Zone Valves, Circulators, Relays & Controls 

Taco Comfort Solutions
Подписаться 10 тыс.
Просмотров 28 тыс.
50% 1

Presented by John Barba
Integrated controls are commonplace in hydronics, but are you making the most of them? In this program, you’ll learn about ZVC and SR control panels, how they work, what they do, and some of the hidden secrets that can make your job easier and add functionality to your systems.

Опубликовано:

 

4 окт 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 34   
@SalemHeatingandCooling
@SalemHeatingandCooling 4 года назад
👍👍👍👍John is the BEST.... Went to his class at WIRSBO a loooooooong time ago.
@sbitschy
@sbitschy 3 года назад
I buy as much taco as I can because the training is very good and very accessible. Thanks Taco for putting the money into your training
@TacoHVACtv
@TacoHVACtv 2 года назад
Thank you for your business!
@halfpoundbobby
@halfpoundbobby 2 года назад
Excellent video. Great information. Also very poignant (in retrospect) about the prediction regarding the quarantines ending back then.
@TacoHVACtv
@TacoHVACtv 2 года назад
We appreciate your feedback! Thank you, HalfPoundBobby!
@ramandeepgill6769
@ramandeepgill6769 3 года назад
wonderful video. so help full
@ronstephan7773
@ronstephan7773 3 года назад
Very useful. Thanks so much
@Takuplumbing
@Takuplumbing 3 года назад
how do you wire a relay with an aquastat, most aquastats i've come across are already wired as a relay.
@johnnyadams3244
@johnnyadams3244 2 года назад
I had an Erie Controls relay, which I thought had failed as radiant floor heating circulator would not energize. I replaced the Erie with a Taco 501. Still not circulator so I had to temporarily connect it to the NC. After many hours of troubleshooting, I found a broken end switch wire at a bundle of wires connected to the radiant floor heating actuators.
@TacoHVACtv
@TacoHVACtv 2 года назад
Glad you found the issue! Good work!
@johngallati8164
@johngallati8164 2 года назад
GREAT VIDEO
@TacoHVACtv
@TacoHVACtv 2 года назад
🙂
@watchfast1
@watchfast1 2 года назад
2:00 How to ask a question during the live presentation 3:30 single pump relay SR 501-4 12:57 questions about single pump relay 14:44 multi pump relay SR 504.4 22:12 EXP expandable relays 24:35 plugs, switches and controls 33:18 zone valves 1:09:59 still taking questions
@WeightLossChristian
@WeightLossChristian 2 года назад
Wait... is the valve normally closed and opens to send hot water when energized, or are the electrical contacts normally closed and open when energized, thus closing the valve. I though NC meant the valve actuator was closed. This makes it sound like the electrical connection is normally closed. ???
@TacoHVACtv
@TacoHVACtv 2 года назад
Good Day Bob, Thanks for watching the Taco Tuesday webinar series. We make all styles of zone valves in many different configurations. There are some that are normally closed (NC) and then some that are normally open (NO). In most instances, we use NC valves which means while the valve is sitting there, without power, is closed until there is a call for heat, the motor gets power and open the valve. The Zone Sentry zone valve uses that power a little differently. When the call for heat occurs, power is applied to the motor, the capacitor gets charged and when it fully charges, the power is discharged and the valve opens. While the valve is open, the capacitor now recharges and when the call for heat goes away, power is removed from the motor, the capacitor discharges again therefore closing the valve. I hope this answer your question and if not, please do not hesitate to contact us or your local Taco representative.
@fosterhensleycm8378
@fosterhensleycm8378 2 года назад
Lowering to 69 opens the thermostat, need to turn higher than room temperature to close unless relay being used for cooling
@davidmerkrebs9967
@davidmerkrebs9967 3 года назад
explain zc zr for tankless coil
@gyver471
@gyver471 3 года назад
Yes we need an explanation of that how the tankless get priority.
@TacoHVACtv
@TacoHVACtv 2 года назад
Hello David, The ZC ZR terminals on a Switching relay are used in a boiler that has a tankless coil. In other words, the boiler is maintaining a temperature and not a cold start for domestic hot water for the home to be available. When there are multiple heating zones in the house and those zone circulators are controlled with a SR panel, you then remove the factory installed jumper between ZR and ZR and connect it to aquastat that is controlling the water temperature. The result is when the aquastat calls for heat, it would temporarily shut off the power to the zone circulators to ensure all of the heat the boiler is making is used for the domestic hot water.
@RodriguezElectrical
@RodriguezElectrical 3 года назад
The lord of the trainors!!💪🏽
@tedcolarusso4406
@tedcolarusso4406 2 года назад
How do the system and dhw circulators work if you DO NOT want dhw set as a priority zone? With zone valves..
@TacoHVACtv
@TacoHVACtv 2 года назад
Ted, If you had a DHW circulator and a heating circulator that supplied zone valves for heating the house, you would need a ZVC controller that would control the zone valves only and then you need to us a Switching Relay (SR) for the 2 circulators.
@ronstephan7773
@ronstephan7773 3 года назад
If I have one zone with one thermostat but three circulator pumps which of these zone relays should be used?
@robblacie2377
@robblacie2377 3 года назад
One thermostat and 3 circulators?
@carlcutlip659
@carlcutlip659 2 года назад
i have a sr503-4 how to run my oil forced air furnace, and the pump on hotwater stove
@TacoHVACtv
@TacoHVACtv 2 года назад
Hi Carl, The SR-503 is designed as an interface between your low voltage thermostats and your high voltage circulators. There are many applications for the switching relays and you can view the different wiring diagrams here and find the one that matches your application. www.tacocomfort.com/documents/FileLibrary/100-92.pdf
@dspreeuw
@dspreeuw 2 года назад
Question: I installed a Rheem combi boiler that needs the "heat demand" 2 wires to be between 0-10 DC Volts.....which Taco controller can I use?
@TacoHVACtv
@TacoHVACtv 2 года назад
dspreeuw, thanks so much for watching the Taco Tuesday webinar series. Before I answer that question, can you tell me what model boiler you are using so that I may review the product and recommend the correct controller? Thanks
@vinceb7918
@vinceb7918 2 года назад
@@TacoHVACtv I missed the live webinar, but viewing now via RU-vid. I am presently considering installaton of a Lochinvar NKC Combi, which uses 0- to 10- volt signal. Residence is presently one zone; slight possibility of one additional zone added later. Which Taco controller can be used? And, how would it integrate with the internal Lochinvar NKC pump? I have benefitted from viewing webinars a great deal. Thank you John, Dave, and Rick.
@fernandoalvarez3891
@fernandoalvarez3891 2 года назад
I need help with my system it says I have a valve open an im not getting heat to my upstairs
@TacoHVACtv
@TacoHVACtv 2 года назад
Fernando, the Zone Valve Controller (ZVC)has two indicator lights on it per zone. The one on the left is amber in color and when lit, indicates that the thermostat has a call for heat. The light on the right is red and indicates that the zone valve has opened and the endswitch on the zone valve has closed. If you have just the amber light and not the red, this will indicate that the motor of the zone valve may not be operating properly. If you have just the red light and not the amber light, the endswitch in the zone valve may have a problem. I hope this helps you find your issue.
@carlcutlip659
@carlcutlip659 2 года назад
Hello
@sporty-scum
@sporty-scum 3 года назад
I have a zone constantly calling for heat. Thermostat is off the wall so theres no issue there. I removed the wires from that zone on the switch relay and once I turn the boiler back on, it calls for heat and the only hot pipe is zone 2, providing heat to the second floor. I do not need heat at this point in the year. Is it safe to just turn the water valve to that zone off? Thank you for anyone's help.
@TacoHVACtv
@TacoHVACtv 2 года назад
It sounds like you may have an endswitch inside the zone valve is stuck or broken. Yes you can turn off the flow of heat to that area but there may still be a call to the boiler until it is corrected. What zone valve are you using?
Далее
Deep Dive  Switching Relays and Zone Valve Controllers
1:01:50
HA-HA-HA-HA 👫 #countryhumans
00:15
Просмотров 3,5 млн
Zone Valves vs.  Zone Circulators
1:00:47
Просмотров 2,3 тыс.
Zone Valves
14:11
Просмотров 15 тыс.
How 3 Phase Power works: why 3 phases?
14:41
Просмотров 1,2 млн
Navien NFC-200 6 Zone Installation Overview
7:23
Просмотров 15 тыс.
TACA - Intro to VAV Calibration
4:49
Просмотров 1 тыс.
CAN Bus Properties and Troubleshooting
18:09
Просмотров 1,4 млн
Hydronics System Components
12:31
Просмотров 376 тыс.