Hacks Installed Deadly Water Heater - Gas Valve Replacement - We SHUT IT DOWN! 

Mikey Pipes - Pipe Doctor Plumbing & Heating & Air
Подписаться 158 тыс.
Просмотров 37 тыс.
50% 1

Another handyman special right here folks. The people living in this house are very lucky the gas valve was defective cause this water heater would definitely been running! Hacks Bring Us Stacks! We shut it down!
⚠️Do not attempt to install this product if you are not qualified and/or trained working with gas equipment.⚠️
What’s in your Veto? Here is mine:
Veto TP-XXL amzn.to/3zX10vg
Milwaukee M18 Blower: amzn.to/46iTo6j
Milwaukee M12 Fuel 1/4" Impact Driver amzn.to/3I9yLfI
Milwaukee PVC cutter: amzn.to/3sbrdUc
Mini Waterproof Storage bin: amzn.to/3yfgsEv
Wiha Allen Keys: amzn.to/33ipGmb
HIKMICRO B20 amzn.to/33iGklx
Furnace Switch amzn.to/31X89PT
Milwaukee Light amzn.to/3I38Lmh
Wagos amzn.to/34QoiaU
Milwaukee Set amzn.to/33vnQOz
Torpedo Level amzn.to/3no1oOk
Crescent set amzn.to/3GtZeV8
Wiha 7 piece set amzn.to/3rkISaK
Milwaukee step bit amzn.to/3I395Bv
Flare wrench amzn.to/3noJZ8s
Ridgid 10” wrench amzn.to/3GvRnqa
Fluke non-contact tester amzn.to/31VQgAQ
Klein drivers amzn.to/3qoe21W
Knipex Wrenches amzn.to/3trzFjS
Klein 11-1 amzn.to/3tpsPLD
12” crescent amzn.to/3A0CZ6S
Gerber Gear Pocket Knife amzn.to/3foaW7I
Yellow Jacket Hand Ratchet amzn.to/3nrDgup
I am on Discord & WhatsApp!
Discord: / discord
WhatsApp Group: chat.whatsapp.com/CHZWtZe4KMG...
Mikey Pipes Uncensored: / @mikeypipesuncensored
New oval raised silver stickers are from:
Armored Decal Company Inc.
35 Victoria St. E, Unit 9
Alliston, Ontario L9R 1T3
(p) 705-435-6665
(e) ken@armoreddecal.com
(Tell them Mikey Pipes sent you)
Please support this channel and Mikey Pipes and consider the following…
Pipe Doctor FlexFit Embroidered Caps
Minimum donation of $37 is appreciated
(If you are international - please add a minimum of $40 for shipping/postage)
Shopping on Amazon? Please use my referral link amzn.to/2PjjS4v
Sticker Requests:
Do you want a sticker to show your support of this channel? Email your request to me! mike@mikeypipes.com
Name
Address
City, State, Zip
Consider making a donation of $5.00, or ANY amount, to the postage fund! I literally mail out stickers all over the globe. I've sent stickers to HVAC guys in Afghanistan, New Zealand & all over Europe.
PayPal is: office@pipedoc.net
Venmo: @PipeDoctor
CashApp: $mikeypipesny
Want to send a love letter, note or gift? Our mailing address is:
Mikey Pipes
C/O Pipe Doctor Plumbing
80 E Hawthorne Ave
Valley Stream, NY 11580
#localplumber #waterheater #MikeyPipes

Хобби

Опубликовано:

 

6 авг 2023

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 122   
@davonmaye3123
@davonmaye3123 11 месяцев назад
Nicely done, Mike! One of the few people I actually see replace the gas control valve the way I do, without draining the whole water heater. Just make sure your new valve is directly next to you, then rock and roll.
@drakbar5957
@drakbar5957 11 месяцев назад
A lot of fossil fuel devouring units in that small space. Even a CO detector won’t save you from the downhill vent into the chimney. Mikey Pipes went with Door #1 and prevented his client from getting zonked!
@mattl643
@mattl643 11 месяцев назад
Mikey Pipes....provides quality service and saves a few lives while he's at it. Job well done boys.
@Chris2745100
@Chris2745100 11 месяцев назад
Some parts of the country are so hot right now you really don't need a water heater. Phoenix, Dallas, Houston to name a few places.
@PlumbThumbs
@PlumbThumbs 11 месяцев назад
Keep it up Mikey. Way to keep the public safe!
@armandomadrigal9793
@armandomadrigal9793 11 месяцев назад
MUY BIEN !!!, you sir are a PRO fessional thru and thru
@Hvachack97
@Hvachack97 11 месяцев назад
That bracelet looks really pretty
@Hvac-dude
@Hvac-dude 11 месяцев назад
Great job guys 😊😊😊😊
@bountiful420
@bountiful420 11 месяцев назад
Great stuff !
@jackpfeffer4213
@jackpfeffer4213 11 месяцев назад
Total hack install i shut one down just like that last week
@jackpfeffer4213
@jackpfeffer4213 11 месяцев назад
@@PipeDoctor you got that right its kinda scary really how little people care about others safety
@drwhoeric
@drwhoeric 11 месяцев назад
Was surprised that you had doubts about the Gas Valve being bad. Seems tens of thousands if not hundreds of thousands of Rheem Water Heaters were manufactured with defective gas valves. Most of the defective Gas Valves were manufactured around year 2021. Some failed immediately, others failed shortly to a year after.
@tphvac87
@tphvac87 11 месяцев назад
I’ve found one vented in buctduct shut it down, disconnected the gas and wiring from gas valve to, said a friend of the family did it! 🤦‍♂️ He’s no friend sir
@kellybrown2314
@kellybrown2314 11 месяцев назад
gas line to water heater should have a drip leg before the gas valve on the water heater.
@MyberTube
@MyberTube 11 месяцев назад
---- getting a new Lochinvar Knight combi installed in a couple weeks ---- good bye old oil fired Weil Mclain --- stoked!!
@eddiew.6485
@eddiew.6485 11 месяцев назад
That guy bought the water heater from a “friend”, then drove by the Depot, flagged down a Chuck with a Truck who could install a water heater, and Presto, ala peanut butter sandwich!
@REWYRED
@REWYRED 11 месяцев назад
The sad thing is the homeowner or whoever did that install will have that thing connected back up and making hot water before the sun sets .... At least you have video evidence and a shit ton of witnesses that show you leaving the unit in a safe, non functional state. If anything happens you can easily say "Lookie see, it wasnt me!"
@gas_man1565
@gas_man1565 11 месяцев назад
dont you guys in America have tags your local gas utility company gets notified on what happens at a home. in Ontario at least everything is sent in to our local gas utility company and gets handled from there. if its not fixed withn 30 days the gas supply to the house gets turned off until the infracton has been resolved!!
@TheBigbass13
@TheBigbass13 11 месяцев назад
flue pipe isnt even screwed together! Red tag!
@jasonthewiczman5442
@jasonthewiczman5442 10 месяцев назад
Never safe - it's why your here - safety!
@ricklee827
@ricklee827 11 месяцев назад
Some more food for thought I got stuck by in a Rheem hot water tank from Home Depot because of the size issue 3 days later it wasn't working the parts were not available I remove the tank and reinstalled the new one and Rheem gave me a hell of a labor reimbursement
@ricklee827
@ricklee827 11 месяцев назад
​@@PipeDoctorI work directly with the Rheem hot water tank company on this situation and got 50 bucks out of Home Depot
@carmencompoli5993
@carmencompoli5993 10 месяцев назад
I noticed the flex gas line to hot water heater had no drip leg to it .we normally make sure furnaces and water heaters have them installed.
@nikets0
@nikets0 8 месяцев назад
sediment trap, yes you should
@johngraves2968
@johngraves2968 11 месяцев назад
ADD, most flex states on it, single use only, so new flex line needed.
@Chris_In_Texas
@Chris_In_Texas 11 месяцев назад
Good catch on all the bad things with the install. I have always heard bad things about Honeywell gas valves, to stay away from them. Why did they put a pan with the outlet not connected to anything, pretty stupid! 🤦‍♂🤷‍♂
@davidbrinkmeyer5850
@davidbrinkmeyer5850 11 месяцев назад
Where’s the tee for a gas drip? T & P relief valve pipe NOT w/I 6” of the floor. CODE VIOLATIONS!
@methodical
@methodical 11 месяцев назад
In my area, and lots of others, the drain pans are required to be metal when used with gas heaters...
@throttlebottle5906
@throttlebottle5906 11 месяцев назад
yes, they really should be metal for gas appliance.
@01Hokiefan
@01Hokiefan 11 месяцев назад
That was a homeowner Home Depot special. All parts and supplies are from Home Depot which is fine just do it right. What is the point of a pan when it isn’t piped into a drain.
@markh.6687
@markh.6687 11 месяцев назад
If you have a minor leak, you might catch it in the pan before it damages anything else.
@markh.6687
@markh.6687 11 месяцев назад
@@PipeDoctor The Sarcasm is strong with this one.
@01Hokiefan
@01Hokiefan 11 месяцев назад
@@markh.6687 Not if the pan is not capped. Well I guess it will hold a little water before it runs out the hole.
@markh.6687
@markh.6687 11 месяцев назад
@@01Hokiefan This is true.
@ATSNorthernMI
@ATSNorthernMI 11 месяцев назад
Could this water heater be outfitted with a power vent and vented with PVC or do you have to order a water heater with a power vent attachment?
@undaya
@undaya 11 месяцев назад
smaller vent to be above or below the larger?
@MrSmooth302
@MrSmooth302 11 месяцев назад
Should be a minimum of 6” clearance between the boiler exhaust and the water heater exhaust to reduce the boiler causing back pressure on the water heater when both are running. Also higher btu equipment should always be the lowest exhaust than work your way up from there which they did do that correctly lol
@throttlebottle5906
@throttlebottle5906 11 месяцев назад
it's probably been that way for 50+ years with a shorter tank, them putting in a tall unit is one issue, flue pipe is technically the wrong size, ugly smashed and restricted looking. codes usually don't force you to change the size on replacement of appliance only(they may there), but if the chimney/breach is having anything done or the flue is rotted away, then yes it has to be changed. if the pipe wasn't so forked up, I'd say jam in a short tank and show them tail lights.
@cody5495
@cody5495 9 месяцев назад
I looked up the flue sizing table in the code book... the flue vent diameter is sized on the height and btu.. looks like 3 inch is legal in this case.. am I wrong?
@Matts_Crafty
@Matts_Crafty 11 месяцев назад
Mike dumb question... is it legal to tap the water into the boiler exhaust? I see that a lot out here in cali with water heaters being tapped into gas furnaces exhausts just curious? I'm guessing no due to probably substantial exhaust pressure differences between the water heater and boiler...
@ltsiver
@ltsiver 11 месяцев назад
What is with all these gas venting to chimneys with exhaust gas traps?
@noahholt482
@noahholt482 11 месяцев назад
Was that kevs wrench ?
@walterbordett2023
@walterbordett2023 11 месяцев назад
If the 40,000 BTU water heater requires a 4 inch flue pipe, why does the included diverter accept 3 inch or 4 inch pipe? The down pitch is an obvious fail. Can you discuss when you need a stainless liner and when the terra cotta flue tiles are OK?
@randyblackburn9765
@randyblackburn9765 11 месяцев назад
What did you do about the up hill 3 inch vent ?
@user-rg7vy7xv6h
@user-rg7vy7xv6h 11 месяцев назад
You didn't get water in the pilot tube when you unscrewed the control did you ? You should have bent it to the side .
@everettstevenson2111
@everettstevenson2111 11 месяцев назад
Hey Mikey, like it says on the back of the US one dollar bill ? I got my eye on you again.
@stephenzies8867
@stephenzies8867 11 месяцев назад
Pipe Doctor Mike D. And Peter Saved Another Life Or Lives In That Home Today. 👋 👍
@ItsTheCostanza
@ItsTheCostanza 11 месяцев назад
Customer states: I knew a guy who did it cheaper for me
@ItsTheCostanza
@ItsTheCostanza 11 месяцев назад
@@PipeDoctor absolutely.
@tphvac87
@tphvac87 11 месяцев назад
@@PipeDoctorfamous last words with that water heater
@brianbushay8283
@brianbushay8283 11 месяцев назад
You missed that the flexible riser on the right is plastic under that branded SS and can not be within 18" of the top of the water heater and within 6" of the flue
@brianbushay8283
@brianbushay8283 11 месяцев назад
Maybe if you do not change it out when you replace the water heater but that is not anywhere near immediate. where local codes allow it most water heaters are installed with it
@davep153
@davep153 11 месяцев назад
I see mentioned about the bad gas valves. Would quality be horrible because of COVID shutdowns around production and shipping products worldwide? No quality control, bad parts from other places etc etc? Just asking if recalls for those models?
@MassEffectFVR
@MassEffectFVR 9 месяцев назад
The Home Depot special .. vent is undersized, no liner, using an appliance connector, no drip leg, room probably has insufficient combustion air and likely no fitter's tag .. Mikey pipes I'm surprised you still went forward with the gas valve replacement I would have just shut her down and left an "A" tag and got the home owner to convert to a power vent direct vent
@PipeDoctor
@PipeDoctor 9 месяцев назад
Well, you know what they say - the show must go on! Sometimes you just have to work with what you've got and make the best of it. But I'll definitely keep your suggestions in mind for future projects!
@user-cb3um9yc6x
@user-cb3um9yc6x 5 месяцев назад
Also i see plastic pan for gas water heater illegal in Va. not sure in your location
@JimmydaGooch
@JimmydaGooch 11 месяцев назад
Question, could you just put 6x6x4 Y or T fitting in there where it enters the chimney?
@williamloder9194
@williamloder9194 11 месяцев назад
The 6 x 6 x 4 wye would be to low to pick up water heater vent. Go install an electric water heater
@jfarm_1311
@jfarm_1311 11 месяцев назад
We had a home warranty company install our water heater and piped it with a down slope as well. Sad
@jfarm_1311
@jfarm_1311 11 месяцев назад
@@PipeDoctor too late now. They fixed it while I was at work and charged heftily for it 🤬. Wife of course paid them. It’s a long story
@pendragon4964
@pendragon4964 10 месяцев назад
no dirt pocket
@PipeDoctor
@PipeDoctor 10 месяцев назад
No drip leg.
@jonwillis9075
@jonwillis9075 11 месяцев назад
Hacks bringing you (and Peter) the stacks. Plastic shank, good grief....Home Depot, right?
@fatcat-hc4pj
@fatcat-hc4pj 11 месяцев назад
👍👍
@davidriccitiello6421
@davidriccitiello6421 11 месяцев назад
Mike, some homeowners think a cheap cash only install is the best. What they miss is that all those faces on those cash bills are dead. I guess that homeowner was looking to join them. I like it when you point out the hackery.
@MalleusSemperVictor
@MalleusSemperVictor 11 месяцев назад
I am a home owner and I installed my own water heater when ours took a crap. Even I installed it better than this.
@xlostf8x348
@xlostf8x348 11 месяцев назад
NCI Combustion class is a good training to pay for. Scared the F out of me.,
@williamloder9194
@williamloder9194 11 месяцев назад
Homeowners never learn. I was in Home Depot a few years ago. I was in the plumbing isle and witnessed a young couple looking at 4 in venting material for a gas water heater they were installing. One problem was they were looking to buy the venting made for dryers. They obviously didn't know what they were doing. Not sure why they bothered installing a waterheater pan with nowhere to drain
@MosheKatz
@MosheKatz 11 месяцев назад
There is one possible reason to put a pan without a drain - you can put an alarm-connected water sensor in the pan and give a little extra time to react to a leak before the water is all over the floor. You just need to have a cap on the pan's drain outlet.
@ATSNorthernMI
@ATSNorthernMI 11 месяцев назад
@@MosheKatz Just drill a hole in the floor and let it drain into the crawl space. I am bad for not finishing the drain pain install. Mine has never been hooked up and I figure that the tank will rust out in about 7 to 10 years and when i'm done procrastinating, I will eventually install the piping to the pan. Most likely, the tank will fail and my house will be flooded and then I will make it a priority for next time.
@ATSNorthernMI
@ATSNorthernMI 11 месяцев назад
@@PipeDoctor If it wasn't for home depot, I would have been living in a car. I would have bought a furnace from them if it was available. Even my employer at one time sold direct comfort and then stopped. I ended up ordering it through alpine and wanted to have a local company install it but they wouldn't touch direct comfort and said they are only sold online and are dangerous junk. Then quoted me some insane amount of money to install a new unit so I ended up reading the installation manual(lots and lots of pages that tells you everything you need to know) and installed it myself in 2020 and its been keeping me warm every winter ever since. I also have CO detectors all over my house with wifi so I get an alert on my phone if i'm not home.
@MosheKatz
@MosheKatz 11 месяцев назад
​@@ATSNorthernMI You're forgetting about houses with concrete floors on the lowest level - quite common in a large part of the country. For example, in Maryland, you'll often see a water heater (and other equipment, such as HVAC) in an unfinished part of the basement, right next to other rooms which are finished. Water leaking onto the floor will ruin the flooring of the finished space, so catching the leak and alerting about it is very important. (I don't know why builders don't put floor drains in these mechanical spaces, but it's pretty common that they don't.)
@ATSNorthernMI
@ATSNorthernMI 11 месяцев назад
@@MosheKatz In those situations, it is good to drain into the sump pump area or install a leak detector. I have a simple company called mocreo sensor that allows me to monitor multiple grow rooms for humidity and temp to having leak detectors on their A/C or any other system to detect a leak in real time to alert my phone and even shut the system down if its an A/C if needed.
@ricklee827
@ricklee827 11 месяцев назад
How about the relief valve drip leg not sure what material it was but it needs to be 6 in above the floor. Watching them video again it looks like it was black iron that is a very bad thing
@ricklee827
@ricklee827 11 месяцев назад
First of all I highly respect you but having a thread on the end of the pipe does not have anything to do with my comment about the drip leg being black iron and or not six inches off the floor Plum on brother
@ricklee827
@ricklee827 11 месяцев назад
​@@PipeDoctorI looked at it again it's galvanized correct me if I'm wrong so the material it's okay it's just higher off the floor where I am as per code
@imchris5000
@imchris5000 11 месяцев назад
hey I got a question so I got a rheem powervent water heater well every few months I have to take the burner and wipe off white soot from the flame sensor. what would cause natural gas to produce white soot?
@throttlebottle5906
@throttlebottle5906 11 месяцев назад
also, contaminates in the air being used for combustion or lack of air/exhaust backpressure. if you use lots of cleaners, bleach, sprays, etc. in the house/basement anywhere near it could be causing it. basement walls leaching in bad gasses? water leaks/very high humidity? that's where coaxial vented models are nice, using outdoor air, well until people put a pool nearby or do other stupid things around the vents. 🤣
@kens.3729
@kens.3729 11 месяцев назад
Hacks bring you Stacks but this Hack could have Killed their Customer. This Company needs to be Called Out for doing Unlawful Installation Practices. 🤪👎
@kens.3729
@kens.3729 11 месяцев назад
RHEEM Brand Water Heaters are a BIG Seller at the Big Orange Store. 🤪👎
@robertanderson7115
@robertanderson7115 10 месяцев назад
Drip leg is missing
@timfife2128
@timfife2128 11 месяцев назад
Where’s the dirt leg
@TheMartyheredia
@TheMartyheredia 11 месяцев назад
Wouldn't the manufacturer supply a 4" draft devirter? It didn't look like the old draft devirter. I did years of warranty repairs on w/h. If one was not installed as per manufacturers instructions, it would void the warranty.
@noahholt482
@noahholt482 11 месяцев назад
I wondered that to but with local codes I’m sure they can’t keep up
@rcmechanialgroup2856
@rcmechanialgroup2856 11 месяцев назад
The diverter fits for 3" and 4"
@JOHNPHUFNAGEL
@JOHNPHUFNAGEL 11 месяцев назад
what stops the customer from turning everything back on?
@markh.6687
@markh.6687 11 месяцев назад
If they can run the water heater without the gas line, I'd like to see it.
@cheeseman9967
@cheeseman9967 11 месяцев назад
Nothing...
@markh.6687
@markh.6687 11 месяцев назад
@@PipeDoctor Here's an idea (not sure if it's legal under plumbing or gas codes however). If a licensed person red tags and shuts down a natural gas or propane appliance, they also use Permatex orange thread locker (no heat required to remove, but stronger than blue thread locker) on the gas supply pipe cap to show they tried to keep the owner/user from hooking up again)? Of course, cellphone photo or video would be another measure taken.
@everettstevenson2111
@everettstevenson2111 11 месяцев назад
Apollo 13 flight control, do we have a go or no go, copy? Mikey we still on VOX or Baby Vox again, copy ?.
@gas_man1565
@gas_man1565 11 месяцев назад
2 things with the gas piping that really concerned me. 1. the 1/2" npt should have a drip leg (drip pocket) 2. the gas pipe should be supported., which it was not. the venting is a whole different story!! wow the person who installed it should get their licenses taken away from them, im kinda hinting that most likely the home owner or someone he knows did the work!! no gas Licenses pro would ever do that. I would also turn their gas boiler off due to the chimney being in that shape!! Very Scary!! job needs either 5' or 6" common vent. 4 inch vent for water heater and what ever size the draft hood off the boiler is!!!
@Craigcul
@Craigcul 11 месяцев назад
You may find that they will just put another gas pipe in there and continue to use the heater as is maybe the local gas company should have been informed as well about the hazard.
@Craigcul
@Craigcul 10 месяцев назад
OK, i see now you have proof that you disconnected the system so if they reconnect it and something happens it is not on you.@@PipeDoctor
@thardie
@thardie 11 месяцев назад
Next time, make sure you block the barcode too - I was able to get all that guy's personal information from the barcode.
@scottmaz4063
@scottmaz4063 11 месяцев назад
#1
@everettstevenson2111
@everettstevenson2111 11 месяцев назад
@@PipeDoctor optimus prime, autobots, transform.
@renenunez1254
@renenunez1254 11 месяцев назад
So it was the gas control after all. Then you proceeded to install it knowing that you were going to tear down his setup. Looks like the Pipe Doctor is actually the Pipe Police and yes you feel good for protecting the Pipe Doctor and Rheem from liability and finally the client. Peter, however, appears doubtful. The sad thing is that local code enforcement passed the installation. The poor guy got screwed all the way around.
@noahholt482
@noahholt482 11 месяцев назад
How do you know they passed it ?
@renenunez1254
@renenunez1254 11 месяцев назад
@@noahholt482 Because a different Pipe Police signed off on the permit. Pipe Police galore...
@christopherchance4860
@christopherchance4860 11 месяцев назад
where did you gat the idea that passed?
@GnarlsDarwin
@GnarlsDarwin 11 месяцев назад
Riddle me this: Who reports you when you choose; To make a youtube; Of shoddy run pipes; charged at full price; you know this ain’t news…it’s the…
@scottmaz4063
@scottmaz4063 11 месяцев назад
Everything there illegal
@scottmaz4063
@scottmaz4063 11 месяцев назад
They will hook it back up after you leave.
@everettstevenson2111
@everettstevenson2111 11 месяцев назад
Hey Mikey, of Mikey Pipes Plumbing not easy being cheesy. I like your podcast/social media, looking thru some comments/reply. That would have been a $10,000 project to correct those problems with the gas fired hwh. That gas might have locked itself out, a lot of short cycling, because of flue gas flow in the flue piping? I know a few dead homeowners, do you? Love you buddy, might sound a little queer again. lol.
@everettstevenson2111
@everettstevenson2111 11 месяцев назад
the gas valve might have lock itself out, because of all the short cycling, unquote.
@everettstevenson2111
@everettstevenson2111 11 месяцев назад
@@PipeDoctor No, I have not Mikey, it is hard to believe you are going to the scrap yard every week too.
@terrybrennan4978
@terrybrennan4978 11 месяцев назад
3 inch on the downward slope.... What could possibly go wrong?? 🤦🏼🤦🏼🤦🏼🤦🏼 More dangerous than smoke.
@mrharry8466
@mrharry8466 11 месяцев назад
That is a rocky mistake. Come on any professional should know flue requirements.
@westsidehvac1097
@westsidehvac1097 2 месяца назад
Your so posee to push button in to light . Changes control but not vent pipe.
@Hvac-dude
@Hvac-dude 11 месяцев назад
I don't think home depot lowes should be able to sale and plumbing supplies becuase of that reason agian amazing job guys well done😊😊
@Jeff-xy7fv
@Jeff-xy7fv 11 месяцев назад
They shouldn't be able to sell breaker panels and electrical wire to unlicensed people either. Only licensed electricians should be able to buy them.
@weber247
@weber247 11 месяцев назад
Oy vey!
@handymanbrian8269
@handymanbrian8269 11 месяцев назад
im not one for over-regulation....but, water heaters should be sold to contractors only (at least ones with a business license & insurance)
@throttlebottle5906
@throttlebottle5906 11 месяцев назад
black market issues, they'd start falling off the back of trucks and floating out of warehouses everywhere. 🤣 as if they don't grow legs and walk out of stores as is.
@handymanbrian8269
@handymanbrian8269 11 месяцев назад
@@throttlebottle5906 well the reason they cost so much (i used to pay $140 for a 40 gallon gas WH) is because of the insurance that the manufacturer adds
Далее
Спецэффекты в Симс 4
00:36
Просмотров 210 тыс.
Which national team are you rooting for at Euro 2024?
00:17
Вопрос Ребром: Сергей Бурунов 2
1:03:47
Water Heater Leaking At Relief Valve Diagnose / Fix
15:29
30 Minute Secret Makes Your Water Heater Last Decades
13:03