eltico316 Год назад
God no, that was 3 HVAC/R companies ago and thankful I don’t go there anymore. Crappy equipment, especially dolphin mall TDBrzl
@Eltico316
@Eltico316 Год назад
I recognized the cooling tower while watching your vid, lol
@20antman
@20antman Год назад
@@Eltico316 Yea man I take care of the cooling tower, it’s for the marina. But now I don’t do anything for Texas de Brazil.
@20antman
@20antman Год назад
@@Eltico316 Hell yea dolphin mall was tough. Grettle was the manager there for a long time. You had to go through 3 different ladders. Lol Dude we used to put an extension ladder from the 2nd floor straight to the rooftop. Like a short cut.
@syedbasheer8210
@syedbasheer8210 4 года назад
Great video🍾
@throttlebottle5906
@throttlebottle5906 6 лет назад
good job, and explanation to not break the new control board by "impact gunning it down" ..... no reason to fix bad airflow due to poor engineering up front!!!!!!!!!!!!!! yes filters are guaranteed dirty long before service call and overlooked on purpose! why have filters? just spew the dirty air back and plug the evap. coils solid LOL!!
@khanshahzad77
@khanshahzad77 3 года назад
nice information thanks, sir, I would ask you about the blinking light in the p.c.b of trane package r410 can you please give me detail about? thank you
@cthomaspac
@cthomaspac 4 года назад
You should use the TEST terminals. To run the board thru it’s test mode next time. The RTRM will flash twice if there is a diagnostic .
@Tanneritefilledfido
@Tanneritefilledfido 4 года назад
Ive noticed that when ever the blower motor chatters its 10/10 times the rtrm board on these old tranes
@20antman
@20antman 4 года назад
Yep I agree with you. I replaced so far 3 of those ftrm boards from chattering blower contactors. Of course not on the same units but in different trane packaged units.
@ronaldzeigler9057
@ronaldzeigler9057 4 года назад
You have got it brother
@ninosanchez8798
@ninosanchez8798 3 года назад
Are you driving those Nissan service trucks?
@20antman
@20antman 3 года назад
Yea. I’m assuming your in the miami area??
@ninosanchez8798
@ninosanchez8798 3 года назад
No I’m in Mexico but I had the same Truck
@20antman
@20antman 3 года назад
@@ninosanchez8798 oh ok cool bro. Yea they are tough vans. He have a few of them. A lady ran the red light and wacked my van. My van barely moved. The turning radius sucks though.
@JCM2LA
@JCM2LA 6 лет назад
Good video thanks
@johanchalco5117
@johanchalco5117 6 лет назад
Nice repair. Them boards are a pretty penny. How you liking the Nissan nv van ?
@20antman
@20antman 6 лет назад
Yea a little pricey. But its the customers problem. The NV is nice. The turning radius sucks though. Making U turns is a pain. Chevy is letting the 2500 v8 with back up camera, power windows out the door $21k . That is a steal compared to the Nv up around $28-30k. I would jump all over the chevy if i can go back. At the time chevy was asking for more than my nv2500. Just figured ill give you some input. Thanks for checking out my video.
@johanchalco5117
@johanchalco5117 6 лет назад
Anthony Reardon hvacr I own Nissan 2 nv 2500 high roofs V8 and one versa note i4 for my estimates and an nv 200 4 cyl for service tech I love riding the nv 2500 but I enjoy paying for gas on the versa note😄
@joemorales9093
@joemorales9093 6 лет назад
Was stat on "fan auto" when board wouldn't bring fan on?...I currently have pretty close to same unit where as soon as unit is powered,heat will come on but not fan......but in "fan on",the fans comes on......I was gonna replace stat b/c the space temp is 70 & it's set for 70.......also,there is a bunch of these same units w/ the same stat....its the only stat calling for heat....all other stats in warehouse are set & read the same (70/70)......
@20antman
@20antman 6 лет назад
In my case the fan was set to " fan on". The control board ( rtrm board) was receiving a steady fan signal. But it kept cycling the fan. If your not sure i would swap the thermostat with another unit for a day or two. If the problem switches to the other unit then it must be the thermostat. If the problem still remains at the original unit. Then it could be the control board or something else with the unit. If you have several of the same thermostats just swap the face plate. leave the base and wiring attached to the wall.
@joemorales9093
@joemorales9093 6 лет назад
Anthony Reardon hvacr I'm gonna do exactly that.....thanks brother!!!!!......please keep making vids!.....
@MICKSHRED
@MICKSHRED 4 года назад
Dont you need 5 degree up to 10 for proper superheated vapor
@Patrick_1227
@Patrick_1227 Год назад
What kind of cooling tower was that in the beginning?
@20antman
@20antman Год назад
It was a Protec cooling tower.
@20antman
@20antman Год назад
It was a Protec cooling tower.
@airmechanical7163
@airmechanical7163 6 лет назад
Was that near the Miami Beach marina?
@20antman
@20antman 6 лет назад
yep
@rocker8692
@rocker8692 3 года назад
You related to the other Reardon who does AC in North Carolina?
@20antman
@20antman 3 года назад
No, Look at the spelling of our last names. It’s not even the same last name.
@andresland9906
@andresland9906 3 года назад
Why not use the test terminals?
@matthewgregory8218
@matthewgregory8218 3 года назад
Frozen compressor dangerous
@jonhvac
@jonhvac 6 лет назад
So do I get a commission of $ those leads make you?😁 I hope u went to the beach and kick those sweaty Crocs off and celebrated with an ice cold can of Pibb🍹 For job well done💪😸👍
@20antman
@20antman 6 лет назад
Hell yeah bro. I love those alligator leads. They definitely went to a good cause. I use them all the time. Thanks bro!!
@jonhvac
@jonhvac 6 лет назад
Anthony Reardon hvacr They defiantly went to a goid cause. God speed🙏
@mychoclabwinston
@mychoclabwinston 4 года назад
Or just use a damn screwdriver, why the need for a drill on such a sensitive part.
@20antman
@20antman 4 года назад
I hear you but everyone has their own preference. I prefer a screwdriver so you can feel how snug it is. Thanks for watching 👍🏻
@nilbertocohen4963
@nilbertocohen4963 3 года назад
please don't shake the camera all the time
Далее
Trane Voyager, no cooling. hvac service call.
11:13
Просмотров 2,5 тыс.
No AC, Trane package unit not cooling
13:08
Просмотров 89 тыс.
«Ой Бой» откуда выражение?
00:45
Qora Gelik
00:26
Просмотров 431 тыс.
Trane RTU Issues | HVAC
22:27
Просмотров 15 тыс.
Commercial Rooftop Units Troubleshooting- Fall 2020
1:47:59
New Trane RTU Start up
48:53
Просмотров 2 тыс.
Faulty what condenser fan motor or relay???
18:50
Просмотров 4,1 тыс.
Trane RTU with bad Economizer module
4:32
Просмотров 12 тыс.
Reliatel Training
7:25
Просмотров 22 тыс.
Trane voyager thermostat interface board
6:56
Просмотров 11 тыс.
Which HVAC Brand Do I Prefer?? | HVAC Business Owner
11:30
Compressor Won't Start On Trane RTU @ Data Center
8:15