Adding a Powerflex 525 to RSlogix 5000 over ethernet 

PLC Automation Training
Подписаться 17 тыс.
Просмотров 153 тыс.
50% 1

Setting up the AOP for the powerfex 525 in RSlogix 5000 using V20
Any feed back would be nice thank you for watching.

Опубликовано:

 

5 авг 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 132   
@Ranjit399
@Ranjit399 8 лет назад
Informative. Concise. Nicely done.
@gameslayer64
@gameslayer64 7 лет назад
Thanks for the video it came in very handy with trying to add a VFD to my PLC I didn't have high hopes when starting to look for information on how to do it so I am glad you posted this video.
@AngelGonzalez-to2ob
@AngelGonzalez-to2ob 5 лет назад
Great video. I learned in this video what i had not learned in hours of reading. Thank you!
@doming266
@doming266 9 лет назад
I work for a municipality that of course locks its employees out of RU-vid. I spent about three hours today trying to figure out how to add a PF525 to my RSLogix 5K project. Started out I could not see the PF525 in add devices so I spent a great deal of time on RA knowledge base to find the answer. To make a long story short I finally got it configured and moving along. Along my path to enlightenment I had ran across this video, once again can not view it at work. Upon getting home with my tail wagging with excitement looking forward to see what this video entails. I pour myself a cold drink and fire up my pc and watch the video. WOW!!! If I could have seen this video at work the hours it would have saved me. I would like to thank you for putting this awesome video up I have subscribed to your channel and will definitely share with my network. Looking forward to your future post. Thanks again.
@PLCAutomationTraining
@PLCAutomationTraining 9 лет назад
Frank Dominguez Thank you for the feedback it means a lot and keeps me motivated to continue adding more videos to help those who need it. RU-vid is a great place, i don't understand why some companies block it. I make a lot of these as a refresher for myself as well.
@guilhermecarneiro2116
@guilhermecarneiro2116 Год назад
Great video 👏👏👏
@richardarendt7175
@richardarendt7175 3 года назад
Thank you very much. I had figured out a lot of it but there were a few things that I never would have guessed. Good Tutorial... got me up and running!
@PLCAutomationTraining
@PLCAutomationTraining 3 года назад
You're welcome, I am glad this video was helpful for you!
@ziyaddinyusupov4433
@ziyaddinyusupov4433 7 месяцев назад
Very informational. Thank you
@BrianCB28
@BrianCB28 11 месяцев назад
Excellent tutorial! Thank you.
@disun4152
@disun4152 4 года назад
Amazing tutorial video. I was much impressed by the clear English voice and good knowledge. I have subscribed the author videos already. The first time I have ever subscribed a you tube author. I will be watching more on this Author's other videos. I am interested in Siemens stuff as well
@nashwanalshargabi9860
@nashwanalshargabi9860 5 лет назад
Excellent job. Thanks
@Saurabh_Gambhir
@Saurabh_Gambhir 3 года назад
Your videos are so informative. Please make regular videos on rs logix 5000 .you are awesome.
@kacemabdallah1368
@kacemabdallah1368 5 лет назад
thank you so much,it's very helpful.
@irfaaankhaaan
@irfaaankhaaan 5 лет назад
Excellent. !!!! What a life saviour video !!! Thanks mate
@hectormb88
@hectormb88 4 года назад
Great video. Easy to understand.
@jasonwilson9117
@jasonwilson9117 8 лет назад
Thanks. Great video.
@MamadAbedi
@MamadAbedi 9 лет назад
Thank you man, look forward to see more videos from you. :)
@PLCAutomationTraining
@PLCAutomationTraining 9 лет назад
Thank you for watching
@badenkey
@badenkey 8 лет назад
Great Tutorial, Thanks a lot
@ivanritchie5119
@ivanritchie5119 9 лет назад
thanks for the video man, very helpfull
@ceilingwalker1
@ceilingwalker1 5 лет назад
Very nice. Thank you.
@lpfagundeseai
@lpfagundeseai 9 лет назад
Very nice video!!! I'll show this video to my students and i hope they enjoy it as mush as i do. Thank for share your knowledge!
@PLCAutomationTraining
@PLCAutomationTraining 9 лет назад
No problem let me know if I can help in other tutorials!
@petedazer2556
@petedazer2556 6 лет назад
Well done!
@rahulrpatil3005
@rahulrpatil3005 5 лет назад
Thanks a lot man , really helpfull .
@FacesintheStone
@FacesintheStone 9 лет назад
Thanks a bunch man!
@openbooktips
@openbooktips 3 года назад
Best video i've seen on this topic. Thank you. New subscriber.
@soemin4847
@soemin4847 4 года назад
Thank you very helpful
@malcolmandthebends2914
@malcolmandthebends2914 2 года назад
Thank you Sir
@sagi110788
@sagi110788 9 лет назад
very useful video .....thanks sir
@PLCAutomationTraining
@PLCAutomationTraining 9 лет назад
Thank you and your welcome
@cuongngovan81
@cuongngovan81 7 лет назад
Good Video,
@Padredimitry
@Padredimitry 6 лет назад
Thank you!
@jonathansegura5702
@jonathansegura5702 9 лет назад
thanks, thanks, thanks sr., muchas gracias.
@viraguen
@viraguen 8 лет назад
Thanks for the video. Can I use RSLogix 5000 Mini or Lite to configure VFD like this?
@SafeAndEffectiveTheySaid
@SafeAndEffectiveTheySaid 7 лет назад
nice job!
@PLCAutomationTraining
@PLCAutomationTraining 7 лет назад
Adriano Me thank you
@jpinckneyltr450
@jpinckneyltr450 5 лет назад
Great video. But what if you want to see running from the drive. I have been trying to find how to program ladder so you can see drive running? Thanks
@sebastianallende5288
@sebastianallende5288 4 года назад
Hi, do you have any experience doing the same thing but with CCW software? I am trying to control a 525 using a micro820 PLC, I have both devices in a program in CCW (I can control the PW525 from CCW) but I can not find out how to pull the Powerflex variables into the global variables list.
@mantrazone
@mantrazone 8 лет назад
Gracias super el video
@ricardordzbenavente6383
@ricardordzbenavente6383 7 лет назад
Great!!!
@edsoncavazos4689
@edsoncavazos4689 6 лет назад
thx bro!
@Jackgitz23
@Jackgitz23 7 лет назад
Thank you for this awesome video. Quite clear and to the point. Question: How different is the PowerFlex 753 setup from the 525 as you show here? Do you have any vidoes for that? Thanks!
@PLCAutomationTraining
@PLCAutomationTraining 7 лет назад
Jackgitz23 the 755 is different. though has many similarities. the hardest part with the 755 was getting the IP address setup.
@osamafattah127
@osamafattah127 5 лет назад
Thank you
@wtar8469
@wtar8469 2 года назад
Help, please. How can upload the parameters from one powerflex 500 was faulted to a new powerflex 500. Because is to many parameters on the application, i would like to know if is it possible to download the parameters directly from the plc to VFD. Thanks
@veoteveo1
@veoteveo1 6 лет назад
could you do a vid using tags in the AB controller to program logic in intouch.
@pato1982000
@pato1982000 Месяц назад
Can you explain with multi drive on the same program.. how can I control two oh more drives .. because pf525 is always looking for port 0
@AhmedAboudGP
@AhmedAboudGP 8 лет назад
Thanks
@guangyaoli6218
@guangyaoli6218 7 месяцев назад
Boss I would like to ask. You have two internet cards with different ip address. So which ip address is your computer setting match to? Thank you very much
@controld333
@controld333 9 лет назад
Very informative, good clear exemplified presentation. I like the simplicity of the complex intelligence of this drive. By the way I have a question, what is the Ethernet switch you recommend when connecting several drives? to aim reliability but keeping in mind my stinging budget.
@PLCAutomationTraining
@PLCAutomationTraining 9 лет назад
hirschman switches are the best in my opinion.
@controld333
@controld333 9 лет назад
PLC Automation Training Thanks alot for the recommendation, I will look into it.
@nirajbegani4115
@nirajbegani4115 5 лет назад
Is there same settings for poweflex 753
@necofme
@necofme 4 года назад
video is ok, very easy .! but need to add that for the Speed control, need it a jump in the control pin 11 to 1. to model 525 over 5hp
@RobManVids
@RobManVids 5 лет назад
Thank you for your very informative videos. I'm a little confused as to why you were going to show us the old school way of adding a drive to the tree and then you did a match drive. Matching the drive isn't really old school is it? There is a lot more that can be added manually right?
@PLCAutomationTraining
@PLCAutomationTraining 2 года назад
Yes I'm not sure what I was thinking back then sorry
@robertonogueira9874
@robertonogueira9874 5 лет назад
1- Which version of 5000 we may use the Discover Modules resource? 2- Are you sure that AOP (add on profile) is useful for Rslinx?? (Thanks for share your knownledge. Regards from Brazil)
@danielellerington870
@danielellerington870 8 лет назад
hi, awesome video! would this be the same for the powerflex 40 with comm e adaptor?
@PLCAutomationTraining
@PLCAutomationTraining 8 лет назад
yes except the speed ref is a different value i believe or the 70 i dont remember
@danielellerington870
@danielellerington870 8 лет назад
Wow, fast response! I've been reading RA literature and the generated tags are different to the 525. I am building a new control panel with 4 powerflex 40 and would rather use ethernet instead of hard wiring them all. I also read about multidrop with 1 comm e card and I assume modbus daisy chain to the rest, but programming seems more indepth. What would you advise? I'm dan Btw from uk
@viniciusspaceandlife7388
@viniciusspaceandlife7388 4 года назад
Thanks for the tutorial! Could you please explain why did you created a automation network with a network module and other private one with the other card? Is it mandatory to use drivers on private networks or it was just made for your network topology and project only?
@PLCAutomationTraining
@PLCAutomationTraining 4 года назад
This was just what I usually do for facility installs, this helps keep network congestion down and helps organize networks, there is no real good reason why I do it this way but this is just an example why.
@viniciusspaceandlife7388
@viniciusspaceandlife7388 4 года назад
@@PLCAutomationTraining Thanks a lot for replying me!
@vorapobautomation9760
@vorapobautomation9760 4 года назад
How to setting analog input 0-10 vdc signal fastest response ?
@MrFK2
@MrFK2 7 лет назад
Can I follow the same procedure if I'm using a Powerflex 40 instead?
@PLCAutomationTraining
@PLCAutomationTraining 7 лет назад
MrFK2 I haven't tried a powerflex 40 in this situation
@husainsaifuddin2101
@husainsaifuddin2101 7 лет назад
do you do training?
@mattgallagher7105
@mattgallagher7105 7 лет назад
Thanks for the video. Why is Pump_1:0 Start used instead of the input? Is it because the VFD will start outputting power to the pump motor?
@PLCAutomationTraining
@PLCAutomationTraining 7 лет назад
Matt Gallagher please rephrase your question im a little confused
@mattgallagher7105
@mattgallagher7105 7 лет назад
Sorry - I meant in the ladder logic portion, you used a PB start to activate "Pump_1:0 Start". I was wondering the difference between this tag and "Pump_1:I". At about 11:05 you said "we don't want the input, we want the output".
@PLCAutomationTraining
@PLCAutomationTraining 7 лет назад
Matt Gallagher because the inputs are what you are reading from the drive and the outputs are what you are writing to the drve, sorry for the late response.
@holdenjames808
@holdenjames808 7 лет назад
Great video. I am having issues with the ramp function though. I have 420 seconds in the drive but it jumps to 60 hz immediately. Also, when I try to adjust speed reference from 60 to anything else it stays at 60. Do these need to be on "velocity" mode? Or is "position" mode okay?
@PLCAutomationTraining
@PLCAutomationTraining 7 лет назад
Jordan Vande Brake velocity mode. then check the speed reference parameter in the drive to make sure its setup over ethernet ip
@PLCAutomationTraining
@PLCAutomationTraining 7 лет назад
Jordan Vande Brake also make sure min freq hz is at 0 and max is 60 unless you need more
@holdenjames808
@holdenjames808 7 лет назад
thank you very much for the prompt replies. My min and max is 0-60 HZ. It does seem to respond now to my 'freq command' logic. And, seems to accept my accel rate. However, it automatically instantly jumps to 60 HZ and THEN comes back down to the commanded frequency, at the accel rate, entered. I obviously want to send it the start command and have it accel to 60 HZ over 4-7 minutes(starting centrifuge motor).
@holdenjames808
@holdenjames808 7 лет назад
I must have had some other parameters fighting with each other. Reset to factory default and started from scratch adding only what I thought I would need. Seems to be working fine. this was a great video. Huge help. Thank you.
@PLCAutomationTraining
@PLCAutomationTraining 7 лет назад
Jordan Vande Brake seperators they use to use powerflex 700, is this a pump to the seperator
@darthenx2585
@darthenx2585 8 лет назад
Great video! Do you have a video or can you show how to read the output current from the drive. For example what logic instruction do you need to use to read it.
@PLCAutomationTraining
@PLCAutomationTraining 8 лет назад
in the configuration screen where the match drive is in the upper right corner you can add the current. I'll add it to a quick video for you
@PLCAutomationTraining
@PLCAutomationTraining 8 лет назад
Here is your link ru-vid.com/video/%D0%B2%D0%B8%D0%B4%D0%B5%D0%BE-qCxT4ig-smc.html
@guangyaoli6218
@guangyaoli6218 7 месяцев назад
Boss. I would like to ass one question. You have two ethernet cards in plc. In this situation data cable from pc should plug in which card? And which ip address should be match in pc ip address setting? Thank you very much and look forward for you respond!
@PLCAutomationTraining
@PLCAutomationTraining 6 месяцев назад
We're you able to figure it out? Sorry was away on business and was not online
@johnrece6622
@johnrece6622 3 года назад
When you download online I thought the processor will switch to program mode?
@jinblade
@jinblade 3 года назад
Keep getting module not configured. Any suggestions
@Saurabh_Gambhir
@Saurabh_Gambhir 3 года назад
Please make video on adding AENTR module and LIO module and E3 MODULE used for small pumps in rs logix 5000
@guzmanjimmy3
@guzmanjimmy3 8 лет назад
Very cool video could you do some programing with an allenbradley compaqlogix using studio 5000, I would be very happy to see that. thanks
@PLCAutomationTraining
@PLCAutomationTraining 8 лет назад
yes I can though they are very simular
@guzmanjimmy3
@guzmanjimmy3 8 лет назад
I appreciated thank you
@jeyaprakash8560
@jeyaprakash8560 8 лет назад
use full video super
@iankerrigan7214
@iankerrigan7214 7 лет назад
great video, can you show me how to start stop powerflex 527 in rs5k using the motion commands
@PLCAutomationTraining
@PLCAutomationTraining 7 лет назад
Ian Kerrigan I'll do a motion course soon
@Pyrtas
@Pyrtas 6 лет назад
Now you have a "Race condition" between STOP and START signal over Ethernet. It's better wait to remove stop signal and then execute start cmd.
@petrbrezik1606
@petrbrezik1606 9 лет назад
Hello, please could you give here some description of input and output signals, or a reference to a document where these signals are described. Thanks sir
@PLCAutomationTraining
@PLCAutomationTraining 9 лет назад
Could you explain exactly what you want and I will send you the info you are requesting. Thanks for the view
@RaulHerrera-nw9qr
@RaulHerrera-nw9qr Год назад
what if one is using an older version of rslogix 5000 and doesnt have module discovery ?
@PLCAutomationTraining
@PLCAutomationTraining 6 месяцев назад
You can manually add it
@YASHJARIWAL
@YASHJARIWAL 7 лет назад
Really Helpful tutorial. one Situation i am facing. The PF525 drive is already configured and running perfectly fine. now i wanted to monitor the drive parameter when it is currently running. to do that i got online with the PLC and got into the properties of the PF525 from the I/O configuration in RSLogix5000. and from there i clicked on Drive tab but then was getting Error as '"AUTOMATIC CONNECTION FAILED - MISSING DEVICE IN PORT 1 IN OFFLINE DRIVE". So is the Drive Configured incorrectly? and Is there any Solution to the Above Error
@PLCAutomationTraining
@PLCAutomationTraining 7 лет назад
YASH JARIWALA i will look this up i havent ran into this one can you send me a pdf of the drive parameters from ccw
@YASHJARIWAL
@YASHJARIWAL 7 лет назад
i dont have a saved CCW file. its been somehow deleted. i can send you the PDF of the Problem which i am facing so that you can have a better idea of it.
@YASHJARIWAL
@YASHJARIWAL 7 лет назад
Can you provide me a mail id to which I can send you the PDF ?
@manexemano7428
@manexemano7428 6 лет назад
Hi! I have installed five (5) pf525 in my system. I always experience this F073 faults, can you please help me resolve this. 3 of pf525 was programmed in ml1100 and the other two was in the ml1500 both in rslogix 500. hope you can help me.
@PLCAutomationTraining
@PLCAutomationTraining 6 лет назад
Manex Emano is it all of them?
@manexemano7428
@manexemano7428 6 лет назад
wow! thank you for the response! yes! all of them. I noticed that if I run ccw and get connected online of the 5 pf525, that annoying fault will be gone. but no one needs to get their lappy hook up in the network just to get rid of that fault, right? can you please help me because I know I missed lots of things here. I just recently changed my system, by the way. It was actually designed separately (the cip station [ml100] and the process station [ml1500] ) but since my boss gave me another requirements and tasks that the systems should be connected all in the ethernet for much easier (not actually) data and command exchange. I already made a rung that will make the command logic clear faults always on so that it will clear immediately the fault. --- will this help or i just made it worse?
@PLCAutomationTraining
@PLCAutomationTraining 6 лет назад
Manex Emano I would check your message times if you want to send me the rss I could look at it for you. Coldbluemountainapps@gmail.com
@goranhikl5723
@goranhikl5723 6 месяцев назад
Great video if you can download. what if you can't
@guangyaoli6218
@guangyaoli6218 7 месяцев назад
Boss if I have two internet card win plc with different ip address.which ip address I should match in my pc address setting? Thank you very much
@PLCAutomationTraining
@PLCAutomationTraining 7 месяцев назад
Doesn't matter if you bridge your connection
@miguelangelcastrosanchez3134
@miguelangelcastrosanchez3134 8 лет назад
hi, mi name is miguel, I electronic ingeenire, and your video is very nice, but i need the Softlogix 5800 v16, you know any page or link where i can download de software? please!
@herb9880
@herb9880 5 лет назад
Can you show more video about Kinetix servo drive ?
@PLCAutomationTraining
@PLCAutomationTraining 5 лет назад
Yes coming up
@viniciusperetti1724
@viniciusperetti1724 7 лет назад
hey man, how can i get the status of the ethernet connection ? Sorry by my English, I am from Brazil.
@PLCAutomationTraining
@PLCAutomationTraining 7 лет назад
Vinicius Peretti GSV instruction attribute entrystatus then compare the destination status using an MEQ for ethernet
@PLCAutomationTraining
@PLCAutomationTraining 7 лет назад
Vinicius Peretti mask equals
@scorepion533
@scorepion533 6 лет назад
Please any one can help me to control this vfd (start/stop and speed setpoint) in Automode using ethernet ip and manual mode using push buttons. I have switch manual-off-auto THANK YOU.
@PLCAutomationTraining
@PLCAutomationTraining 6 лет назад
Send me your program
@scorepion533
@scorepion533 6 лет назад
@@PLCAutomationTrainingyour email plz
@kezzibaba
@kezzibaba 8 лет назад
Hey can you please create a ADD ON INSTRUCTION TUTORIAL ? I WILL REALLY APPRECIATE IT.
@PLCAutomationTraining
@PLCAutomationTraining 8 лет назад
what type of add on would you like to see?
@kezzibaba
@kezzibaba 8 лет назад
+PLC Automation Training preferable i will like to see AIO that involves data transfer. Don't quite understand how to explain it but i will like to see you dosomething more advance using AIO if that makes sense. Thanks.
@PLCAutomationTraining
@PLCAutomationTraining 10 лет назад
@webmarvels6743
@webmarvels6743 Год назад
Helpful, but watching people write code is mind-numbing - I'd recommend prepare that and just talk to it briefly.
@PLCAutomationTraining
@PLCAutomationTraining 6 месяцев назад
I agree but sometimes that numbing removes extra questions plus sometimes people use short cuts and it's nice to learn myself
@Nicofish2023
@Nicofish2023 10 месяцев назад
How to contact you ?
@PLCAutomationTraining
@PLCAutomationTraining 6 месяцев назад
What do you need help with
@Nicofish2023
@Nicofish2023 6 месяцев назад
@@PLCAutomationTrainingi need training on VFD
@kayserkayser8685
@kayserkayser8685 4 года назад
Porfa traducelo al español
@PLCAutomationTraining
@PLCAutomationTraining 3 года назад
If i could speak fluent i would
@disun4152
@disun4152 4 года назад
Amazing tutorial video. I was much impressed by the clear English voice and good knowledge. I have subscribed the author videos already. The first time I have ever subscribed a you tube author. I will be watching more on this Author's other videos. I am interested in Siemens stuff as well
Далее
БАТЯ И СОСЕД😂#shorts
00:59
Просмотров 2,1 млн
Survive 100 Days In Nuclear Bunker, Win $500,000
32:21
PowerFlex 525 Basic Setup For ethernet
9:59
Просмотров 103 тыс.
Why The Windows Phone Failed
24:08
Просмотров 223 тыс.
Adding Ethernet Modules in Studio 5000
16:18
Просмотров 11 тыс.
БАТЯ И СОСЕД😂#shorts
00:59
Просмотров 2,1 млн