It could not be compiled and warned that need to password for compile for Siemens side. I did exactly the same what you did but S7-1500, Tia Portal V16. Appreciate all your support.
When I download for V16, it is working. But it is for S71200. I did exactly the same like in video but for S71500. It could not be downloaded to plc. Need to compile but not possible without password
yes, this is the exactly the case shown in the video, S7-1200 runs as Profinet master to control the ET200SP, mean time communicates as Ethernet/IP device.
Hi , thanks for this tutorial, I am trying to use this method with S7-1517 and compctlogix, I can't establish the communication, the Valid status of the FB is always False the code is 7603, can any one advice, thanks in advance.
It most likely you missed some configuration, I would recommend reading the 109782315 manual carefully from the link support.industry.siemens.com/cs/document/109782315/ethernet-ip-adapter-connecting-third-party-control-systems-to-simatic-s7-controllers-via-ethernet-ip?dti=0&lc=en-DE
@@electricalautomation Hello, Thanks for your reply, I finally fixed the issue, I had to use move instruction to set the IP address for the remote device, that was not mentioned in the video or in the manual either, thanks for your help, much appreciated.
I believe you are asking the PRO V EIP (ETP is typo). To communicate it, your Siemens S7-1500 need to run as EIP scanner, pls refer to this video ru-vid.com/video/%D0%B2%D0%B8%D0%B4%D0%B5%D0%BE-zU5FYHFK5x4.htmlsi=Y043AaUqtazfLm_y
Micrologix doest support EtherNet/IP Scanner and Adapter. But if you can try to use ModbusTCP, Micrologix runs as Modbus TCP Server, Siemens runs as Client. ru-vid.com/video/%D0%B2%D0%B8%D0%B4%D0%B5%D0%BE-Pty8eB6NDe4.html. Please check if your Micrologix support Modbus TCP, old version doest support
I used it in couple of applications and was not get this password issue. Do not open this FB, just use it and compile at your project level instead of the FB inside.