April Testing Fire Alarm Back up Generator and Emergency Lighting 

NIC’S - SYSTEMS & ELECTRIC
Подписаться 27 тыс.
Просмотров 12 тыс.
50% 1

Развлечения

Опубликовано:

 

5 апр 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 170   
@kc0eks
@kc0eks 2 месяца назад
Dude has backup lights and a monitored fire alarm system and strobe in the shed. Man we should all be this protected.
@TheJakeman789
@TheJakeman789 2 месяца назад
No kidding. But it is major overkill lol so much redundancy
@nics-systems-electric
@nics-systems-electric 2 месяца назад
The only redundancy is emergency lighting as it's not needed when the generator is there however it's still nice to still have light during the 20 seconds before the generator starts as it allows me to still move around and stop whatever I'm doing safely
@NewEnglandAviaton987
@NewEnglandAviaton987 2 месяца назад
@@nics-systems-electricI have a demo system in my room - one board , messy and two systems in my house one basement and one my bedroom and the one in my bedroom is the P2R/W L on code 3 no sync module but the P2R/Wls don’t need sync modules on 2 devices
@mbcommandnerd
@mbcommandnerd Месяц назад
I have to tell you, Nic. I’m one of the few people who actually find your generator videos to be SUPER interesting, so keep on making them!
@nics-systems-electric
@nics-systems-electric Месяц назад
Awesome, thank you!
@officer_potato9118
@officer_potato9118 2 месяца назад
Some people would say having commercial-grade safety systems installed in a residential structure is redundant and unnecessary. Way i see it as thats probably the most fire safe house in your county, and its your house, you do what you want with it. I would love to do something like this myself to my house honestly. Problem is i dont own one yet 😂. At the bare minimum if that equipment never really helps you in an incident [though I know at least the power backup and emergency lighting systems have], the experience and knowledge gained from doing all that work - very clean and professionally done by the way - is more valuable than all of the equipment monetary costs combined. Love to see it. Be back for the next one.
@nics-systems-electric
@nics-systems-electric 2 месяца назад
Thank you I appreciate the support! That's exactly how I see it myself.
@Theexitisrightthere
@Theexitisrightthere 2 месяца назад
Good video, I think that you should do the pull station by the panel in the house, and the shed heat detector for the garage.
@RossTheGenMan
@RossTheGenMan 2 месяца назад
Great video. Activate the garage with the pull station in the pool shed. Activate the house with pull station in the shed under the porch.
@firealarm421
@firealarm421 2 месяца назад
Awesome. On your May test. For the house system can you do the pull station in the shed
@noahv1
@noahv1 2 месяца назад
Love the vids, keep it up. Waiting for the next install! Love the install videos.
@nics-systems-electric
@nics-systems-electric 2 месяца назад
Thank you I'm glad you enjoyed
@Bruva-the-caff-fan
@Bruva-the-caff-fan 2 месяца назад
@@nics-systems-electricUPLOADD EVERYDAYYYY
@Bruva-the-caff-fan
@Bruva-the-caff-fan 2 месяца назад
@@nics-systems-electricI LOVE YOUR VIDSSS
@benhawkes2752
@benhawkes2752 2 месяца назад
Awesome job as always Nic
@gamerboy12970
@gamerboy12970 2 месяца назад
Great one nic
@rodgodx345
@rodgodx345 2 месяца назад
Oh wow nice sneak peek of the new addition ;-----)
@johnuhlig323
@johnuhlig323 2 месяца назад
Would like to see the security system tested on the garage I recently installed a DSC NEO on my house and would like to see testing to see how you do it. This could be a separate video. Thank You
@nics-systems-electric
@nics-systems-electric 2 месяца назад
I did a test not too long ago I may do one again at some point just not something I show much as I do not have much knowledge on it
@lutinoflake5115
@lutinoflake5115 2 месяца назад
You should do the duct detector in the house again!
@themexicanmerc
@themexicanmerc 2 месяца назад
who wants to see him collab with ser safety?
@hotbytesB
@hotbytesB 2 месяца назад
Bring the fog machine back
@cussmustard4748
@cussmustard4748 2 месяца назад
Regarding your comment about your generator videos: I actually discovered your channel through that content as opposed to your more popular FA videos. I’d love to see more.
@DanTDMJace
@DanTDMJace 2 месяца назад
Me who found him by the railroad crossing video: 💀
@JamesGlancy-es8go
@JamesGlancy-es8go 2 месяца назад
Dude that's awesome!
@nics-systems-electric
@nics-systems-electric 2 месяца назад
Thank you
@Thesystemsensor
@Thesystemsensor 2 месяца назад
Hello Nic, happy april
@mimi2
@mimi2 2 месяца назад
I think you should try testing heat detectors next month. Not the attic ones but the addressable ones
@michaelloving8004
@michaelloving8004 2 месяца назад
Hi Nic, is there a use case and/ or method of generator being monitored for it starts up like in a building when the power goes out and the generator like supervisory condition ? I enjoy your videos.
@nics-systems-electric
@nics-systems-electric 2 месяца назад
Yeah it's a requirement for generators supplying life safety power for a fully legal generator it needs to be supervised for running as well as low fuel and other trouble conditions in order for it to be considered a legal power source that will change your fire alarm battery calculations
@michaelloving8004
@michaelloving8004 2 месяца назад
@@nics-systems-electric thanks
@aerhardt
@aerhardt 2 месяца назад
Would it be possible to enable audible silence on just the chime strobe? Maybe it would be nice to know if the garage building is still in alarm without the noise after you silence it.
@nics-systems-electric
@nics-systems-electric 2 месяца назад
I don't believe it's an option on these Canadian panels I could be wrong though
@CJP_Productions
@CJP_Productions 2 месяца назад
@@nics-systems-electric wait but dont those panels be the same here in the US? or no?
@nics-systems-electric
@nics-systems-electric 2 месяца назад
@@CJP_Productions this is a 320C the C is for Canadian it is different than the US model
@joeycaridi3030
@joeycaridi3030 2 месяца назад
09:25 For a second I thought your Garage Building B fire alarm system went off again from a detector that randomly activated like from last time but it turns out it's from the System Sensor P2W horn strobe installed in some sort of storage room of your house where that exit sign is as it kinda creates confusion when you're outside and the fire alarm goes in in the garage or in the house as it's confusing of which system activated as to better avoid that confusion replace the P2W with an L-Series set on the 3K tone because it allows you to tell the difference of which System activated but in a minor part of your house when you're outside as the 3K tone isn't needed on the garage System because they're a major part of the building. And this can be useful to tell the difference if both systems activated at the same time
@nics-systems-electric
@nics-systems-electric 2 месяца назад
You can tell which system if there is strobe going off on the garage that's why there is a blue strobe for building annunciation
@keithpierce8458
@keithpierce8458 2 месяца назад
Great video
@Sylvite.
@Sylvite. 2 месяца назад
What do the notifications look like on your phone? (What do they say, what pictures do they have if any, what system is in alarm, etc)
@nics-systems-electric
@nics-systems-electric 2 месяца назад
No detailed information just a power loss but I showed that in both of my videos on installing it in the garage and house system
@Flamenmagic
@Flamenmagic 2 месяца назад
Let’s see for may tests For the garage: the pull in the storage shed For the house the smoke by the front door
@MrJohnnyDIY
@MrJohnnyDIY 2 месяца назад
What tome do you have the System Sensor L-series horn strobe in the main garage set to?
@nics-systems-electric
@nics-systems-electric 2 месяца назад
All of them are on low
@Firealarmperson902
@Firealarmperson902 2 месяца назад
i want to see the pull station in the house. love the video
@nics-systems-electric
@nics-systems-electric 2 месяца назад
Which one? There's four of them and we did one in this video.
@Firealarmperson902
@Firealarmperson902 2 месяца назад
@@nics-systems-electric the one in laundry room
@AnaSilva-de9yj
@AnaSilva-de9yj 2 месяца назад
Great videos you have
@rodgodx345
@rodgodx345 2 месяца назад
U should do a drill test on the annunciator
@nics-systems-electric
@nics-systems-electric 2 месяца назад
I could do it separately however it can't be used as the monthly test as it's not a legal test
@brandonkonicki2177
@brandonkonicki2177 2 месяца назад
Are you going to add to the house system a couple of co alarms and a a strobe on the front of the house ?
@nics-systems-electric
@nics-systems-electric 2 месяца назад
No because CO detection is not necessary and outside strobes are too aesthetically not pleasing
@stillthakoolest
@stillthakoolest 2 месяца назад
There is no gas in the house so whats the point
@GaryBeltz
@GaryBeltz 2 месяца назад
What did Jackson do that got him banished to the back yard? That LF horn strobe closest to the panel really makes the wall vibrate lol
@nics-systems-electric
@nics-systems-electric 2 месяца назад
Because he's freaking out and being an ass. I think the F clips need to be tightened on the box
@Williams_elektronik
@Williams_elektronik 2 месяца назад
22:33 POV: nick thinking on a good aprils fools joke but then remebering that the video is coming out later
@user-fd6so2bs1d
@user-fd6so2bs1d 2 месяца назад
for the garage, you should use the tower pullstation if it is still there
@DanTDMJace
@DanTDMJace 2 месяца назад
It isn't
@Firealarmfanatic5967
@Firealarmfanatic5967 10 дней назад
​@@DanTDMJace it is still there
@lightsfansmore6619
@lightsfansmore6619 2 месяца назад
27:53 You should buy a muzzle for Jackson if you want to stop him from barking for no reason
@nics-systems-electric
@nics-systems-electric 2 месяца назад
That's not what they are meant for
@An_Official_Scratcher
@An_Official_Scratcher 2 месяца назад
You should make it so that when you silence the garage system, the chime strobe silences but the amber strobe keeps flashing until the garage system is reset.
@nics-systems-electric
@nics-systems-electric 2 месяца назад
How would that be possible
@cucumbers3292
@cucumbers3292 2 месяца назад
1/4 of the way to 100K nice
@relevanteaglealarms109
@relevanteaglealarms109 2 месяца назад
Trying to find the video on installing a massive lever switch on the demo board
@Fire-Lite457
@Fire-Lite457 2 месяца назад
Have you ever thought about replacing the KDM-R2 with an NCA-2 on the house system?
@nics-systems-electric
@nics-systems-electric 2 месяца назад
No as it makes programming difficult or impossible without using verifier
@Fire-Lite457
@Fire-Lite457 2 месяца назад
@@nics-systems-electric Yeah that’s true.
@v8guru402
@v8guru402 2 месяца назад
Idea for another update. You can have the garage door open automatically, when the CO alarm goes off.
@nics-systems-electric
@nics-systems-electric 2 месяца назад
If residential garage doors had contacts that could be tied into
@eDoc2020
@eDoc2020 2 месяца назад
@@nics-systems-electric Almost all openers (except some of the latest models) just use dry contacts for the wall button. Add a magnetic reed switch (to tell if the door is closed or not) and then a relay could activate the button. That should be reliable enough but won't work if the door is only partially open. A more reliable way could be to hold the safety sensor circuit open while the alarm is active and pulse the button. That should only fail if the door is already moving the moment the alarm comes in.
@nics-systems-electric
@nics-systems-electric 2 месяца назад
@@eDoc2020 mine does not operate with a dry contact
@eDoc2020
@eDoc2020 2 месяца назад
@@nics-systems-electric You must have one of those super-new ones then. You could still solder a pair of wires across the actual button in the controller if you really wanted to.
@Random_Emergency_Light
@Random_Emergency_Light 2 месяца назад
Nice Great video
@nics-systems-electric
@nics-systems-electric 2 месяца назад
Thanks
@Random_Emergency_Light
@Random_Emergency_Light 2 месяца назад
If i was you i would keep the 2 in main foyer of garage and washroom and the generator and outside and get rid of the non needed ones and you most Definitely need one in Furnace/Fire Alarm Panel Room
@jeanclinton682
@jeanclinton682 15 дней назад
Hi, I have an NFS 320 notifier fire alarm panel with 138 smoke detectors and 25 modules. Now my panel is showing multiple trouble"INVERB". The same device showing "inverb" trouble blinks a green colour as a normal device, sometimes the same device blinks a red colour and sometimes the same device keeps the LED red in colour. Could you please suggest to me your expert advice?
@KidderVerse
@KidderVerse 2 месяца назад
On the next test you shoukd set the house system off using the T-bar by the panel
@Harper_DobniYT
@Harper_DobniYT 2 месяца назад
Nic have you tried that trick I told you about with air freshener and the CO detector?
@nics-systems-electric
@nics-systems-electric 2 месяца назад
I have not yet
@DanTDMJace
@DanTDMJace 2 месяца назад
Whats the trick
@Harper_DobniYT
@Harper_DobniYT 2 месяца назад
@@DanTDMJaceyou spray air freshener on a CO detector and it’s supposed to go off
@CGray1234
@CGray1234 2 месяца назад
@@Harper_DobniYT Pretty sure that could damage the detector. There's a reason they make detector-rated sprays
@IanGSully
@IanGSully 2 месяца назад
Why was the "Signals Silenced" LED flashing on the panel for the house? It never usually does that... does it?
@nics-systems-electric
@nics-systems-electric 2 месяца назад
You'd have to give a timestamp to see which you are referring to
@IanGSully
@IanGSully 2 месяца назад
@@nics-systems-electric 10:31 It was flashing with the "Fire Alarm" LED
@nics-systems-electric
@nics-systems-electric 2 месяца назад
@@IanGSully yeah, I'm not sure why
@IanGSully
@IanGSully 2 месяца назад
@@nics-systems-electric Just looking at the panel's manual. And what I found on Page 12 of the manual, it says that when it is flashing "Signals Silenced" like that it means that there are some outputs that are off and some that are on. And that's due to the fact that you have the NAC 3 set on something else so right now it is not energized with an Alarm state like NAC 1 & 2 are.
@nics-systems-electric
@nics-systems-electric 2 месяца назад
@@IanGSully interesting thanks for the research
@eetnaviation
@eetnaviation 2 месяца назад
Next time please set off the tower pull-station!
@BlakeFA_TECH
@BlakeFA_TECH 2 месяца назад
Nj and nyc and Long Island had a 4.8 earth quake at 1036 it went off when I was in a meddle of a test!
@robertbeyers1308
@robertbeyers1308 2 месяца назад
For May 1st inspection have somebody help you with the testing. And set the house in the garage off at the same time. The second person will pull one on the inside switches. Why you do the other
@Beehivestaterailfan
@Beehivestaterailfan 2 месяца назад
Amazing video
@nics-systems-electric
@nics-systems-electric 2 месяца назад
Thanks
@ReignFreyta
@ReignFreyta 23 дня назад
Wow i love this one
@JyKrp
@JyKrp 2 месяца назад
Awesome
@marksmith-ew7ir
@marksmith-ew7ir 2 месяца назад
Nick Are you going to place a switch after the fuse holder to prevent electric shock when plugging the the fuse back in to restore from testing the generator.
@nics-systems-electric
@nics-systems-electric 2 месяца назад
I just talked about that because people keep complaining and explained it
@jodiwarren5381
@jodiwarren5381 Месяц назад
Do a Bring in your garage, even the high 1:22 1:23
@MrJohnnyDIY
@MrJohnnyDIY 2 месяца назад
I know you did a tutorial of how to wire a pull station non addressable to a horn strobe but could you possibly do another but with a non addressable fire light dual action pull station and a different horn strobe?
@nics-systems-electric
@nics-systems-electric 2 месяца назад
It's the same thing
@joshlambeth9200
@joshlambeth9200 2 месяца назад
Nice
@ivanschmutzok2255
@ivanschmutzok2255 Месяц назад
average girl: hey I have a tree house in my yard what do you have nic: a substation
@techadka
@techadka 2 месяца назад
Do you have alarm in your house for carbon monoxide?
@nics-systems-electric
@nics-systems-electric 2 месяца назад
No not necessary
@michaelhicks3341
@michaelhicks3341 2 месяца назад
Nick we had power outage six times at our house
@Williams_elektronik
@Williams_elektronik 2 месяца назад
Its funny how nick has summer and i in sweden has snowstorm and -10 celsius
@michaelhicks3341
@michaelhicks3341 2 месяца назад
Nick do the house and the garage in May
@nics-systems-electric
@nics-systems-electric 2 месяца назад
I do them both once a month
@Harper_DobniYT
@Harper_DobniYT 2 месяца назад
Part I loved about the video 00:00 - 30:09
@Eterrnal_Andrew
@Eterrnal_Andrew 2 месяца назад
Yo Wsp nic!
@raf-e-leo
@raf-e-leo 2 месяца назад
Hi
@camden-mg3wz
@camden-mg3wz 2 месяца назад
Says it’s not a 30 minute test ends I’d being 30 minutes long
@matthewphelan9288
@matthewphelan9288 5 дней назад
there are two types of dogs hearing the fire alarm or smoke alarns ayla (calm dogs) 😇😇😇😇😇😇😇😇😇😇😇😇 jaxson (the angry dogs)🤬🤬🤬🤬🤬🤬🤬🤬🤬🤬🤬🤬🤬🤬🤬🤬🤬🤬🤬🤬
@Neptunesalad12
@Neptunesalad12 2 месяца назад
Next month activate both the fire alarm system and carbon monoxide system at the same time
@justinramey121
@justinramey121 2 месяца назад
👍👍👍👍👍👍👍👍👍👍👍👍 that's for you nic
@cincophone_
@cincophone_ 2 месяца назад
Hey, Nic, when I was talking to my friends today, they ran away from me! Why? I feel bad about that!
@nics-systems-electric
@nics-systems-electric 2 месяца назад
Sounds like a them problem
@cincophone_
@cincophone_ 2 месяца назад
​@@nics-systems-electricOkay! What do you mean?
@CGray1234
@CGray1234 2 месяца назад
@@cincophone_ it's their problem
@cincophone_
@cincophone_ 2 месяца назад
@@CGray1234 How is it their problem
@CGray1234
@CGray1234 2 месяца назад
@@cincophone_ They're just bad friends
@stormspotter
@stormspotter 2 месяца назад
edwards integerty and wheelock ns
@winnipegmbrailfan2013
@winnipegmbrailfan2013 2 месяца назад
Hey how are you this weekend
@nics-systems-electric
@nics-systems-electric 2 месяца назад
Hard to tell just started
@fortniteinminecraftt3794
@fortniteinminecraftt3794 2 месяца назад
What salary do you make a month in Canada as a fire Marshall
@nics-systems-electric
@nics-systems-electric 2 месяца назад
@@fortniteinminecraftt3794 I have no idea I'm not one
@CJP_Productions
@CJP_Productions 2 месяца назад
@@nics-systems-electric your just like me then, i pretend, act, and think im a fire marshall, but in reality im just an unpaid assistant, but the thing i get "paid" with gifts do :/
@nics-systems-electric
@nics-systems-electric 2 месяца назад
@@CJP_Productions I don't pretend to be a fire marshal i've never claimed to be one. I am apprentice electrician that's what I do. depending on the company you're with you will often be handling lots of fire alarm as an electrician and working closely with technicians.
@AnaSilva-de9yj
@AnaSilva-de9yj 2 месяца назад
Where’s the annunciatior for garage
@nics-systems-electric
@nics-systems-electric 2 месяца назад
There isn't one it's not needed
@AnaSilva-de9yj
@AnaSilva-de9yj Месяц назад
😮😮
@windy21397
@windy21397 2 месяца назад
Hello😊
@gamerboy12970
@gamerboy12970 2 месяца назад
Yea
@Earth_Number_12
@Earth_Number_12 2 месяца назад
Why did you replace your Led alarm back to the strobe and I expected you replaced your advances in the building with L series Strobes and also you have a bathroom in your house are you gonna put a remote strobe in there
@nics-systems-electric
@nics-systems-electric 2 месяца назад
No I never had LED alarms up
@Earth_Number_12
@Earth_Number_12 2 месяца назад
@@nics-systems-electric are you gonna replace the advance strobes into the L series Strobes except the Outside ones?
@nics-systems-electric
@nics-systems-electric 2 месяца назад
@@Earth_Number_12 probably not
@Dawezil
@Dawezil 2 месяца назад
1 hour or less team
@michaelfmarek
@michaelfmarek 2 месяца назад
Yes
@CGray1234
@CGray1234 2 месяца назад
Cringe
@raf-e-leo
@raf-e-leo 2 месяца назад
Wassup nic how is your weakend right now
@AnaSilva-de9yj
@AnaSilva-de9yj 2 месяца назад
😂
@Walnutdie
@Walnutdie 2 месяца назад
Under 1 hout club join here 👺👺👺👺👺👺👺
@CGray1234
@CGray1234 2 месяца назад
Cringe
@dustinkey8885
@dustinkey8885 2 месяца назад
do a drill
@nics-systems-electric
@nics-systems-electric 2 месяца назад
Can't use drill as a monthly test that does not count
@CJP_Productions
@CJP_Productions 2 месяца назад
@@nics-systems-electric he/she meant as in the NEXT video you upload
@nics-systems-electric
@nics-systems-electric 2 месяца назад
@@CJP_Productions I'm aware of that however you cannot use the drill button as a functional test
@giamansd712
@giamansd712 2 месяца назад
duct detector in the house and bathroom detector in building b
@cjelevators223
@cjelevators223 2 месяца назад
First lol.
@NyxKemo
@NyxKemo 2 месяца назад
Cringe
@SodiumInduction-hv
@SodiumInduction-hv 2 месяца назад
Cringe
@CJP_Productions
@CJP_Productions 2 месяца назад
whats wrong with saying "first"?, we ALL do that, stop acting like he/she said the "hard-R"
@cjelevators223
@cjelevators223 2 месяца назад
@@CJP_Productions i agree lol
@SodiumInduction-hv
@SodiumInduction-hv 2 месяца назад
@@CJP_Productions 💀nobody is acting like anyone said the hard r
@Corwin09-ji8sx
@Corwin09-ji8sx 2 месяца назад
The so-called fire in your shed was a fake, and was only meant for April Fools. Right?!
@nics-systems-electric
@nics-systems-electric 2 месяца назад
April fools
@Corwin09-ji8sx
@Corwin09-ji8sx 2 месяца назад
​@@nics-systems-electricOf course it was made for April Fools, but the wildfire risk getting higher in the U.S and Canada is real.
@nics-systems-electric
@nics-systems-electric 2 месяца назад
@@Corwin09-ji8sx you asked so I told you... currently almost all of British Columbia is at very low or low danger rating however that has nothing to do with my April fools video.
@user-gv7nc4ij1p
@user-gv7nc4ij1p 2 месяца назад
I hate fire alarm.🚨🔈🔉🔊
@nics-systems-electric
@nics-systems-electric 2 месяца назад
Don't watch the videos then
Далее
90% Don't Know About This Fatal Generator Connection
11:17
Basement Fire System Test 26 | Siemens Horn/Strobes
15:30
Add Outlet To Unfinished Basement Or Garage
14:16
Просмотров 822 тыс.
Honeywell/Ademco Vista 20p Test 12: The voice siren
12:07
До конца😂😂😂😂
0:19
Просмотров 4,8 млн