Transformer Circuit breaker and Fuse size Calculation 

Rashid iqubal
Подписаться 3,2 тыс.
Просмотров 8 тыс.
50% 1

Transformer Circuit breaker and Fuse sizing Calculation.
Learn how to calculate proper size of VCB and Fuse for Transformer.
#electricalengineering
#rashidiqubal

Опубликовано:

 

8 сен 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 26   
@NomanQudrat-u2p
@NomanQudrat-u2p 2 дня назад
Brother very nice
@seanakiiki7670
@seanakiiki7670 5 дней назад
Great, thxu
@Rashid-iqubal
@Rashid-iqubal 5 дней назад
Thanks for watching...
@nazmulkabir2481
@nazmulkabir2481 6 месяцев назад
Very Very Informative and helpful
@Rashid-iqubal
@Rashid-iqubal 6 месяцев назад
Thanks for watching
@vinodkumarprajapati5182
@vinodkumarprajapati5182 16 дней назад
Very good
@Rashid-iqubal
@Rashid-iqubal 16 дней назад
Thanks 🙏🏽
@manmohandhir9117
@manmohandhir9117 5 месяцев назад
In India we follow iec rules and not nec rules.You can consult any state electricity authority and you will discover that proper fuse size for this transformer will be 80 A.CB rating for secondary will of course be 1.25 times secondary current.
@kaleemahmad6573
@kaleemahmad6573 6 месяцев назад
Why you did not consider the fault current of primary side of HT 33 KV brraker rating will come above 800 amp if you will see the fault current
@Rashid-iqubal
@Rashid-iqubal 6 месяцев назад
Actually In this video I explained CB current rating as per load.. For fault current calculation we should divide full load current (Is) / impedance. Short circuit current always higher than normal current rating of breaker. Every circuit breaker has two types of rating that is current rating and short circuit rating (ka) As per my first example we have selected 630amp circuit breaker and its short circuit current would be 52.49/4.71% =1.1Ka I will make another video which cover all safety protection. Thanks for watching
@brajeshtripathy7599
@brajeshtripathy7599 3 месяца назад
Please make a video on Transformer, DG sets, UPS selection in details.
@Rashid-iqubal
@Rashid-iqubal 3 месяца назад
Sure my next video will be on Generator and transformer. Thanks for your suggestion
@AfrozAlam975
@AfrozAlam975 11 месяцев назад
U explained very well and your voice is so energetic and crystal clear. May i request to please earthing wire and pit calculation pe ek video banayen. Like high rise sky scrappers, hospital and residential building me earthing and selection of bare copper wire clams and pit etc
@Rashid-iqubal
@Rashid-iqubal 11 месяцев назад
Thanks, sure i will upload soon..
@noelfaithfulkari2857
@noelfaithfulkari2857 Месяц назад
thank you sir for your amazing explanations. any video on transformer sizing??
@Rashid-iqubal
@Rashid-iqubal Месяц назад
@@noelfaithfulkari2857 thanks for watching, my next video will be on transformer size calculation method.
@manzoorkhan5246
@manzoorkhan5246 Месяц назад
For sizing breaker, contactor and cables which standard you normally use?
@Rashid-iqubal
@Rashid-iqubal Месяц назад
@@manzoorkhan5246 NEC
@manzoorkhan5246
@manzoorkhan5246 Месяц назад
@@Rashid-iqubal please explain it further or mention any specific code like 23567
@nategreene45
@nategreene45 6 месяцев назад
What if it is a step-up transformer? 480v, 3ph to 4,160v, 3ph. Say impedance is 5%. Am I using 600% factor from the table to size the circuit breaker on the primary (480v) side?
@deepakmuyal4096
@deepakmuyal4096 4 месяца назад
Kindly upload substation design videos
@Rashid-iqubal
@Rashid-iqubal 4 месяца назад
Will upload soon
@souravhajra1645
@souravhajra1645 6 месяцев назад
What do we use to select a circuit breaker, full load current value or short circuit current value? Please clarify, i am so confused..
@Rashid-iqubal
@Rashid-iqubal 6 месяцев назад
For circuit breaker calculation you need both full load current and short circuit current. Through full load current you can find out the rating of breaker. If current exceed then full load current in any circumstances like over load or short circuit, breaker will be trip. While short circuit current work when huge amount of current flow like 100 or thousand times more then full load current then breaker trip immediately in few mili second. It will protect system from fire as well as breaker it self. So if you purchase circuit breaker you need both rating. Eg 1000A ACB with 50KA short circuit current in 1sec. Or 36KA in 3sec. Thats mean circuit breaker can tolerate 50Ka current upto 1 second. Hope you understand.
@souravhajra1645
@souravhajra1645 6 месяцев назад
Thanks alot, understood completely sir..
Далее
BREAKER AND CABLE SIZES FOR ELECTRICAL CIRCUITS.
11:39
Просмотров 173 тыс.
Cable Selection Method | Cable size calculation
13:08
Они захватят этот мир🗿
00:48
Просмотров 502 тыс.
How Surge Protective Devices Function
10:41
Просмотров 10 тыс.
What is a Lost Neutral? Lost Neutrals demonstrated.
12:21
Short Circuit Fault Level Calculation
7:06
Просмотров 169 тыс.
HOW TO SIZE A TRANSFORMER !
15:45
Просмотров 33 тыс.
Cable tray size calculation method in simple way
8:37