Wiring the A/C disconnect 

grayfurnaceman
Подписаться 158 тыс.
Просмотров 51 тыс.
50% 1

This one covers how to wire the 240 volt, 30 amp disconnect commonly used with split system A/C units. This video is part of the heating and cooling series of training videos made to accompany my websites: www.graycoolingman.com and www.grayfurnaceman.com to pass on what I have learned in many years of service and repair. If you have suggestions or comments they are welcome.
If you are a homeowner looking to repair your own appliance, understand that the voltages can be lethal, the fuels are highly flammable and high pressures are used. Know your limits.

Хобби

Опубликовано:

 

24 янв 2021

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 48   
@blakejohnson3767
@blakejohnson3767 3 года назад
Line in. Load out. Simple and to the point. Thanks GFM!!
@grayfurnaceman
@grayfurnaceman 3 года назад
Welcome GFM
@BartSimpson-nr1dy
@BartSimpson-nr1dy 2 года назад
Great and very specific information. As always, well made video
@realmiketroyer1700
@realmiketroyer1700 Год назад
I have learned when I see it done in a GFM video, I have seen the best way to do it.
@woodrowellenburg4381
@woodrowellenburg4381 11 месяцев назад
Thank you so much, I really enjoyed the straightforward information.
@stuff5109
@stuff5109 3 года назад
Also would point out that line goes to the inside terminals so that when the disconnect is pulled the fuses don't have power. Then you can change the fuses without worry.
@MusicEducationwiththeMan
@MusicEducationwiththeMan Год назад
Thanks Gray Furnace Man!
@hansg562
@hansg562 14 дней назад
Thank you again!
@analogmoz
@analogmoz 3 года назад
Never not the time to refresh on the basics!
@DaLeSy.
@DaLeSy. 3 месяца назад
How do you test the fuses? Should your voltmeter be set to ohms? Does it say on the fuse what the ohm reading should be?
@rafaelhernandez8376
@rafaelhernandez8376 2 года назад
Excellent explanation. If there is a white neutral wire coming from the breaker box to the disconnect, where is this connected?
@grayfurnaceman
@grayfurnaceman 2 года назад
In this disconnect, there is no option for neutral. If there were a provision for a neutral, it would not be switched in the disconnect. GFM
@Rufio6814
@Rufio6814 2 года назад
@@grayfurnaceman do you just clip the neutral short then? My Romex comes with 3 wires and a ground.
@grayfurnaceman
@grayfurnaceman 2 года назад
@@Rufio6814 Yes. GFM
@jordankiskaden6139
@jordankiskaden6139 2 года назад
With those 2 small individual fuses on a 30amp Central Air Unit. Would you use 2 - 15 amp fuses or 30amp?
@grayfurnaceman
@grayfurnaceman 2 года назад
30 amp GFM
@Abortiz12
@Abortiz12 Год назад
I won’t be using it to supply my a/c but instead an outlet for my above ground pool. Should I still get a 30 amp fuse?
@jkbrown5496
@jkbrown5496 3 года назад
Current code requires connections be torqued down to mfr spec using the proper torque wrench or screwdriver, etc. (approved means). Guess too many people had the wrong idea about tight. 2020 NEC 110.14(D)
@grayfurnaceman
@grayfurnaceman 3 года назад
In the real world, nobody uses a torque wrench. You know that. Tight means tight. GFM
@jkbrown5496
@jkbrown5496 3 года назад
@@grayfurnaceman Oh, I understand that. I was just pointing out the language has changed to "shall". Another reason you don't want to get caught out with a loose connection.
@johnnygallardo76
@johnnygallardo76 Год назад
So if you're connecting female power cord with alligator clips to get power for say the vacuum it doesn't matter which terminals you stick the alligator clips on?
@grayfurnaceman
@grayfurnaceman Год назад
It will work both ways, but it is best to use correct polarity. GFM
@lengthao9159
@lengthao9159 18 дней назад
Quick question if the plug for the disconnect is burnt on one of the 4 tips does that mean one of the wire is loose or bad terminal ? Do I need to change out the whole disconnect box??
@grayfurnaceman
@grayfurnaceman 18 дней назад
It is probably a loose wire. In any case, the whole disconnect must be replaced. GFM
@Bairov
@Bairov 2 года назад
Will I be able to send more power back to Edison's grid if I choose a 60amp over a 30amp disconnect?
@grayfurnaceman
@grayfurnaceman 2 года назад
You don't understand, you pay Edison for power. And whether you use a 60 or 30 amp disconnect makes no difference. GFM
@Bairov
@Bairov 2 года назад
@@grayfurnacemanSorry I have solar panels and whatever I dont use goes back to the grid
@grayfurnaceman
@grayfurnaceman 2 года назад
@@Bairov If the wiring is also upgraded, yes GFM
@Standon139619
@Standon139619 Год назад
Does need a neutral connected from MSP or just a ground?
@grayfurnaceman
@grayfurnaceman Год назад
If the disconnect is for 240 volts only, no neutral is needed. GFM
@Gonzalezjimmy265
@Gonzalezjimmy265 3 года назад
Probably stupid question but why is it that a neutral is not needed?
@grayfurnaceman
@grayfurnaceman 3 года назад
The disconnect is a 240/208 disconnect. There are no 120 volt loads connected to it. If you had a 120 volt circuit on the appliance, you would need a neutral. GFM
@flyingwyoming5184
@flyingwyoming5184 2 года назад
How would I wire 110 volts to this?
@grayfurnaceman
@grayfurnaceman 2 года назад
That is a 240 volt disconnect. It cannot be used for 120 volts. A 120 volt disconnect will have only one pole disconnected. GFM
@OU8Aspark
@OU8Aspark 2 года назад
Do you know why they are fused?
@grayfurnaceman
@grayfurnaceman 2 года назад
The NEC requires it lol It used to be only a requirement that you have a disconnect. Not that it had to be fused. I personally think its not necessary. There is a fused disconnect (breaker) in the panel. GFM
@Skystorm405
@Skystorm405 Месяц назад
Lets say I installed the black/white wires coming from the house to the L R posts instead of the LINE posts? (because of some other idiot on RU-vid that I listened to.) When I turn the breaker on, turn the A/C on at the thermostat, then I hear a poof and the next thing I know my brand new fuses are now toast.. I'm guessing that being wired up wrong is what caused my fuses to blow and not something else ..
@peterlakers1
@peterlakers1 Год назад
What causes disconnect to blow fuses??????❓
@wadepatton2433
@wadepatton2433 Год назад
current in excess of the fuse capacity (which should match the circuit cap) lightning might provide that. you can get boxes without fuses.
@MusicEducationwiththeMan
@MusicEducationwiththeMan Год назад
Our disconnect doesn't have fuses.
@1down5up_enduro
@1down5up_enduro 14 дней назад
Why do fuses go out?
@grayfurnaceman
@grayfurnaceman 13 дней назад
Generally, there are 2 reasons for fuses to blow: Excessive amp draw of the circuit, such as a short in the compressor windings. What seems to be more common, the terminals overheat due to poor connections ie loose connections or a poor connection in the disconnect itself. GFM
@mikepelletier1399
@mikepelletier1399 3 года назад
I might add... those are aluminum lugs, probably should put a dab of noalox on that, especially if its outside.
@grayfurnaceman
@grayfurnaceman 3 года назад
This disconnect is CU only. Although, noalox would not hurt. GFM
@Spector_NS5_RD
@Spector_NS5_RD 3 года назад
Thanks for the video. But I hate when an electrician installs a fused disconnect after a properly rated breaker for the equipment im installing. Why? Cause i never have the fuses! And sure as hell he doesn't install them because most disconnects are sold without fuses! I'd rather do everything myself, including the line voltage wiring from panel to a non-fused disconnect.
@grayfurnaceman
@grayfurnaceman 3 года назад
The use of fused disconnects depends on the codes you are under. A disconnect using a breaker is allowed but most contractors will not use them as they are more expensive. GFM
@Dalot7777
@Dalot7777 Год назад
Wow I'm over here waiting for u to install the wire and nothing.. I hate videos like this that waist my time..
@lakersfanalbq
@lakersfanalbq Год назад
exactly . another pretentious old timer who fails to educate FULLY . Then way later he finally explains the dumb use of a fused disconnect is due to being a cheap old timer
Далее
How To Install An AC disconnect - ALL WIRING!
14:53
Просмотров 85 тыс.
The air conditioner service disconnect
8:21
Просмотров 367 тыс.
Старый Дим Димыч вернулся😱
00:16
How To Hook Up a 240-Volt AC Disconnect Switch
13:14
Просмотров 25 тыс.
How to install an A. C. Disconnect
8:21
Просмотров 303 тыс.
How to Extend Short Wires | Easy Fix Anyone Can Do
6:52
Install 30 amp ac disconnect (run conduit and wires)
5:21
Change An HVAC Service Disconnect
11:06
Просмотров 17 тыс.
The Deadly Chicago 3-Way (Only 2 Wires)
8:02
Просмотров 439 тыс.
Заварушка на пляже!
1:00
Просмотров 2,3 млн
Гигантский лук из семян!
0:43
ВЫХЛОП НА ЯПОНЦА TWIN LOOP #shorts
0:52