VFD DC Overvoltage में Trip हो रहा है ? DC Overvoltage Fault क्यूँ होता है ? VFD Troubleshooting | 

BOL BULBUL Industrial Electrical
Подписаться 21 тыс.
Просмотров 18 тыс.
50% 1

VFD DC Overvoltage में Trip हो रहा है ? DC Overvoltage Fault क्यूँ होता है ? VFD Troubleshooting |
#vfd
#overvoltage
#dc
#electrical
#bolbulbulindustrialelectrical

Опубликовано:

 

7 янв 2023

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 77   
@Technicalcobra
@Technicalcobra Год назад
03:00 formula konse standard se liya h?
@devkrishvlogs
@devkrishvlogs 8 месяцев назад
Thanks ji
@BOLBULBULIndustrialElectrical
@BOLBULBULIndustrialElectrical 8 месяцев назад
Welcome
@Gulshan99176
@Gulshan99176 Год назад
Good job sir..
@BOLBULBULIndustrialElectrical
Thank you
@gunasekaransekaran8773
@gunasekaransekaran8773 Год назад
Great
@BOLBULBULIndustrialElectrical
Thank you
@patelchetanbhai4223
@patelchetanbhai4223 7 месяцев назад
ABB vfd acs560 driver me display me remot local nahi horaha he
@gunasekaransekaran8773
@gunasekaransekaran8773 Год назад
Very useful
@BOLBULBULIndustrialElectrical
Thank you
@user-sy9sn7tb4h
@user-sy9sn7tb4h 10 месяцев назад
How to use breaking resistor and how to breaking resistor size
@mustafashaikh8303
@mustafashaikh8303 4 месяца назад
Very good
@BOLBULBULIndustrialElectrical
@BOLBULBULIndustrialElectrical 4 месяца назад
Thank you
@prosanjitchakraborty2119
@prosanjitchakraborty2119 6 месяцев назад
@BOLBULBULIndustrialElectrical
@BOLBULBULIndustrialElectrical 6 месяцев назад
Thank you
@GangadharDas-eo7wh
@GangadharDas-eo7wh Год назад
Good👍💐
@BOLBULBULIndustrialElectrical
Thank you
@kamalosama4277
@kamalosama4277 10 месяцев назад
Thanks for your information,but sir I have danfoss vfd showing DC link under voltage, kindly explain to us how to solve this warning alarm.
@BOLBULBULIndustrialElectrical
@BOLBULBULIndustrialElectrical 10 месяцев назад
Video bana dunga.
@ramyagyamishra6261
@ramyagyamishra6261 8 месяцев назад
Sar Mera 45 kilo wat ka c 2000 plus vfd Har Bar ovn par trip Maarta hai Humne breaking register lagaya hai Fir Bhi solution bataiye na sar
@muhammadfarooq9482
@muhammadfarooq9482 10 месяцев назад
Sir vacon ka lift vfd drive ka out put on/off ho raha ha
@BOLBULBULIndustrialElectrical
@BOLBULBULIndustrialElectrical 10 месяцев назад
Start / stop command mil raha hoga. Control wire loose hoga. Check Karo.
@nlmehra3680
@nlmehra3680 Год назад
Sir, good evening . Your very nice explanation. I wish to ask why dc bus high voltage fault where as dc bus voltage is 580V and as soon as giving power tripping.
@BOLBULBULIndustrialElectrical
High DC bus voltage hoga to trip hoga.
@ArshadKhan-tf1pb
@ArshadKhan-tf1pb 11 месяцев назад
Hi sir hamare paas dalta El vfd ka ou error araha ha. Input 220v to 240 ha aur out put 3 phase 220v ha. Jasay he main run karta hun aik dam ou ka error Ata ha. Jab gear motor ke wires ko hatata hu phir fault nahi data. Please help me
@BOLBULBULIndustrialElectrical
@BOLBULBULIndustrialElectrical 11 месяцев назад
Motor decoupling karne se sahi chal Raha hai ? Ou fault means DC bus overvoltage. Agar load jyada hoga ya jamming condition hoga to ye fault ayega. Motor & gear box check kare.
@eprohoda
@eprohoda Год назад
nice - would you liek a promo?.👍
@vishalthakur7852
@vishalthakur7852 Год назад
Sir ACS 355 mai f0001 code aa rha hai overcurrent ka motor ka IR , WR sahi hai decouple karvake uski shaft ko ghuma kar dekh liya hai koi jamming nahi hai Phir bhi vo fault dikha rha hai aur rpm 11 se 12 tak hi jaa rha tha ( sidha drive ko replace kar du )
@BOLBULBULIndustrialElectrical
Speed reference increase kar ke dekho.
@vishalthakur7852
@vishalthakur7852 Год назад
@@BOLBULBULIndustrialElectrical Karke dekh liya hai sir
@SachinPatel-vx3yi
@SachinPatel-vx3yi Год назад
Check Par 11&20group
@RahulRai-zp5tq
@RahulRai-zp5tq Год назад
Schinder vfd 260kw ka kuch time run hone ke baad vfd display pr vfd over heet show kr rha hi eysa kyu plz explain sir
@BOLBULBULIndustrialElectrical
Cooling ka intejam kijie. VFD panel ko AC room mein install karna chahie. VFD panel me cooling fan hoga to uska filter clean kar dijie.
@suhailjamadar7267
@suhailjamadar7267 Год назад
Hello mam I have danfoss fc102 which is running smoothly. But i am getting an alarm repeatedly as( 2 warnings see alarm log) i checked and found its earth fault and short circuit. I checked the circuit and motor found everything in condition. Please help me to find the solution for this.
@BOLBULBULIndustrialElectrical
Does motor trip or alarm comes in running condition ? If motor trips , disconnect the motor and start the VFD. Measure the voltage . If it's trip then fault is in VFD.
@vishalthakur7852
@vishalthakur7852 Год назад
Sir apne hoist mai ACS 800 lga hua hai usme torque fault aa rha hai no load pe bhi Kya check karna chahiye sir
@BOLBULBULIndustrialElectrical
Torque ka setting check kar lo.
@BOLBULBULIndustrialElectrical
Brake agar release nahi hoga to torque me trip hoga. Brake check kar lo.
@vishalthakur7852
@vishalthakur7852 Год назад
@@BOLBULBULIndustrialElectrical ok sir kal check kar lunga Decouple mai bhi agr yahi fault aa jaaye to kya check karna hai sir
@harshpradhan102
@harshpradhan102 4 месяца назад
DC link over voltage bhi yahi hota hai kya sir??
@BOLBULBULIndustrialElectrical
@BOLBULBULIndustrialElectrical 4 месяца назад
Yes
@SunilVerma-nk6gw
@SunilVerma-nk6gw Год назад
Abb fault f0021 kya hai
@BOLBULBULIndustrialElectrical
VFD ka type bolo ?
@sugrivkumar1552
@sugrivkumar1552 Год назад
Vfd dc under voltege problem kayse salve kre
@BOLBULBULIndustrialElectrical
AC input voltage low hone se dc under voltage hoga. Input voltage measure karo.
@rohitdewangan7129
@rohitdewangan7129 Год назад
Sir DC drive releted video banaiye
@BOLBULBULIndustrialElectrical
Thik hai
@shahzadgull1782
@shahzadgull1782 Год назад
Rukesh gee good morning Abb vfd main DC voltage missing fault code 5681 ka kiya solution hay Thank you
@BOLBULBULIndustrialElectrical
VFD type ? ACS 809 ya ACS 550
@shahzadgull1782
@shahzadgull1782 Год назад
ACS 480
@shahzadgull1782
@shahzadgull1782 Год назад
App ka shukariya app nay reply kiya 🙏
@BOLBULBULIndustrialElectrical
Drive ka parameter check karo. Group 95 & 99 me.
@shahzadgull1782
@shahzadgull1782 Год назад
@@BOLBULBULIndustrialElectrical app ka shukariya ❤️❤️❤️🌹🌹🌹🌹
@Myamazingdiary
@Myamazingdiary Год назад
Reset kaise karte hai vfd ko ABB vfd drive me ye bataiye?
@BOLBULBULIndustrialElectrical
Reset button press karke.
@Myamazingdiary
@Myamazingdiary Год назад
@@BOLBULBULIndustrialElectrical sir hamare site me Ahu's Moter ke liye 15kw ka abb vfd drive laga huwa hai use trip alarm show ho raha aur vfd only hand mode me run ho raha please sir problem kya ho sakta hai bataye please
@yedeshdhiwar3979
@yedeshdhiwar3979 8 месяцев назад
Sir please app no. Dijiye n
@BOLBULBULIndustrialElectrical
@BOLBULBULIndustrialElectrical 8 месяцев назад
8249341942
@milappatel2872
@milappatel2872 Год назад
Is me hv ir test ka video muko na
@BOLBULBULIndustrialElectrical
2/3 din pahle ka video dekh le.
@milappatel2872
@milappatel2872 Год назад
@@BOLBULBULIndustrialElectrical infinitive current kya hota hai?
@BOLBULBULIndustrialElectrical
Jisse number me prakas nahi kar sakte usse infinite se represent kia jata hai.
@milappatel2872
@milappatel2872 Год назад
Vfd mai ac to dc dc to ac kyo kiya jata hai ? Direct ac kyo nahi diya jata ?
@BOLBULBULIndustrialElectrical
VFD is variable frequency drive. VFD incoming supply is in 50 HZ . But output supply is in variable frequency. To obtain that variable frequency incoming AC supply is concerted to DC. Then by modulating that DC we get different frequency voltage .
@pardeepswami8223
@pardeepswami8223 10 месяцев назад
Sir apka contact number kya hai
@BOLBULBULIndustrialElectrical
@BOLBULBULIndustrialElectrical 10 месяцев назад
8249341942
Далее
Troubleshooting a VFD overvoltage fault
21:32
Просмотров 3,3 тыс.
ТРУБОЧКА СКВОЗЬ НОС 😳
00:40
Просмотров 252 тыс.
Why inductor choke used in Variable frequency Drive?
8:11
Low DC BUS VOLTAGE FAULT /York Chiller VSD.
3:55
Просмотров 1,8 тыс.
ABB ACS580 VFD - IMPORTANT PARAMETERS & SETTINGS
21:47
VFD Control Methods | Scalar Mode | Vector Mode
13:35