Тёмный

ELECTRICAL BUSBAR SIZING 

The Electrical Solutions Channel
Подписаться 1,7 тыс.
Просмотров 13 тыс.
50% 1

An electrical bus bar is defined as a conductor or a group of conductor used for collecting electric power from the incoming feeders and distributing them to the outgoing feeders.
Busbars are generally made of Copper or Aluminium.
An undersized busbar will result in excessive heating of the busbar under normal operating condition, leading to rise of temperature beyond permissible limits.
While, an oversized busbar will lead to a costly switchboard.
Major factors affecting Busbar Sizing are
Voltage and Current rating of the system
Enclosure Ingress Protection rating
Forced ventilation or natural ventilation
Working and ambient temperatures
Heat loss by convection and radiation
Heat generated in the busbar
Busbar current rating is normally defined as below:
1. Continuous Current rating
2. Short-circuit Current rating
Continuous Current Rating is the amperes that a Busbar will carry continuously in free air without exceeding the temperature limits. Continuous Current rating is expressed in Amperes (A).
Whereas, Short-circuit current rating is the maximum current a busbar can safely withstand for a specified time (such as 1 second or 3 Seconds). Short-circuit current rating is expressed in kilo-amperes/Sec (kA/Sec).

Наука

Опубликовано:

 

20 мар 2022

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 31   
@tamjidkabir1543
@tamjidkabir1543 Год назад
I have watched all the tutorials in your channel. Great contribution to the engineering community. Highly appreciated...❤❤
@jhontejada5773
@jhontejada5773 Год назад
Very intelligent ; i cannot see this approach in my prevuous studies all things is new for me...good job man!!!
@uuday9093
@uuday9093 2 года назад
Very informative video with lucid explanation! 👍 Looking forward to more videos.
@theelectricalsolutionschan1095
@theelectricalsolutionschan1095 2 года назад
Glad you liked it!
@shavaizkhan8165
@shavaizkhan8165 Год назад
Please keep making such videos your videos are excellent
@theelectricalsolutionschan1095
Thank you, I will
@ramjiram4867
@ramjiram4867 Год назад
Very insightful informative video brother. Thank you very much.
@theelectricalsolutionschan1095
Thanks. Glad that you found the video useful. Please let me know your comments on my other videos. Please do subscribe to my channel and share with your friends.
@ganapathypv6587
@ganapathypv6587 2 года назад
Very well explained easy to calculate. Thanks🙏
@theelectricalsolutionschan1095
@theelectricalsolutionschan1095 2 года назад
Thanks. Glad that you found the video useful. Please let me know your comments on my other videos. Please do subscribe to my channel and share with your friends.
@MrPcwortex
@MrPcwortex 2 месяца назад
Great video. I'm trying to find information about the minimum distance between copper bars with different potentials depending on voltage. Maybe you know where I can find this information?
@prakashsatapathy1034
@prakashsatapathy1034 Год назад
Awesome. Please make a video on diesel generator sizing
@theelectricalsolutionschan1095
Thanks. Glad that you found the video useful. Please let me know your comments on my other videos. Please do subscribe to my channel and share with your friends. Videos on the above topic under preparation and will be uploaded shortly.
@rizalinotormis5447
@rizalinotormis5447 Год назад
i think coeffecient k1 is mistakenly calculated. if e=10mm and a=120mm then e/a=0.0833, therefore, k1 should be 1.76 or 1.8?
@theelectricalsolutionschan1095
Thanks. Yes, you are correct. The value of e/a has been erroneously calculated as 0.12 instead 0.08. Hence value of K1 will have to be changed accordingly. Glad that you found the video useful. Please let me know your comments on my other videos. Please do subscribe to my channel and share with your friends
@itachiiQuang
@itachiiQuang Год назад
Can your gave to me the document iec or ieee or evelent ? Pls help me
@theelectricalsolutionschan1095
Thanks for your comment. IEC & IEEE standard references are indicated in the video. These standards can be bought from various sources. However, copying and distribution is not allowed.
@ganesha_pandiyan247
@ganesha_pandiyan247 4 месяца назад
Hello Sir, is this busbar calculation applicable for HV traction battery's Cell to cell and module to module busbars??
@kittipotkaewnade5113
@kittipotkaewnade5113 Год назад
From the video, after calculation you use only continuous current to consider busbar size. What about short-time withstand current? Do we also need it to consider busbar size?
@theelectricalsolutionschan1095
Thanks for your comments. Once the busbar rating is decided (continuous and short circuit rating), the Continuous current rating is used for deciding the busbar cross-section. Glad that you found the video useful. Please let me know your comments on my other videos. Please do subscribe to my channel and share with your friends.
@mariomamani5692
@mariomamani5692 Год назад
What standar (ANSI or IEC ) is the base of Busbar Rating?
@theelectricalsolutionschan1095
Busbar rating is based on busbar property (Cross-section, No of parallel busbars, section profile, support spacing, etc.) and not on any particular standard.
@noname-ug2qx
@noname-ug2qx 2 года назад
Short circuit calculation upto the busbar is incorrect. Impedance of the incomer, transformer and cable should be considered. Other than that, the concept if informative.
@theelectricalsolutionschan1095
@theelectricalsolutionschan1095 2 года назад
Thanks for your comment. The Short Circuit calculation used in the example is a short cut one and neglects all impedances except transformer impedance. This will result in the maximum fault current that will be seen by the busbar as explained in the video.
@iroshanlahiru609
@iroshanlahiru609 2 года назад
Bus bar current capacity 630A , its according Thumb calculations suitable 50*10 , but standard chart show 50*5 Which is correct ?
@theelectricalsolutionschan1095
@theelectricalsolutionschan1095 2 года назад
Thumb rule calculation will give you a very high Busbar cross section as it based only on current density of the busbar material. But actual busbar sizing requires taking into account various other factors as explained in the video.
@josephansah5121
@josephansah5121 2 года назад
Does the length of bus bar determined current it will carry or the thickness of bar determine the current it will carry. Thank you
@theelectricalsolutionschan1095
@theelectricalsolutionschan1095 2 года назад
Thanks for your comment. No, Busbar length doesn't determine the current capacity. However, thickness of the busbar is one of the major factors which determines the current capacity.
@mandardahi
@mandardahi 2 года назад
Thanks for informative video. We refer K.C. Agrawal's book for busbar sizing in which skin and proximity effects, busbar supports also are taken into consideration. What is your take on this ?
@theelectricalsolutionschan1095
@theelectricalsolutionschan1095 2 года назад
Thanks for your comments. Skin effect and proximity effect do influence the busbar size. These effects basically increase the impedance of the conductor which in-turn reduces its current carrying capacity. Impacts of these effects are captured through the Conditions Co-efficients K1 & K3 in the MELSON and BOTH formula. Busbar supports design and distance between the supports are designed based on the short circuit rating of the busbar and not the other way around. Accordingly, once the Electrical rating is finalized, the supports and gap between can be designed (this is mostly carried out by the Panel manufacturers).
@mandardahi
@mandardahi 2 года назад
@@theelectricalsolutionschan1095 Thanks for the clarification
Далее
Busbar Comparison Guide
6:14
Просмотров 59 тыс.
HOW TO SIZE A CABLE !
17:27
Просмотров 3,6 тыс.
БИМ БАМ БУМ💥
00:14
Просмотров 3,6 млн
Best exercises to lose weight ! 😱
00:19
Просмотров 11 млн
Busbar sizing
9:27
Просмотров 128 тыс.
HOW TO SIZE A TRANSFORMER !
15:45
Просмотров 32 тыс.
HOW MANY AMPS CAN A COPPER WATER PIPE BUS BAR HANDLE
12:30
UNDERSTANDING ELECTRICAL LOAD SCHEDULE
12:47
Просмотров 11 тыс.
Harmonics
24:06
Просмотров 382 тыс.
Battery  low 🔋 🪫
0:10
Просмотров 13 млн