Charging And Troubleshooting Air Conditioning In Low Ambient Conditions 

HVAC Know It All
Подписаться 33 тыс.
Просмотров 9 тыс.
50% 1

When charging or troubleshooting air conditioning systems in low ambient conditions, it is important to understand the concept and methods of doing so. Check out this quick podcast on the subject anchor.fm/hvac.... In the video, an ICM condenser fan speed control was used with a thermistor. I had to troubleshoot and determine the best place for the thermistor positioning. Once the position was determined, the charge was adjusted to ensure optimal performance in low load conditions.
Save 8% on your purchase www.trutechtoo... with promo code knowitall
Visit HVAC Know It All on social media Facebook
/ hvacknowitall
Instagram
/ hvacknowitall1
LinkedIn / gary-mccr. .
Listen to the HVAC Know It All Podcast anchor.fm/hvac...
Visit www.hvacknowit... for articles, and tips
#lowambientkitinstallation #lowambientairconditioning #lowambientcharging

Опубликовано:

 

24 янв 2021

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 46   
@HVACKnowItAll
@HVACKnowItAll 3 года назад
Love AC in the winter time 😆
@kemuelpounall8740
@kemuelpounall8740 3 года назад
Hey...The refrigerant that you added ...will it affect the system in summer time or when the ambient temperature rises?
@elijahbasika3126
@elijahbasika3126 3 месяца назад
Watching from Papua New Guinea...
@Bluecollarrebel
@Bluecollarrebel 3 года назад
Never had to install one but now I'm fully infromed👊
@Luzt.
@Luzt. 3 года назад
Great content. Thank you for posting. 1. The temperature-pressure relationship on which the operation of this regulator is based is only valid for mixture of gas + liquid. The location of te probe should be close to the end of condenser where no hot gas/superheated vapour can exist. Putting the sensor on the liquid side of the condenser should not cause problems, maybe raise the pressure lightly. 2. The sensor should not be affected by (temperature of) the air. Blocking air flow around it with e.g. some sillicone sealant could be a good idea. 3. The fan should not spin below 70F measured by the sensor but it looks like it did spin. Have you checked that the fan stops at 70F by putting the sensor to 70F and below? 4. It would be a good idea to disconnect the fan manually and check pressures as a first step to confirm that the controller can actually do its job. 5. Obviously, the 'heat-pump jumper" was set correctly.
@HVACKnowItAll
@HVACKnowItAll 3 года назад
Yes fan stops. Sensor position final location was in the coil out the outlet. The controller didn't perform well with the sensor on the liquid line and insulated on 3 different units.
@HVACRSurvival
@HVACRSurvival 3 года назад
Well laid out video and explained in full detail👍👍. Good job!
@HVACKnowItAll
@HVACKnowItAll 3 года назад
Thank you!
@Coonhoound89
@Coonhoound89 3 года назад
We also rig units were I work with a cut in cut out pressure switch wired through a relay to achieve the similar outcome for low ambient conditions
@jesuss4437
@jesuss4437 3 года назад
I Installed this on a Trane 20 ton condenser and both of my motors over heated after 40 mins of run time. Spoke with tech support and confirmed that it was set up correctly. Was told that with that model unit I’d have to upgrade both the motors, add heat sinks, and rain guards.
@HVACKnowItAll
@HVACKnowItAll 3 года назад
Was the motors that burnt out ball bearing?
@jesuss4437
@jesuss4437 3 года назад
@@HVACKnowItAll yes. According to tech support they were ball bearing. They still worked after the cooled off.
@wd8557
@wd8557 2 года назад
For me just so I know it works and I don't want to be called back ICM makes a transducer that can be installed on the discharge .
@appa32472
@appa32472 2 года назад
Same issue I had today except on a rtu. Carrier.
@nakiapringley5391
@nakiapringley5391 2 года назад
Great tip💯💯💯💯
@hvacir9176
@hvacir9176 3 года назад
thanks for sharing
@HVACKnowItAll
@HVACKnowItAll 3 года назад
My pleasure
@chriswheeler4962
@chriswheeler4962 2 года назад
Great video! Thank you
@actechformallyyomama746
@actechformallyyomama746 3 года назад
I prefer pressure action on low ambient controls. I always add a freeze stat to the evaporator as well. I’ve also found TXV with a hard start kit for better in low ambient control. Depends on what the customer will pay for. Good video. Thanks and stay safe.
@billj4859
@billj4859 3 года назад
I've never had good luck with these controls
@actechformallyyomama746
@actechformallyyomama746 3 года назад
I use a fan cycle switch myself. Tried and true. I’ve used them for over 40 years.
@tongwang-fk4ox
@tongwang-fk4ox Год назад
icm head pressure control does not come with the wire that connect the line 1 to the line 1 terminal. what kind of wire use to connect line 1 to the line 1 terminal?
@capitolrefrigerationheatin7501
@capitolrefrigerationheatin7501 3 года назад
never have good luck with those fan cycling, always find issues with them. I use the one that sense pressure not temperature
@FORVERIMAGES
@FORVERIMAGES 3 года назад
Pressure sensing is the only way to go, never been a fan of temp sensing for low ambiant control or fan cycling, pressure never lies.
@hvacrnortheastern2110
@hvacrnortheastern2110 3 года назад
That's why we don't use fan control in refrigeration system it shows the different by using a fan control txv doesn't get liquid like a head master control.
@HVACKnowItAll
@HVACKnowItAll 3 года назад
Yes ORD and ORIs work great
@DanO181919
@DanO181919 3 года назад
Good video! Do you have any videos on wiring diagrams for walk-in coolers and/or freezers
@HVACKnowItAll
@HVACKnowItAll 3 года назад
I dont no longer sorry
@coldfinger459sub0
@coldfinger459sub0 3 года назад
Air conditioning in winter time call the ambient conditions go down to Goodwill or a thrift shop and pick up a six man or eight man tent cut the bottom out set up a tent it’ll be nice and 90° in there and you could set your sub cooling and superheat as if it was summertime in Florida Are use a pressure switch I don’t like the thermistor
@malton88
@malton88 3 года назад
Does this ambient control kit need other accessories Such as a hard start kit or anything else? And does it matter if its a txv or piston coil?
@HVACKnowItAll
@HVACKnowItAll 3 года назад
Hard starts for locked up compressors or low voltage situations. Not needed in low ambient conditions. You'll need a crankcase heater for sure and possibly wind baffles.
@edilsonserafim4784
@edilsonserafim4784 2 года назад
Hey man hope everything is ok I am always watching your videos,I worked on a carrier motormaster low ambient control today same scenario,it’s tricky to set the right evaporating temperature right due to condenser fan constantly speeding up and down some times you will run under 32° evaporating temperature for seconds and it will go back up,specially if there is low load inside the room,you can correct me if I am wrong I know you have much more experience then me too
@HVACKnowItAll
@HVACKnowItAll 2 года назад
Yes difficult to set up for sure, it'd much easier if it was fan speed instead of fan cycle
@edilsonserafim4784
@edilsonserafim4784 2 года назад
@@HVACKnowItAll I agreed now due to is temperature outside bypassing the condenser fan won’t work either thanks for replying my message
@brugotti
@brugotti 3 года назад
fan cycle switch
@HVACKnowItAll
@HVACKnowItAll 3 года назад
They work too, but a lot of pressure fluctuations. Fan speed works much better.
@xraybravo7180
@xraybravo7180 3 года назад
Now whats that sleeve bearing and ball bearing ?
@HVACKnowItAll
@HVACKnowItAll 3 года назад
Ball, I explained that in the video
@ebcrew
@ebcrew 3 года назад
Can you go off of sub cooling at such a low temp?
@HVACKnowItAll
@HVACKnowItAll 3 года назад
If the fan speed is maintaining 100⁰f why not
@sjefoekel6058
@sjefoekel6058 3 года назад
What do you mean condenser froze up? Was it in heat mode?
@HVACKnowItAll
@HVACKnowItAll 3 года назад
The suction line freezing and the compressor.
@xraybravo7180
@xraybravo7180 3 года назад
York socks last time I called tech support it took 30 minutes
@HVACKnowItAll
@HVACKnowItAll 3 года назад
They answered my call right away but yes sometimes wait times can be long.
@craighvac1808
@craighvac1808 3 года назад
Those icm controls are junk, never last very long
@HVACKnowItAll
@HVACKnowItAll 3 года назад
Time will tell
Далее
Short 38 - Low Ambient Cooling
16:48
Просмотров 6 тыс.
Compressor Oil Return and Oil Failure Controls
14:12
Просмотров 31 тыс.
Refrigerant Overcharge Troubleshooting and Prevention
21:47
HVAC 107 Scenario: Low Ambient
11:40
Просмотров 11 тыс.
WALK IN COOLER WINTER CHARGE
10:10
Просмотров 12 тыс.
ICM325A Universal Head Pressure Control (Install)
8:51