COM18. ModbusTCP Client via Siemens S7-1200/S7-1500 PLC and TIA Portal 

Electrical Automation Hands-On
Подписаться 22 тыс.
Просмотров 105 тыс.
50% 1

#ModbusTCP #Siemens #PLC
Next: COM19. ModbusTCP Server via Siemens S7-1200/S7-1500 • COM19. ModbusTCP Serve...
Playlist: • Industrial Automation ...
In this video, Siemens S7-1200/S7-1500 runs as Modbus TCP Client, while Test Tool ModSim 64 runs as Modbus TCP Server.
COM16. ModbusTCP Client via Allen-Bradley CompactLogix PLC
• COM16. ModbusTCP Clien...
COM17. ModbusTCP Server via Allen-Bradley CompactLogix PLC
• COM17. ModbusTCP Serve...
COM18. ModbusTCP Client via Siemens S7-1200/S7-1500 PLC and TIA Portal
• COM18. ModbusTCP Clien...
COM19. ModbusTCP Server via Siemens S7-1200/S7-1500 PLC and TIA Portal
• COM19. ModbusTCP Serve...
COM20. ModbusTCP - Siemens S7-1200/S7-1500 (Client) and Allen-Bradley CompactLogix (Server)
• COM20. ModbusTCP - Sie...
COM21. ModbusTCP - Allen-Bradley CompactLogix (Client) and Siemens S7-1200/S7-1500 (Server)
• COM21. ModbusTCP - All...

Наука

Опубликовано:

 

21 фев 2021

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 174   
@waymamma
@waymamma 3 года назад
Fantastic video! Very well produced and with clear explanations, thanks so much for your efforts!
@electricalautomation
@electricalautomation 3 года назад
Glad it was helpful! Welcome!
@ndukwehenryibiam
@ndukwehenryibiam Год назад
One of the best tutorials on MODBUS....if not even the very best detailed one here. Thanks so much sir
@pablojuliano4066
@pablojuliano4066 11 месяцев назад
Great video to understand how to use modbus client in tia portal. Thank you for the explanation!
@electricalautomation
@electricalautomation 11 месяцев назад
Glad it was helpful! Welcome!
@sarahmoody7574
@sarahmoody7574 6 месяцев назад
As per all the other comments this is a fantastic video, thanks so much as I was much in need of it! Modbus all configured and now understood for future use!
@electricalautomation
@electricalautomation 6 месяцев назад
Glad it helped!
@rangaswamy8604
@rangaswamy8604 3 года назад
Good series of videos on communications. Thank you.
@electricalautomation
@electricalautomation 3 года назад
Glad you like them! I am working two videos talking about the ModbusTCP between Siemens and Allen-Bradley PLC. They will be launched in next week.
@arbjful
@arbjful 3 года назад
This is great tutorial for starting on Siemens MODBUS communication, I found this very helpful for starting on MODBUS TCP communication. You have explained the concept very clearly and descriptively. Thanks for posting video.
@electricalautomation
@electricalautomation 3 года назад
Glad it was helpful! Welcome to my channel!
@arbjful
@arbjful 3 года назад
@@electricalautomation I have a question regarding Disconnect flag, is this always False?? No need to set True?? For some reason the Status always shows 7002..I don't know why
@electricalautomation
@electricalautomation 3 года назад
@@arbjful "Disconnect" should be OFF. ON at here means disconnecting the communication connection. Please view carefully all the settings and parameters. Also check the settings from your server-side, it also may be blocked by the windows firewall.
@banci1100
@banci1100 2 года назад
YOU ARE HAVING A VERY USEFUL VIDEO ON THE EARTH FOR THIS TERM!! Thanks alot.
@electricalautomation
@electricalautomation 2 года назад
Thank you so much for your comments! WELCOME!
@electricalautomation
@electricalautomation 2 года назад
Thank you so much for your comments! WELCOME!
@WilloooIsBlue
@WilloooIsBlue 2 года назад
Huge thanks for this video, helped me out massively with a project I was working on. -TKC
@electricalautomation
@electricalautomation 2 года назад
Glad it helped! Welcome!
@kgauravb
@kgauravb 2 года назад
Very informative thank you for sharing such valuable knowledge. 👏🙏
@electricalautomation
@electricalautomation 2 года назад
So nice of you! Welcome!
@egrabhishek
@egrabhishek 2 года назад
Thank you for the awesome video and for all the help. Just a small tip for any one struggling with SIEMENS PLC 1212C When using MOD_BUS_CLIENT >> Set the correct slave address in System Generated MB_CLIENT_DB. Set MB_UNIT_ID to your required Slave Address (Default in SIEMENS is 255). Upload program and restart the PLC for changes to take effect. Use the same Slave Address in your Desktop application as well. Hope it helps someone.
@electricalautomation
@electricalautomation 2 года назад
Thanks for pointing it out, and highlight this issue my dear friend. I also discussed shortly at 30:58 in the video. The UNIT_ID is a very explicit hidden behind, figuring out this can save many time during the ModbusTCP communication troubleshooting.
@gabrieldigiuseppe3106
@gabrieldigiuseppe3106 11 месяцев назад
Incredible! Thank you very much for the excellent video
@electricalautomation
@electricalautomation 11 месяцев назад
Glad you enjoyed it!
@jrffabiano2544
@jrffabiano2544 6 дней назад
Ótima aula professor! Parabéns 👏👏👏
@electricalautomation
@electricalautomation 2 дня назад
Thanks!
@jakobdannesboe9900
@jakobdannesboe9900 Год назад
This is an excellent video.! thank you.! Keep up the good work
@electricalautomation
@electricalautomation Год назад
Thanks, will do!
@moisesbraga9393
@moisesbraga9393 Год назад
Great vídeo man! Props to you. This one will help me a lot. I just subscribed to your channel.
@electricalautomation
@electricalautomation Год назад
Welcome! Thanks a lot!
@rucahuenu3252
@rucahuenu3252 2 года назад
Great JOB ! Thank you very much to share it !
@electricalautomation
@electricalautomation 2 года назад
Welcome! I glad you like them!
@MarcoMolino-tb5yw
@MarcoMolino-tb5yw Месяц назад
incredibly complete video, thank you very much!!
@electricalautomation
@electricalautomation Месяц назад
Thanks! Glad it would be helpful!
@d.militomilito2002
@d.militomilito2002 2 года назад
Really good explanations! you are the best.
@electricalautomation
@electricalautomation 2 года назад
Glad you like them! Thanks for watching!
@felipepaiva4798
@felipepaiva4798 3 года назад
Congratulation for the video and thanks for the tips! I tested the Modbus client mode of PLC with a Cobot UR10 (Universal Robots) as server, and had a good comunication to data exchange. So, that is an item that i like to share with everybody, in my case the error 8383 appears when i begin the comunication and to solve this error i change the "Data_len" parameter (Before: 15 | After: 5) and after this, both comunicate normally reading and writing to/from the address of cobot! OBS: The data was at format "int".
@electricalautomation
@electricalautomation 3 года назад
Thanks for watching and thanks for your sharing. According to the 'int', I guess you are using holding register 4xxxxx. and probably the Cobot provides 5 registers to communicate. Therefore, 15 length didn't work. Good to hear it works. Thanks!
@daigealbertas
@daigealbertas 3 года назад
Thanks! Great video and perfect explanation!!!
@electricalautomation
@electricalautomation 3 года назад
Glad it was helpful! Thanks for watching! Welcome!
@user-ji5uk8tq8u
@user-ji5uk8tq8u 4 месяца назад
Thank you very much for this great video!
@electricalautomation
@electricalautomation 3 месяца назад
Glad it was helpful!
@wandersonpereira9884
@wandersonpereira9884 5 месяцев назад
Awesome video, man. You saved my life! Thanks.
@electricalautomation
@electricalautomation 5 месяцев назад
Glad it helped! Welcome!
@kme8134
@kme8134 2 года назад
Thank you!!! Very good explanation.
@electricalautomation
@electricalautomation 2 года назад
Glad it was helpful! Welcome!
@crja4114
@crja4114 Год назад
Nice Video, thanks man
@alfonsogustavo91
@alfonsogustavo91 Год назад
Nice video man, thanks!
@electricalautomation
@electricalautomation Год назад
Glad you liked it!
@fabiobettanello2625
@fabiobettanello2625 2 года назад
Very useful, thank you!
@electricalautomation
@electricalautomation 2 года назад
Glad it was helpful!
@bmw23i47
@bmw23i47 9 месяцев назад
Awesome, Thanks!
@electricalautomation
@electricalautomation 8 месяцев назад
Welcome! Thanks!
@bobeldukla
@bobeldukla 3 года назад
Very helpful. Thank You very much..
@electricalautomation
@electricalautomation 3 года назад
Glad it was helpful! Thanks, Please view more videos from the play list ru-vid.com/group/PL762SfoJC-e8Ng4OlME8WfQxf9qBhNTJh
@omkardeshpande6999
@omkardeshpande6999 8 месяцев назад
Incredible to me!!
@electricalautomation
@electricalautomation 8 месяцев назад
Thanks! Glad you like them
@MDArman-zi9se
@MDArman-zi9se Год назад
Very good video
@althafali1667
@althafali1667 Месяц назад
Finally, it's working very very thanks
@electricalautomation
@electricalautomation Месяц назад
Welcome 👍
@ricardojohanrojasyupan6022
@ricardojohanrojasyupan6022 Год назад
GRACIAS PAPU
@exodussian
@exodussian 8 месяцев назад
Perfect
@electricalautomation
@electricalautomation 8 месяцев назад
Thanks!
@paulescalante7986
@paulescalante7986 Год назад
beast
@mateussilva3756
@mateussilva3756 2 года назад
Nice explanation! I have a question: What requisition conditions would you use if you had to read data from more than 2 unit_ID in the same slave?
@electricalautomation
@electricalautomation 2 года назад
Thanks for watching, Usually one device/ basically one brand of device will only have one unique Unit ID, the settings can be found from 31:00. I never saw a device with two Unit_ID. If incase a device have, then use another FB and instance DB to Call read/or write
@muhammaddanyal2077
@muhammaddanyal2077 8 месяцев назад
Yes the question is correct , because this can happen while reading dsta from Rtu to TCP gateway which can have multiple devices with unique unit ids and same ip of gateway
@PhotoshopTutorialsInTamil
@PhotoshopTutorialsInTamil 2 года назад
Thank you ❤️
@electricalautomation
@electricalautomation 2 года назад
Welcome! Thanks for watching!
@prataps2341
@prataps2341 3 года назад
Thanks for detailed explanation! Two questions: 1. Isn't there need to use any function codes such as 01H to read output coil objects, 02H to read input coil object, 03H to read holding register and many more types of function codes? 2. If I defined S7-1200 CPU as a Modbus server, how can we assign the modbus addresses to tags...for example MW50, M10.0?
@electricalautomation
@electricalautomation 3 года назад
yes, you can run 01H or 02H. please check the video 11:58 the "MB_DATA_ADDR" 1 to 9999, 10,001 to 19,999. Regarding your second question, MB_DATA_PRT at 16:49 is the PLC tags for matching the Modbus registers
@krzysztofsurgot4537
@krzysztofsurgot4537 2 года назад
Hi, from the other side. I'm wondering about a difference. We can create Function Block and multi-instance of MB_CLIENT instead of the usual Function and Single instance of MB_CLIENT (like in your video). Both ways a program works correctly though which choice is better (including optimization)? Thank you for the video, outstanding work!
@electricalautomation
@electricalautomation 2 года назад
Yes, for multiple FB call, you can use multiple instance DB in one FB call. Multiple instance look nice and great organized, but it is slightly pain when you are doing trouble shoot. It depends on if you did the communication test before or not, if yes, then you can use multiple instance.
@krzysztofsurgot4537
@krzysztofsurgot4537 2 года назад
@@electricalautomation Now it's clear and obvious. Thank you :)
@user-rz6lz5tf5x
@user-rz6lz5tf5x 2 года назад
Good explain
@electricalautomation
@electricalautomation 2 года назад
Thanks for liking! Welcome!
@prabhu0820
@prabhu0820 10 месяцев назад
great!
@electricalautomation
@electricalautomation 10 месяцев назад
Thanks!
@mehmetsukrumeydanc424
@mehmetsukrumeydanc424 3 года назад
ALLAH RAZI OLSUN
@JaikumaR_JacK
@JaikumaR_JacK Год назад
Mass
@donvaryvengesa4711
@donvaryvengesa4711 2 года назад
well explained i have learnt a lot , just one question - if i want to establish communication with S7100 and Motoman Robot using Modbus , is there any file that i have to install on TIA
@electricalautomation
@electricalautomation 2 года назад
To implement Modbus via TIA Portal and S7-1700/1500, you do not need to install additional package, using built in FB and programming discussed in this video is good.
@khbatman9
@khbatman9 Год назад
Thank you for your video. It's a great.
@electricalautomation
@electricalautomation Год назад
Glad you like it! Thanks
@afiffizer5084
@afiffizer5084 Год назад
Where you get device plc_sql_ha?
@Preethigrace
@Preethigrace Год назад
Do we need to add the modbus block in the tia portal or we can directly connect plc to pc via modbus? will u please respond for this soon
@electricalautomation
@electricalautomation Год назад
You need to program the PLC for the modbus communication. If you are going to do Modbus RTU, you also.need to purchase RS232/RS485 modlue by using s7-1200. This video is talking about Modbus TCP, it is RJ 45 ethernet port.
@mb_3000
@mb_3000 7 месяцев назад
Hi I was wondering if you can help me. I have a schrack meter connected to a moxa modbus mb 3000 and my job is to interpret measurements made my the meter in c++. My question is how to connect the modbus to my pc and do you think this tutorial alone is enough to make a valid connection to modbus and will I be able to program in visual studio using the registers? Thank you in advance.
@electricalautomation
@electricalautomation 7 месяцев назад
I am not using and programming C++. For your question, you have to figure out how to use C++ running as Modbus Master (Client) function to connect the Schreck meter. It would be not a easy job unless you can find a proper specialist who did this feature before. Good luck
@afiffizer5084
@afiffizer5084 Год назад
Can i use PLC Sim for run the program?
@marinfrankovic5152
@marinfrankovic5152 Год назад
Hello sir, your video is really good and i really liked it, well explained 🙂 this is a rather stupid question but i want to ask, for the server/client the devices must be plc-s? In my case i have a plc with profinet cable going to a switch were then arrive two cables connected via modbus tcp protocol. Can this fb and this logic also be implemented here? Best regards!
@electricalautomation
@electricalautomation Год назад
Thanks for your watching! You can use Fb and use two instances DB, each one serve one Modbus TCP logic connection.
@liteglow2000
@liteglow2000 17 дней назад
@Electrical Automations : Can you show an example when adding 2 or more MODBUS units ? do it all over again, or use the same blocks ?
@electricalautomation
@electricalautomation 13 дней назад
You can change the settings for the 'target address and modbus address' to switch the communication target, OR , can multiple ModbusTCP Client FB and instance DBs to communicate with different target.
@samershurman877
@samershurman877 Год назад
Hello, Thanks for the video, I do the same, but could not read data from (modsim64) or any other reader. I try tens of times but it is not working at all. Please any suggestion to solve that matter?
@electricalautomation
@electricalautomation Год назад
There is no any hidden operation in the video. It includes every thing. Would you pls let me know your hardware, OS, and TIA Portal software revision you are using?
@mattmeyer8141
@mattmeyer8141 10 месяцев назад
Got this to work just like you said! thanks so much for the detailed expalanation!. Question for all of you. I have a datalogger that is going to pull data out of several PLC's. Should I make my data logger the master (server) and keep my plc's all slaves?
@electricalautomation
@electricalautomation 10 месяцев назад
Glad my video is helpful. If you going to use a software to pull the data, your datalogger will run as Modbus Client(master), your PLC will run as Modbus Server (Slave). You could refer my video ru-vid.com/video/%D0%B2%D0%B8%D0%B4%D0%B5%D0%BE-tacshyBnSp0.html for running the Siemens PLC as Modbus TCP Server case.
@achirayabhaswrr3678
@achirayabhaswrr3678 2 года назад
that's awesome vdo, just curious How many modbus client block can be used? example if we have 12 modbus devices to communicate with.
@electricalautomation
@electricalautomation 2 года назад
You need to check with A-B support for the resources of the controller you are using, because this AOI need TCP Socket resources. But You could also try cyclic change over the parameters and target on the AOI parameters, so do ONE TIME ONE TARGET, this will take only one connection resource.
@vatsalthaker2122
@vatsalthaker2122 3 года назад
My boss give me task to setup this block and make communication with plc you save my day thanks hoping to get more videos...😅😊
@electricalautomation
@electricalautomation 3 года назад
Hi Buddy, Glad to her the video could help! Welcome and thanks for watching!
@standard_user
@standard_user Год назад
How is it possible to read and write the same Modbus adress? Lets say in the holding register 40001 is for Start/stop/Auto/Manual etc. and i want to read at first the actual state and then wirte to 40001 bit 8 (for example the start bit)? I wann use the modbus mapping from the Siemens Climatix PLC
@electricalautomation
@electricalautomation Год назад
You have to plan your 120 Modbus registers into two areas for inputs and outputs respectively.
@lucianogutierrez936
@lucianogutierrez936 3 года назад
Thanks a lot for this amazing video! I have a question, I need to communicate three different servers. Can I add three different MB_CLIENT blocks? It's ok to call three at the same time?
@electricalautomation
@electricalautomation 3 года назад
Sure you can. S7-1200 has 8 TCP connection resources. Use different instant DB name for those three calls.
@lucianogutierrez5259
@lucianogutierrez5259 3 года назад
@@electricalautomation Thanks for your reply. So, to obtain different parameters of the same device I will call MB_CLIENT several times, with de same ID, IP, and instance data block; ensurig that each individual Modbus TCP request finishes execution. What do you thik about that?
@electricalautomation
@electricalautomation 3 года назад
@@lucianogutierrez5259 No. To use one Client to communicate three Server, you need to call three times MB_CLIENT with three different instant DBs. The parameters for the "CONNECT" are individually for each FB call.
@lucianogutierrez5259
@lucianogutierrez5259 3 года назад
@@electricalautomation Well, finally, to read two diffent parameters of one server I call two times MB_CLIENT with the same DB, but two different CONNECT variables. It's OK? CONNECT variables will only differ on ID (connection reference/identifier)? On S7-1200 System Manual V4.5 (13.8.4.2 Example: Legacy MB_CLIENT 1: Multiple requests with common TCP connection) uses the same CONNECT_ID. I'm so confusing about that. Thanks so much for your attention!
@electricalautomation
@electricalautomation 3 года назад
@@lucianogutierrez5259 Use different Instant DB, please. each call use different CONNECT variables. In the CONNECT, their target IP, can be the same target server. means this PLC does not know you are communicating one server or two server, IT ONLY CARES THE CONNECTION AND DATA.
@ethantu1976
@ethantu1976 Год назад
Hello, 如果寄存器是间断的,如何做轮询?或者要读多个server?
@adnansheikmytheen7549
@adnansheikmytheen7549 Год назад
If we connect multiple meters via modbus gateway where we need to set the slave device ID in PLC program
@electricalautomation
@electricalautomation Год назад
If the target devices are less than 8, then you can use different instance DB "like shown 5:00 DB10". Each device has a unique instance DB, ID, ADDR IP address as shown at 8:40
@mohabsayed-xl3dg
@mohabsayed-xl3dg 11 месяцев назад
readings are in word data type , how i can change to real type to match with actual reading ?
@electricalautomation
@electricalautomation 11 месяцев назад
A real variable comes with 4 bytes, but each modus register only takes two bytes. So either slipt a real and transfter it as two words, or using * 10 then.using Int instead if your real value is less than 6553.5
@viswajeethakuthota3286
@viswajeethakuthota3286 11 месяцев назад
Data transfer is okay but how to switch on / off the coils I don't want to read any data I want to simply on/ off coils in modbus function it is selected as 3 how to change it??
@electricalautomation
@electricalautomation 11 месяцев назад
operating the individual bool/coil needs to call the other Modbus FC code. but it is not efficient in the PLC CPU level communication. The common way is that using FC06 16 for exchanging WORD, then using PLC logic to decode the WORD into 16 bits.
@mitulsuthar3519
@mitulsuthar3519 Год назад
what could we do if we have to read the data with different offsets parameters?
@electricalautomation
@electricalautomation Год назад
You have to read an entire segment, then sort them out by your own program
@shadreckmugabe4841
@shadreckmugabe4841 Год назад
You are a star 🎉🎉🎉 , what a tutorial , consider offering online classes , if yes l want the details my lecturer.
@electricalautomation
@electricalautomation Год назад
Many thanks! Which kinds of topic you are planning to learn? Please find the my playlist, they include many interesting topics.
@maldyniel6362
@maldyniel6362 3 месяца назад
Can i ask u,why array must 120?
@darudxd6415
@darudxd6415 Месяц назад
There is no must, the array should be as long as the value written in DATA_LEN. He made array of 120 for simplicity. Note that the array of registers (read and write) should not be longer than 125. You can see that in help page of MB_CLIENT function block
@girishgajghate1367
@girishgajghate1367 Год назад
Thanks for sharng this video. Can u Please Upload a video for Modbus RTU.??
@electricalautomation
@electricalautomation Год назад
I don't have the hardware for the RS485 port, but Modbus RTU is the similar idea. Just the function block is not the same.
@sameerraj8933
@sameerraj8933 Год назад
Thank you
@electricalautomation
@electricalautomation Год назад
You're welcome!
@r-beanmondy6203
@r-beanmondy6203 Год назад
Thanks for your video, it's very helpful. Could I use it to communicate to actuator sensor using Modbus? With the same steps?
@electricalautomation
@electricalautomation Год назад
Yes, the method will be very similar. You could read the manual from this actuator and see the FC16 or other register variable.
@masrooralam6565
@masrooralam6565 Год назад
Thanks a lot for such a nice explanation sir. I got issue my connection is continuously connecting and disconnecting showing status 7002 and 80C5. I am using TIA V14SP1 with PLCSIM V14SP1.
@electricalautomation
@electricalautomation Год назад
I don't think PLCSIM none advanced can do this communication test.
@rezamagham4495
@rezamagham4495 2 года назад
I am a client and I have 5 server . How I can copy my same data on server 2 and 3 simultaneously?
@electricalautomation
@electricalautomation 2 года назад
You can use 5 Fb call with 5 different instance DB. Note the ID, Target IP address, Local Port should be difference, as shown at 8:23
@chanathipyaemounsuk6017
@chanathipyaemounsuk6017 2 года назад
TIA Portal 17 Can use function block Modbus TCP ?
@electricalautomation
@electricalautomation 2 года назад
Yes
@huyvo9402
@huyvo9402 2 года назад
can you make a setup to show us how to read/write 300 registers from slave device?
@electricalautomation
@electricalautomation 2 года назад
Hello, for Modbus communication, the longest registers can read OR write is around 252.
@industrialplcprogramming2452
hello there. i tried everything all the steps you have done and copy it doesnt work on my simulation. i used PLCSIM advance 4.0 and tia portal v17. my siemens ethernet address end with 137 these numbers i put in the remote ip address and my plc address ends with 140. the results only 7002.i hope u can try using plcsim advanced.
@electricalautomation
@electricalautomation Год назад
I would recommend you use the hardware for the test. Or contact Siemens if you purchased the Sim software.
@aminfamili5318
@aminfamili5318 2 года назад
Hello and thanks for the great video. I am dong the project but the status is #7002. What should I do?
@aminfamili5318
@aminfamili5318 2 года назад
Do you use just one Ethernet socket on your PC? Is it possible to get online and send and receive Modbus packet at the same time using just one ethernet socket?
@electricalautomation
@electricalautomation 2 года назад
One physical ethernet port can be used for multiple tasks, e.g. Profinet, TCP, Modbus TCP etc. For an initial setup, you can use an empty CPU for a test.
@mohdaatif882
@mohdaatif882 Год назад
hiiii,,,,, i am using this modbus tcp ...its working but when i am using NC and NO contact of %m0.5 clock bit for recieving and sending data then its permanent off condition and transmission is done one side ....its not working like On-Off
@electricalautomation
@electricalautomation Год назад
You can set MB0 to be controlled by the CPU, the setting is at the CPU property. The CPU can automatically control the bits to be different HZ.
@mohdaatif882
@mohdaatif882 Год назад
@@electricalautomation i used m0.0 but ots not working like on off bit
@mohdaatif882
@mohdaatif882 Год назад
@@electricalautomation and enabled the m0 bit from system and clock memory but its not work
@electricalautomation
@electricalautomation Год назад
@@mohdaatif882 You need to set the system clock memory and download the CPU
@mohdaatif882
@mohdaatif882 Год назад
hi sir , continue status error 80C8,, how to fix it
@wesleybarcelonista
@wesleybarcelonista 2 года назад
HI I HAVE THE STATUS ERROR (80A4). NEED HELP PLEASE THANKS
@electricalautomation
@electricalautomation 2 года назад
Which FB block show the error 80A4? 80A4 has different meanings on different FBs. But most likely your PLC cannot find the remote device. Check the settings from the other device.
@Time4yes
@Time4yes Год назад
That means I can connect my arduino to my plc right?
@electricalautomation
@electricalautomation Год назад
If your arduino support modbus protocol, that could be done
@Time4yes
@Time4yes Год назад
@@electricalautomation yes it does, I use codesys soft plc with it and it works fine.
@jims9916
@jims9916 3 года назад
thanks a lot for this excellent video. I get the error code 80C5. the status is toggling between 80C5, 7001 and 7002 . I am doing this test on PLCsim.Please can u help. Thanks
@electricalautomation
@electricalautomation 3 года назад
You'd better use hardware or PLCSimAdvance.
@simonemoser9490
@simonemoser9490 Год назад
Many thanks, you are the best I have a problem, i receive the data in the index 2 instead that in the index 1, why?
@electricalautomation
@electricalautomation Год назад
Most likely your address mapping has issue. And what do you mean about the "index". Can you show which min in the video?
@simonemoser9490
@simonemoser9490 Год назад
I mean that i receive the data in the position 1 of the array instead the position 0. I have another issue, i can read the data but i can't write the data, what could be the problem?
@simonemoser9490
@simonemoser9490 Год назад
My server is a hmi
@thohayvietnam1809
@thohayvietnam1809 2 года назад
Em đang cần support Modbus TCP của S7200. CÓ phí ạ. Bác giúp em với
@electricalautomation
@electricalautomation 2 года назад
Not sure I understood your word correctly, I am using translator. Are you asking if you can use S7-200 for Modbus TCP. Unfortunately, it can not. If you are using Smart S7-200 PLC. It can, but the old style S7-200, it can not do Modbus-TCP. You can use an Modbus-TCP/RTU adapter using as bridge.
@thohayvietnam1809
@thohayvietnam1809 2 года назад
@@electricalautomation i wrong typing. S71200 with modbus TCP,
@thohayvietnam1809
@thohayvietnam1809 2 года назад
@@electricalautomation please teamview help me.
@electricalautomation
@electricalautomation 2 года назад
@@thohayvietnam1809 My remote support is billable not for free and I have no time for remote support recently since I am very busy these days. Also In this video, I started from scratch and there is no hidden info. so if you review carefully and follow the steps, you should implement them successfully.
@matioz9125
@matioz9125 7 дней назад
Ok
@sourenamehr6087
@sourenamehr6087 2 года назад
Perfect explanations my friend. Xie Xie
@electricalautomation
@electricalautomation 2 года назад
Glad you liked it Thanks!
@beckenbauer1974
@beckenbauer1974 9 месяцев назад
How can you read and write at the same time?
@electricalautomation
@electricalautomation 9 месяцев назад
Modbus read and write could use the same holding area. So you have to organize the read and write task.
@MrDannesboe
@MrDannesboe Год назад
This is an excellent video.! thank you.! Keep up the good work
@electricalautomation
@electricalautomation Год назад
Thanks, will do!
@rezamagham4495
@rezamagham4495 2 года назад
Perfect
@electricalautomation
@electricalautomation 2 года назад
Thanks! Welcome!
Далее
Это iPhone 16
00:52
Просмотров 416 тыс.
PORTAL SPAMMER🤬🤬🤬| Doge Gaming
00:19
Просмотров 683 тыс.
PLC S7-1200 Modbus RTU read data from power meter
1:26:22
What is Modbus and How does it Work?
8:58
Просмотров 1,7 млн
💢 S7 1200 As Modbus Tcp Client V4.1
22:42
Просмотров 138 тыс.
S7-1200 & Modbus TCP. Server & Client
29:27
Просмотров 4,5 тыс.
Siemens Simatic AX
8:47
Просмотров 10 тыс.
PLC S7-1200 Modbus TCP/IP all function code Part-1
1:10:18