How to Adjust a TXV, TEV or TX Valve 

HVAC School
Подписаться 351 тыс.
Просмотров 104 тыс.
50% 1

Bryan does an in-depth review of how to adjust a thermostatic expansion valve, also known as a TXV, TEV, or TX Valve. He explains why one would adjust a TXV and how to tell if a TXV is working.
You almost never need to adjust a TXV unless you're trying to prevent floodback or fixing a TXV that was adjusted by someone else. Adjustments should be very slow, and it's unwise to do an adjustment without a valid reason to do so.
The TXV has a few different sources of force. The bulb exerts an opening force according to the temperature of the suction line, as the TXV tries to maintain a constant superheat. So, the bulb needs to be mounted to the suction line sufficiently, and the powerhead needs to maintain enough refrigerant charge. (Some powerheads are replaceable, and others are not.) The internal or external equalizer also applies a closing force to counter the opening force. Spring force also exerts a closing force to assist the equalizer's closing force.
For a TXV to work properly, it needs to have a full line of liquid going into it. Therefore, you need to make sure that you have sufficient subcooling or a full sight glass. Before condemning or adjusting a "bad TXV," be sure to check your superheat with probes or clamps to ensure that you don't have a different problem. (It's also worth mentioning that evaporator and compressor superheat can vary quite wildly, especially if the suction line is very long.) TXVs also don't set superheat at a fixed temperature; there is a range based on load conditions. You also don't want to adjust the valve so that it's too far open, as that can cause floodback.
We have to adjust TXVs based on evaporator superheat, and the bulb should be insulated and well strapped to the top or side of the suction line. When you're ready to adjust the TXV, remove the stem cap on the bottom to expose the spindle.
It's easy to make the adjustment if you make a mark at the edge of the spindle. That way, you can keep track of how many turns you make. Many manufacturers recommend turning the spindle only a quarter-turn at a time. Turning the spindle clockwise compresses the spring, which allows less refrigerant to enter the evaporator coil and increases the superheat. Turning the spindle counterclockwise has the opposite effect (less closing force).
Balanced port TXVs help balance the inlet pressure; refrigerant flowing in through the inlet of the valve also affects the valve, and the balanced port tries to prevent it from having as much of an impact. Balanced port TXVs make the operation more stable over a wide range of load conditions.
Hard shutoff or non-bleed TXVs shut when the system turns off. These TXVs are a bit more likely to require a hard start kit in single-phase residential applications.
Read all the tech tips, take the quizzes, and find our handy calculators at www.hvacrschool.com/

Опубликовано:

 

9 ноя 2019

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 56   
@benh2156
@benh2156 4 года назад
How many cranks to get to the center of a TXV-pop Brian? Ohoone, t-whoooo, thr-heee, *owl crunches the powerhead* Edit: Had to, also great video.
@BernadosJoselito
@BernadosJoselito 4 года назад
how i need to buy
@eatcommies1375
@eatcommies1375 4 года назад
Just a quick heads up on using a marker to mark txv position, if there is moisture on the valve, ink might rub off during adjustments, I try to scribe on it instead, (learned this the hard way) also leave the brass cap in the visible area so you don’t forget to put it back on:).Another Good Video! Thank You!
@Val-xi4we
@Val-xi4we 3 года назад
Thank you for updating this!! The video in your previous one was giving me a headache!!
@kylekisebach3966
@kylekisebach3966 4 года назад
Great video, nice graphics and pace. Thank you!
@HVACS
@HVACS 3 года назад
You're welcome!
@happyhappysheep
@happyhappysheep Год назад
Thank you very much for this video. This is very educational, very detailed useful information.
@drair-kp3cx
@drair-kp3cx 4 года назад
Excellent video. Question: Why do some manufacturers (eg. Goodman) recommend adjusting SH in Stage 1 (not 2) to 6 degrees on the compressor side? After watching your video, this seems wrong (or are they using their own parameters?).
@janibashamolla
@janibashamolla 4 года назад
Thanks a lot sir....for good information about TXV...
@grashoprsmith
@grashoprsmith 4 года назад
Great video! If the spindle cap was left off, would that affect operation in any way?
@jhondjirlay9297
@jhondjirlay9297 3 года назад
Thanks for your explanation
@mithileshramteke3882
@mithileshramteke3882 3 года назад
Thank you for very very nice explanation HVAC school
@joseg6073
@joseg6073 4 года назад
Grat video sr. Great tools to thank
@mohammadabdulfattah1867
@mohammadabdulfattah1867 4 года назад
Thank you bro ,really very good explanation 🌹👍
@HVACS
@HVACS 3 года назад
Welcome 👍
@emsathebest
@emsathebest Год назад
Hi. Great video and explanation but can you make a video or quick explanation how the txv works in heating mode. Does it allows revers flow and if it does not how the refregirent flows in the other way? Thank you!
@robert574
@robert574 5 месяцев назад
Thanks for the video. Hope you're still reading the comments. So a question, when you use a larger inside coil (say 3 ton compressor single speed and 4 ton inside coil) do you move the txv bulb down on the coil to lower position where it should be flooded properly? Seems like the compressor would not be able to provide enough liquid for the larger coil, at least for the txv to work properly and not hunt. I see the use of larger coils is common now. Of course, the remaining, say 1/4 of the evaporator above that point would still continue to make heat transfer and of course that would affect the superheat right? How are they making it all work. Any thoughts? Cheers.
@t006
@t006 Год назад
Awesome video it helps a lot …. Thanks a lot
@Kevin-ib4gv
@Kevin-ib4gv 4 года назад
Think of the handle on your water faucet at home. Turning on the water (counter clockwise), allows more water (refrigerant) to flow. More refrigerant flow equals more evaporator cooling and less superheat (cooler). Too little superheat? Turn the "handle" clockwise just like at the faucet, making less refrigerant flow, warming up the coil, and increasing the superheat (warmer). Half a turn at a time and wait 15 to 20 minutes between turns to stabilize.
@001prk
@001prk 4 года назад
hi, could you please make a video on loading and unloading mechanism and its troubleshooting? And how external equalizer work fitted in TEV
@MuhammadAfzal-hn3nx
@MuhammadAfzal-hn3nx 4 года назад
hello hope you ding fine sir its a very good video did these adjustments effect on discharge tep ???
@MuhammadAfzal-hn3nx
@MuhammadAfzal-hn3nx 4 года назад
temp *
@janeilquino2599
@janeilquino2599 3 года назад
Sir.good day.what is the correct adjustment txv low superheat or high superheat.thanks and god bless
@vahagnmelikyan2906
@vahagnmelikyan2906 2 года назад
I'm trying to do diy air conditioning, so do I connect low pressure line to equalizer. How do I add refrigerant if low side is attached to equalizer?
@moinuddinsa6177
@moinuddinsa6177 3 года назад
Where should clamp the sensing bulb exactly in suction line in which position?
@Keegeth
@Keegeth 2 года назад
What’s it mean when the sh and subcool keep fluctuating in sync. So in a span of 10 sec the sc will be 15 then goes down to 3 then after about 2 seconds of being on 2 it goes back up repeatedly up down up down. Is that a charge problem or is something going on with the compressor itself
@mdshahir4022
@mdshahir4022 11 месяцев назад
Very nice
@vahagnmelikyan2906
@vahagnmelikyan2906 2 года назад
Do I have to use the equalizer? Or just ignore that line?
@bisayanghvactechlifetv
@bisayanghvactechlifetv 3 года назад
Hello master.. I just ask about the external equalizer.where is should be the standard location after sensing bulb or before sensing bulb?
@Waymanator123
@Waymanator123 7 месяцев назад
Before
@7x779
@7x779 Год назад
What about TXV valves that have a circlip on the spindle so the actual spindle is not screwing in or out, it would apparently be threaded onto something inside in which case screwing it in May lift the spring retainer up and reduce tension on it. I can't see the brand because it's burned off from somebody who replaced it before, but it's not opening enough want to make sure I'm going the right direction. But definitely the stem does not move in or out as you turn it, so it's obviously only moving something inside of the body, but you cannot tell which direction
@rexhansen2766
@rexhansen2766 4 года назад
What effect will adjusting the TXV valve have on the high pressure side compressor if any?
@u2ooberboober
@u2ooberboober 3 года назад
Increase or decrease refrigerant density resulting in higher or lower head pressure.
@jimmitchell3441
@jimmitchell3441 2 года назад
can you talk sometime about water source heat pumps
@mukeshlutchman4988
@mukeshlutchman4988 4 года назад
Hello Bryan my teacher says that TXV valve can go 10% + or - . So if a valve is 20 Ton by adjusting the superheat it can be used on a 22 ton or 18 ton is that correct
@DJV94022
@DJV94022 4 месяца назад
I did one today lennox .and it was adjustable it said on the box that it was for 1.5ton to 2.5,ton now my unit was 2.5ton the screw out of factory was all closed so im assuming it was for the lowest ton my suction line was just being stuck in 48psi..i cranked it all loose and it went to 101psi which is good down here in florida for heatpump on r410a
@mansourghadhban236
@mansourghadhban236 Год назад
Good job 👍 more
@arana770ify
@arana770ify 3 года назад
Thanks so much
@HVACS
@HVACS 3 года назад
You're welcome!
@jhesiquio
@jhesiquio 4 года назад
DFWI if you know you know 🤙🏻
@DJV94022
@DJV94022 4 месяца назад
Adjustable txv is equivalent to an adjustable fuel pressure regulator in the car world Too much psi means high fuel pressure meaning too much gas being dumped cleaning out your gas tank too fast or blowing fuel line seals/gaskets Too less of fuel pressure can damage your engine due to fuel starvation and spark only being present in the chamber causing damage melting piston
@j727100
@j727100 4 года назад
Why does the Goodman txv charging instructions on the inside of service panel tell you to adjust the txv to find 7°-9° superheat then charge to your subcool?
@drair-kp3cx
@drair-kp3cx 4 года назад
I have the same concern. Just installed a Goodman 3-ton 18 SEER, two-stage, ECMs-all-around, split system heat pump. Instructions (in both the service panel and condenser manual) clearly say to adjust SC and SH in different orders (whereas the video insists on always adjusting SC first). Worse, Goodman also says to adjust SC and SH in Stage 1 (which means low inside air flow, etc). I have not yet found an HVAC guy who could give me some reasonable explanation (and Goodman won't talk to me).
@j727100
@j727100 4 года назад
@@drair-kp3cx yeah sounds backward. Only reason I can think to charge to sc and sh in 1st stage is so the unit is not overcharged when in 1stage but then it will be undercharged in 2nd stage. I would think. Sometimes I have to charge to a lower sc in order to match the sh to manufacturers specifications on some units. Pistons are less complicated to charge as long as you get your target sh correct.
@u2ooberboober
@u2ooberboober 3 года назад
To ensure there is at least enough liquid at the txv high side to promote proper txv operation then dial in the subcooling.
@WilliamMcCormickJr
@WilliamMcCormickJr 2 года назад
@@drair-kp3cx I have installed a few of those Goodman systems and get the subcooling set in 2md stage and everything else works out nicely. I have never adjusted a TXV valve ever. And I doubt I will unless I truly believe someone else messed with it. I worked with an old-timer that would have thrown me off the roof if I messed with a TXV valve. I live on an island and we get a lot of humidity and if we do not lower fan speed the unit upon startup can pull tremendous amperage, and have all kinds of subcooling and superheat issues as well as throw water onto the EMC blower motor. It will not dehumidify or cool properly so we lower fan speed and raise the temperature differential between supply and return and we get excellent dehumidification and cooling. And we maintain a low compression ratio. If you mess with the TXV valve you can starve the evaporator after the house cools down and dries out. This also tends to raise the compression ratio so it is taboo where I live. I do not install in areas where there is no condensate created so I cannot say for sure but I suspect even there you should not mess with the TXV valve. There you would raise the fan speed.
@baldevbhambhariya1061
@baldevbhambhariya1061 10 месяцев назад
Nice
@bryanromero6278
@bryanromero6278 Год назад
what causes an evaporator coil not to be equally cool..? just the bottom half is cold the top half is warm
@mdshahir4022
@mdshahir4022 11 месяцев назад
@mulahtime427
@mulahtime427 4 года назад
👌🏾
@TiesiogJazokas
@TiesiogJazokas Год назад
Soooo then refrig.. tube freezing after TXV so where is the problem?
@ganeshmishra1917
@ganeshmishra1917 3 года назад
👌
@DJV94022
@DJV94022 4 месяца назад
Yeah but lennox factory workers will have you dumping 4-5lb of r410a thinking . 1.the factory workers only added 1lb of r410a to the heat pump 2.youd think when you ask for a warranty indoor txv they send you the same one but they send you a shut screw adj txv .. But we all good now the 3lbs was needed anyways to raise the subcool to spec
@MR-nl8xr
@MR-nl8xr 4 года назад
You used the wrong symbol for less than, again.
@seek3n
@seek3n 10 месяцев назад
Do not try this on oem txv 😂 you'll get a surprise
@wasimedoo7994
@wasimedoo7994 Год назад
Very good information bro I am from Guyana I do fridges freezer and small split ac I do not have much experience with this value but with this information I am leaving thanks for that one small question how can I know the in and the out of the TXV I work on cooler have it never replace or have problems with thanks
Далее
Troubleshooting  the TXV
19:23
Просмотров 45 тыс.
Why and How to Adjust a TXV / TEV
19:15
Просмотров 426 тыс.
TXV TROUBLE, ICE ON EVAPORATOR, HOW TO ADJUST THE TXV?
10:29
How to Check Evaporator Superheat
4:11
Просмотров 97 тыс.
Very cool tool - HVAC schrader core changer
4:44
Просмотров 63 тыс.
HOW TO ADJUST A TXV ON A WALK IN FREEZER LIKE A PRO
8:56
Class - What Superheat Signifies
17:07
Просмотров 226 тыс.