How To Convert 8ft Fluorescent Lights to LED - Ballast Bypass R17D to FA8 

Benjamin Sahlstrom
Подписаться 435 тыс.
Просмотров 101 тыс.
50% 1

My Favorite Tool: amzn.to/3NIFJuO
8ft FA8 Single Pin LED Lamps: amzn.to/2TfgkAo
Replacement FA8 Socket Lamp Holders: amzn.to/2FIb5AY
LED Light Bulb U Clip Brackets: amzn.to/2FIImwa
8ft R17D LED Lamps: amzn.to/2NjFR7z
Wago Lever Nuts: amzn.to/2R5esHy
Wire Nut Twist Connectors: amzn.to/2FDKCog
4ft LED Retrofit Ballast Bypass Bulbs: amzn.to/2uFnAex
4ft Replacement Tombstone Adapters: amzn.to/36McX7F
Get a discount on the Sense Home Energy Monitor if you are a subscriber here: store.sense.com/discount/BENJAMIN
Tools We Recommend: www.amazon.com/shop/benjamins...
0:00 - 8ft Fluorescent Lights to LED Intro
0:18 - Types Of LEDs
1:10 - LED Light Options
1:43 - Testing Fluorescent Power Draw
1:59 - Pay Attention To The Ends
3:26 - LED Light Info
4:04 - TURN OFF THE POWER
4:19 - Remove Bulbs & Covers
4:56 - Remove End Pieces
6:13 - Cut Wires From Ballast
7:00 - Replace End Sockets
10:47 - Wire End Sockets
13:16 - Install LED Bulbs
14:24 - The Moment Of Truth
15:35 - Testing LED Power Draw
18:18 - SUBSCRIBE!!!
Here we go over the process of converting your old fluorescent light fixtures to LED using the ballast bypass method. This eliminates the need for ballast maintenance and will increase the efficiency of your lighting system.
Thanks for watching and subscribing! As an Amazon affiliate I earn from qualifying purchases. Thank you for your support!
Was this video helpful to you? Send a tip:www.paypal.me/bensahlstrom
Become a Patron: / bensahlstrom
Ben

Опубликовано:

 

21 июл 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 214   
@xXBuckOFiveXx
@xXBuckOFiveXx 4 года назад
I do this for a living. I keep rolls of solid 18awg black and white on the truck but as long as you keep a consistent wiring scheme it’s not a huge deal as long as you don’t use green. I’m pretty sure the nec only dictates against using green as a current carrying conductor but yes standard field practice is 120volt white and 277v grey.
@BenjaminSahlstrom
@BenjaminSahlstrom 4 года назад
Awesome. Thanks for sharing your experience! Do you recommend changing out the lamp holders or do you usually match the bulb to the existing ones?
@xXBuckOFiveXx
@xXBuckOFiveXx 4 года назад
Benjamin Sahlstrom Hey thanks I appreciate that. In your case I would’ve changed them. You didn’t need HO lamps and they’re more expensive to retro. As long as they are in good shape, not old and fit the application I’ll leave them.
@huggyandkissyworld4334
@huggyandkissyworld4334 4 года назад
Wiring in the lighting fixtures its no big deal to use different color as long as you followed color code on the supply lines...thanks.
@jolyonwelsh9834
@jolyonwelsh9834 3 года назад
You can buy UL type B LED retrofit lamps with r17D bases. Satco and Keystone make such lamps.
@EM-gr1ps
@EM-gr1ps 3 года назад
Buddy89, all I can find locally is stranded 18 gauge. I tinned the ends with solder and the wire locked in fine. My question is , do you think it's a problem tinning the ends of the wire? Any safety concerns I need to be aware of? Thanks for your input
@RudyNortz
@RudyNortz 4 года назад
I see you kept the old cobwebs. I like to remove them and have new ones installed eventually...
@hubier6661
@hubier6661 4 года назад
I find your page very informative. I’ve never done residential only commercial work. We use MC as a posed to romex and we generally use 12 gauge for our branch circuits! We do tons of conduit bending and 600 kcmil runs! A lot of the things I seen on your page we don’t do out in our field so I’m glad to see different views!
@tonymarder8619
@tonymarder8619 2 года назад
Your video helped us replace 25 ballasts across 5 strings of fluorescents. Saved us $1800 from the electricians quote. Thanks. I’d add a picture of the finished project if I could.
@brianevans6860
@brianevans6860 3 года назад
Ben, I used a previous video for guidance on installing a sub panel and I was successful - everything works as it should! Unfortunately, I'm having issues with regular fluorescents so am going to convert to LED. This video is extremely helpful. Thanks, and yep, I'm subscribed!
@williammccoy9854
@williammccoy9854 4 года назад
Man, these videos are great! I'm getting ready to start a whole home remodel. I'm competent in regards to framing and structural work but I've always been intimidated by electrical. These videos are great. I like the level of detail without mind numbing info saturation that is found in most "learn from a pro" videos... Awesome!
@greenmile4233
@greenmile4233 4 года назад
finally, the least complicated and a simple explanation for bypassing the Ballast...thanks man
@Sparky-ww5re
@Sparky-ww5re 2 года назад
When I do fluorescent to LED tube conversions, I like to apply the labels to warn not to install fluorescent lamps in the fixture, as there is no ballast. In one of the shops I was working at a few years back, a maintenance contractor was injured when a fluorescent tube exploded at the end he was holding, upon inserting the tube which had 277 volts at the tombstone, it had the ballast bypass and was wired for single end power, the other tombstone was used as the support. Just a thought based on my experience working in commercial. In your application not a big deal because 120 volts or even 240 or 277 is not enough to start a fluorescent, wired end to end. If wired single end, definitely should apply the warning label, even more critical at higher voltage like 240 or 277,
@mattzelek7630
@mattzelek7630 2 года назад
Finally, a video that covered all the bases! Well done!
@airitwide
@airitwide 4 года назад
Why not put some white tape on either side of the yellow wire? Calling it off white is like calling blue wire off-red.
@nadarajahsivalingam2665
@nadarajahsivalingam2665 4 года назад
Hei Benjamin, I am very interesting to watch all of your videos. Since you are confident in your work your explanation is crystal clear.Keep it up.May God Bless You and Your Family.
@jolyonwelsh9834
@jolyonwelsh9834 4 года назад
According to article 200 of the NEC, you are required to use white or gray for neutral wires #6 and smaller. You can't use phase tape. The only exception would be is for switch loops when 2 wire romex or M/C cables are used. I think that includes fixture wire as well.
@CoolerQ
@CoolerQ 4 года назад
Man it bugged me that you kept the wire nuts and hanged the Wagos off of a pig tail. :) I definitely would have cut off the wire nuts and put the power input and output directly into the Wagos. Otherwise, it looks really nice and the light quality improvement is immense!
@tompeters4234
@tompeters4234 4 года назад
I love all the extra information. Interesting the 4' bulbs are about $5. I've been buying mostly the cheapie LED fixtures and last paid $15 for a 2pk from Menards. I still admire the Amp tester. Some day, I'll find the cheapest one made as I generally don't need it but just want one. And 100% correct, go with 'off white'. That would be my logic as well.
@Denny_E_Lee7575
@Denny_E_Lee7575 4 года назад
Another awesome tutorial Benjamin...Thanks👍
@aaroningersoll8236
@aaroningersoll8236 3 года назад
This video was extremely helpful, thank you for explaining this so well👍
@robertgaines-tulsa
@robertgaines-tulsa 4 года назад
Electrical code does allow just the ends to be marked with the correct color. White electrical tape works well, but sometimes I'm adventurous and use which heat shrink tubing. White wires can also be marked black when used as a hot such as when using general romex as a 240 line.
@danielherrero431
@danielherrero431 4 года назад
I like your show and the way you explain every thing by the way I celebrate that you work with your kids
@jolyonwelsh9834
@jolyonwelsh9834 3 года назад
A bit of safety advice. If you have a grounded conductor, as is the case with 120 volt, 208 volt high leg, or 277 volt systems, I would recommend connecting the grounded conductor to the end with the spring loaded A8 or R17D lampholder. This will reduce the risk of an electric shock as it is the first to make last to break. This is if you are too lazy to turn off the power when changing lamps which is what you should do.
@duenge
@duenge 4 года назад
I've watched many of your videos....I think you are a bit OCD. I am surprised that those old, dirty fixtures were not taken down, vacuumed, sand-blasted, and powder coated before the conversion was complete. I wish I were you when I was a younger man...A real go-getter!
@shukrimoe2814
@shukrimoe2814 5 месяцев назад
These days its so cheap. More evonomical to buy a complete fixture with the led lights wired, just plug n play, then to take down the old ones vacume, plast, etc.
@EM-gr1ps
@EM-gr1ps 3 года назад
Buddy89, all I can find locally is stranded 18 gauge. I tinned the ends with solder and the wire locked in fine. My question is , do you think it's a problem tinning the ends of the wire? Any safety concerns I need to be aware of? Thanks for your input
@narcisoramos5949
@narcisoramos5949 2 года назад
Nice job done Ben!
@jolyonwelsh9834
@jolyonwelsh9834 4 года назад
They do make LED Retrofit lamps with the R17D (HO) base. Satco makes such a retrofit lamp. I'm fact Satco makes all the weird sizes for retrofitting signs in both single and double sided versions.
@charlesb4267
@charlesb4267 2 года назад
I realize this is an older video at this point as I came across it and was surprised you were doing the retrofit and why I say it that way, is this actually to code in the USA to install these bulbs and therefore bypassing the ballasts. Here in Canada I was told by an electrical supplier who also has licensed electricians as well as speaking with other electricians, its a no go to do this retrofit as far as being to code as well as very possibly voiding your building insurance in the process. Yes some people have certainly done the retrofit not realizing the implications. At the time and not sure if that is different now but most of those bulbs from china are not certified under CSA or UL but that is only part of it, the other problem is that the existing light figures were never approved for 120 volt bulbs ran direct, only for the reduced voltage after the ballast. It was some years ago I did some retrofitting and replacements of fixtures, uninstalled the 8 foot units and installed 4 foots in their place and then replaced all the otherolder 4 foots I had with electronic ballasts. Then installed the retrofit LED bulbs designed to run off of the electronic ballasts. If I could have found actual LED strip lighting fixtures at a price that was affordable at the time I would have done that instead of course but they were beyond insanely priced, have not priced out strip LED lately. The power draw testing I did with an ammeter was interesting as I had experimented by testing the older 4 foot units that had magnetic ballasts with florescent bulbs, then installed LED bulbs and no difference in the power draw. Then I changed out the magnetic units for the electronic ballasts running the same LED bulbs and the power draw dropped exactly half. That was eye opening, I expect dedicated strip LED lights would use less power yet but the newer ballasts with the retrofit LED bulbs were a compromise that kept the type of retrofit I did still to code. The bulbs work great as per the heat not turned on in the shop and can be very cold out and they come on with no issues and no more of that humming and pulsing light that florescent is famous for. Anyway just thought I would share that and to check out if such a retrofit as per this video is allowed by code in your area of the world.
@chilla9174
@chilla9174 4 года назад
Can you make a tour of your workshop? That would be epic
@dirtdevil7bo
@dirtdevil7bo 4 года назад
Hey Ben, yellow wire is considered hot. You can use a hot color as a neautral, just tape it white in several spots to re identify the hit wire as a neautral.
@jameskelso839
@jameskelso839 2 года назад
I agree with Ben here, there is actually different color electrical tape and code requires that any non-neutral wire color needs only be taped with the appropriate color. This is something that you have to do when working with multi-wire systems of more than 2.
@johnakagi1088
@johnakagi1088 3 года назад
Another great video! Thanks.
@m3rdpwr
@m3rdpwr 4 года назад
In older homes with the older codes, it is common to to see a black or white wire being used for the opposite, depending on how something is being fed. It is my understanding that this is acceptable, as long as you wrap the wire in the junction box accordingly, with white or black tape.
@zaz4667
@zaz4667 11 месяцев назад
I like how you showed the neutral on one end and the power on the other. Not being an electrician, I am gonna have to find a schematic so I don't electrocute myself. I got a little lost on the wires all getting tied to the wire nut.
@duanewing3008
@duanewing3008 4 года назад
You were concerned if you should use the existing yellow wire that was in the light fixture. I say yes do it but add a peace of white electrical tape on the yellow wire at both connection points of the yellow wire to indicate that it is a neutral wire.
@joshc474
@joshc474 Год назад
WOW!! finally found the video I was looking for .great job
@conanleeu4903
@conanleeu4903 4 года назад
Great job!
@rjwiderman
@rjwiderman 2 года назад
I LOVE my shop LEDS! BEN…..Thanks for your instructions!
@shukrimoe2814
@shukrimoe2814 5 месяцев назад
Thank you very much. You solved several problems for me. I am replacing our garage's flourecent T12 8" to Led T8, 8". Qauntity 11 fixtures conected in series. My question: I didnt see a ground wire coming out with the L and N wires. Is that normal?.. If not what should I do? Thanx.
@frankmarques8292
@frankmarques8292 2 года назад
Nice Vid, and to the pint, thanks
@GregSr
@GregSr 3 года назад
Wish I would have seen this video before I bought 4 foot LED tubes from Costco. They physically installed ok but would not switch on. I'm sure it had something to do with the ballast. Took the tubes back. I ended up buying the entire LED fixture that came with LED lamps installed. It came with various switchable settings and a motion detector.
@gabrielgonzalez3501
@gabrielgonzalez3501 3 года назад
Really helpful thanks bro
@jamesdodd400
@jamesdodd400 4 года назад
Why do you have blue wire in your single phase panel?
@000gjb
@000gjb 4 года назад
Greetings from Australia. Last year I replaced the suspended ceiling in my factory which had various fluorescent tube light fittings. I replaced all the fittings with flat panel LED's 4 x 1 ft, 3500 Lumen output, 4000K colour temperature, weighing 4 Lbs in weight, about 1/2 inch thick and came with a 3 pin plug on a flexible lead.. They were available either to go into the suspended ceiling rails and had other mounting kits. Larger lighting panels with higher outputs were available.Why would you bother with crusty, rusty old fluorescent light fittings with heat damaged wiring. It would probably be more cost effective than to change out tube fittings.
@falconthree3815
@falconthree3815 3 года назад
I have a very old lamp unit-,the tombstones have a metal clip in the front and two holds in the back, how do I mount the new one . Thanks
@pdab4372
@pdab4372 2 года назад
Great video!
@eddieharbour5922
@eddieharbour5922 2 года назад
great job looking forward to more videos
@arnieselectric007
@arnieselectric007 4 года назад
So, what do you do in your shop there..? Again, a super well done video Ben...
@aaron74
@aaron74 4 года назад
I'm thinking of just taking down the 8 foot HO fluorescents in my garage and putting in standard keyless fixtures with super bright screw-in LED lights. The HO fluorescents are supposed to be rated for cold weather starting, but I'm find they start off pretty dim. I want instant bright in my -20F garage.
@000gjb
@000gjb 4 года назад
Throw them all in the bin. Install flat panel LED's.
@aaron74
@aaron74 4 года назад
@@000gjb Those are really cool-looking! If you don't already have fixtures I would say to go that route. But if you already have the old fluorescent, the retrofit tubes make sense. Also you can change them out easily if they go bad.
@000gjb
@000gjb 4 года назад
@@aaron74 You can add two hat brackets which fix to the back of the LED panel and each of the hat brackets can be be fixed to say a Purlin with one screw each. I have never seen an 8 foot fluorescent tube in my life. Hate to drop or stand on one. It would take months to recover from any deep flesh wounds.
@000gjb
@000gjb 4 года назад
@@aaron74 These LED Panels were $62 AUD each back in January 2018, looking at the receipt. If you can believe any of the chinese literature, they have a lifespan of 30,000 hours or 12.5 man years @2500 hours worked per year ignoring light loss factor, for Lumen depreciation. If one fails, unplug the LED panel from the socket and plop in another one. 5 minutes, including getting the ladder.
@aaron74
@aaron74 4 года назад
@@000gjb Yes, the 96-inch tubes have existed for many years, I have them in my garage. They are quite unwieldy to say the least, but it's one of those things I installed that seemed like a good idea at the time. If I could go back I would have installed either twin 48-inch ones, or cheap keyless sockets (aka Edison sockets). Oh well. Since the fluorescent lights work fine, I probably won't bother dealing with them!
@FixthisCD
@FixthisCD 4 года назад
I didn't know they had 8 foot replacements. Good to know
@BenjaminSahlstrom
@BenjaminSahlstrom 4 года назад
I was glad they did! Makes a huge difference with the brighter bulbs!
@davcot3675
@davcot3675 4 года назад
I think yellow ok for neutral Check NEC 410.130.G.1 for certain lighting u need to install disconnect plugs. Typ orange Plus cool trick use ur cell phone and look at fluorescent lights If looks like barber pole it is magnetic ballast. If no barber pole electronic ballast. Try it out I hate doing light bc so filthy I like doing lights bc of the instant gratification
@daveinwla6360
@daveinwla6360 4 года назад
Pins which are powered (i.e. carry a current) on BOTH ends of a fluorescent tube are a *HAZARD* ! If a workman replacing a tube while the power is ON has a finger touching the pin(s) on the unpowered end, a shock is possible when the powered pin(s) make contact in the socket at the other end. It is safer to have the power fed from one end and have the other end just for physical support. LED tubes for ballast bypass are now almost all "G13 Bi-Pin" or "recessed double contact" for that reason. For G13 Bi-Pins, the socket contacts on one end are "unshunted" so they can be separately wired "hot" and neutral, and the socket on the other end is just for support and not wired. In this project, sticking with the "recessed double contact" format would have been safer.
@dharsh9160
@dharsh9160 3 года назад
Did you use non shunted tombstones?
@patriotamerican62
@patriotamerican62 2 года назад
God bless a American, you know how to fly a flag. I think your videos are very educational. Good job.
@dantx4545
@dantx4545 4 года назад
As for the internal wiring colors I would just use the yellow er...(off white) wire Unless the NEC specifically says otherwise
@BenjaminSahlstrom
@BenjaminSahlstrom 4 года назад
Exactly!
@Connr_-vj7iv
@Connr_-vj7iv 4 года назад
Same here. I like to wrap a small bit of white electricians tape around something being used as a Neutral just to make sure if anyone else was to go back and do something they know for a fact it’s the neutral wire! Great video
@Ruffles206
@Ruffles206 4 года назад
Let me understand, I can replace my bulbs with led, but I have to remove or disconnect the ballast? And one more question this type led bulbs are good brand?
@ibrahimsafi3455
@ibrahimsafi3455 4 года назад
The ballast consumes a lot of power on startup and is necessary for the gas inside the fluorescent bulbs to start up, hence the buzz when you start up the lights. This is not necessary for leds, as they are made differently.
@gabakusa
@gabakusa 2 года назад
I don't see the link for the poll
@alldayjack4830
@alldayjack4830 3 года назад
Will they work outside, in cold weather? Dry location.
@ebeaulieu813
@ebeaulieu813 Год назад
well done
@dmope22
@dmope22 3 года назад
You can re-indentify the yellow wire with white tape to use it as neutral. I like to do that to keep things simply.
@matthewhoffman9242
@matthewhoffman9242 4 года назад
Is there a way to tell if the led replacement bulbs need a ballast? I bought some bulbs on sale at lowes and can't remember if the box said anything
@BrianFullerton
@BrianFullerton 3 года назад
If the label on the tube does not say type one or type 2, and you can't find an OEM cut sheet for the model number, you can always do a smoke test and find out.
@matthewhoffman9242
@matthewhoffman9242 3 года назад
@@BrianFullerton true😅, hadn't thought about that
@coryhagan3336
@coryhagan3336 Год назад
We used the yellow wires when by passing the ballasts on our light fixtures.
@MrMkapusta
@MrMkapusta 4 года назад
It's that young smart talking kid again!
@michaelbenjamin8
@michaelbenjamin8 4 года назад
I don't get it ... when you measured Amps on the blue in the beginning it was 4.75 and after you converted it was 6.25 Amps ?
@gwkgb8474
@gwkgb8474 4 года назад
LEDs are more expensive to run in that configuration but are brighter so in a lumen per amp they are way cheaper to run if you thin you need that much light
@mojunk19
@mojunk19 4 года назад
So much for savings money. You started with 4.9 amps and ended with 6.25. But it is brighter.
@matty4178
@matty4178 3 года назад
I thought the power company says you save on power consumption therefore money with LED's. this conversion doesn't appear that is the case. Am I missing something?
@bobniles1928
@bobniles1928 4 года назад
I have been using lower color temperature LEDs, about 4500K. Light is not as harsh and less bluish. I also reuse the tombstones unless they are cracked or the wiring terminals are discolored due to heat.
@BenjaminSahlstrom
@BenjaminSahlstrom 4 года назад
Yeah, the 6k does seem pretty "harsh" as you mention. 4k is nice and I even enjoy the 3.5k when available.
@davidmarquardt2445
@davidmarquardt2445 3 года назад
@@BenjaminSahlstrom I installed LED strip lights under my kitchen cabinets. The 2 footer is 25 watts and puts out 2,000 lumens, that's 750 lumens more output than a 100 watt incandescent bulb yet uses 75% less power. It's rated at 4,400 K, it's the best light I've ever seen, no pinkish/red or bluish/purple tint, just pure white light.
@jamesipad204
@jamesipad204 3 года назад
The wire should be white. Can you use 18 AWG to run 120 volts?
@rick601a
@rick601a 4 года назад
The inspector here in my area is fine with yellow because it’s inside the fixture. One of the inspectors in our area has opinions that the sockets were never approved for the current rating that they might encounter if the led style bulb fails into a shorted condition. As in the Original application the sockets will never see 20 amps short circuit..But he is older inspector and none of the other building inspectors has brought this up but he brings this up all the time. But he still appeared the installation work.
@BrianFullerton
@BrianFullerton 3 года назад
He actually has a point. The ballast is a current limit on the output lines. The wegos are not performing that function.
@xcmskim4
@xcmskim4 4 года назад
I'm cheap so ill just use any color wiring i have lying around in a light fixture. If this were an electrical box or rough-in follow code. You can also wrap white electrical tape to indicate netural
@aguyandhiscomputer
@aguyandhiscomputer 4 года назад
Purple tape is cool
@garymucher9590
@garymucher9590 4 года назад
Once you are inside any light fixture, you could use pink if that is what you have. The actual colors are set up more for exterior/house wiring coming up to the light fixture. JMHO I guess cleaning everything up before reinstalling things is out of the question...
@chipfriday9967
@chipfriday9967 4 года назад
I would have removed the fixtures, cleaned them and then spray painted them. Then cleaned and repainted the ceiling as well. Would have been interesting to "before and after" put a light meeter on your benches and seen the improvement of all your work.
@Dmitrytln
@Dmitrytln 4 года назад
Wrap yellow wire to white heat shrink. You are using tubes where power goes to both ends, but such tubes are allowed only in few countries. In many countries electrical codes require only one-end powered LED tubes since 2010.
@kevindavis4709
@kevindavis4709 2 года назад
At 9:41 depends on who comes in behind you in the future to replace those tombstones
@IGoProEVERYTHING
@IGoProEVERYTHING 4 года назад
As long as they are different colors all should be good.
@dunckeroo1987
@dunckeroo1987 4 года назад
Don't worry about the yellow wire as neutral : Just make sure all the lighting cases are grounded in some reliable way.
@craigsmith8217
@craigsmith8217 4 года назад
I've been using LEDs in my kitchen ever since they were affordable, mainly to cut down on the heat that seemed to be killing my ballasts in a closed fixture. They do seem to have a limited life of about 2 years, or 10,000 hours, when they begin to dim. My wife keeps the kitchen lights on if she isn't in bed. LOL
@bobdarling3353
@bobdarling3353 3 года назад
I'm struggling!!! I bought a bulb that says it's compatible with a ballast (but I removed the ballast)....does that mean that bulb will not work unless you have a ballast? help please
@BenjaminSahlstrom
@BenjaminSahlstrom 3 года назад
Yes, typically they are either for line voltage or to be used with the ballast. I would recommend the ballast bypass option since that will use less energy.
@bobdarling3353
@bobdarling3353 3 года назад
@@BenjaminSahlstrom Thank You!
@richwood2741
@richwood2741 4 года назад
As long as you keep uniform with all your lights so as to avoid confusion you will be good as long as you dont need an inspection. The lever connectors he used are the old style. The new ones are much better and smaller.
@BenjaminSahlstrom
@BenjaminSahlstrom 4 года назад
That's what I assumed. Keeping it uniform and orderly will make for a safe and easy to understand installation for sure.
@BenjaminSahlstrom
@BenjaminSahlstrom 4 года назад
I have seen those new Wago's. I need to order some and try them out!
@aerofart
@aerofart Год назад
I’m pretty sure NEC states that it is permissible to mark any insulator as neutral with white tape.
@jgwalling
@jgwalling 4 года назад
I would just use white tape wrapping around the yellow wire and that indicating that's neutral
@BenjaminSahlstrom
@BenjaminSahlstrom 4 года назад
That seems like it would be the best and most thorough but yet cost effective way to go for sure.
@qqube4762
@qqube4762 3 года назад
I say use what wire is available from inside the light fixture if possible. It will save on time and money.
@venividivici4253
@venividivici4253 4 года назад
I prefer wirenuts lol. But great video!
@gregsimcock
@gregsimcock 3 года назад
Colour coded wire was designed for electrical installations for a reason and it is good safety-practice to use the coloured wires in an installation so as to keep the uniformity of the original electrical wiring used before the handyman buggers up the electrical wiring installation.
@waynew2831
@waynew2831 3 года назад
Honestly If the next person to come along, does not know enough about electrical wiring to understand what is going on in this simple situation, he has NO business sticking his hands in there in the first place.
@bruceboyles1895
@bruceboyles1895 3 года назад
You ask what to do when wire color is incorrect, as an electrician of 20 + years I used a color flag. A piece of tape that the correct color @ each end of the wire. A flag is tape 2 or 3 inches long w/ both ends sticking up away from the wire.
@kevinsturges466
@kevinsturges466 2 года назад
I would use the "off White" wire but I would put a piece of clealy white tape towards the end for when I forget what I did years from now.
@cengeb
@cengeb 3 года назад
those LED tubes with bare visible LED elements are kinda crude, Philips (Signify) Osram Sylvania have really nice LED Tube lamps, no obvious LED elements, smooth linear lighting, coated tube
@rubencastillo2623
@rubencastillo2623 3 года назад
Goggls so important 4 this job .why? Ur eys in. Away frm glass tht s been known to pop n shoot small fragments of small glass to ur eys gogles a must thk u
@butchs2337
@butchs2337 2 года назад
the old lights used just a little less than 5 amps and now the new lights are using just under 7 amps, i know you get a lot more light from the new lights as you can see but what about what the electric cost, are the new lights going to cost more to use, you should also tell everyone how much longer LED will last, these lights are great compared to the old ones
@roncraig007
@roncraig007 9 месяцев назад
Wrap the ends of the neutral wires with white electrical tape.
@joemaldonado3
@joemaldonado3 Год назад
use the yellow as before. then put white tape or white tubing for ident.
@DKing-sc3nt
@DKing-sc3nt Год назад
You show close to 5 amp draw on each of the three circuits with the ballast and Flo tubes. Your finish LED conversion was pulling more amps. Your electric bill went up !
@FixthisCD
@FixthisCD 4 года назад
Technically it should be white, but anyone that is doing electrical should be good enough to figure it out. Regardless you didn't verify the hot was actually the hot wire, so the colors could be backwards ;)
@BenjaminSahlstrom
@BenjaminSahlstrom 4 года назад
I am 99% sure that the polarity is correct but you're totally right! Obviously it really doesn't matter much since the LED lights are not polar sensitive. Thanks for the comment!
@JohnnyUmphress
@JohnnyUmphress 4 года назад
I believe that the color of wire is not a factor inside of an appliance.
@robertstack2144
@robertstack2144 11 месяцев назад
Use white tape on the yellow wire to signify neutral
@gregfisher216
@gregfisher216 4 года назад
White in this application !
@bobniles1928
@bobniles1928 4 года назад
I install a warning label in the converted fixture to warn that the fixture is LED and not to use florescents. The labels came with the tubes.
@larryfisher5198
@larryfisher5198 3 года назад
Add white tape to wire indicate
@rebel-yellenterprises1479
@rebel-yellenterprises1479 3 года назад
If I repurposed them within the fixture, I would mark each end with white tape to designate it as “N”.
@chipfriday9967
@chipfriday9967 4 года назад
If you are a bit pedantic like me, then spiral wrap the ends of the yellow wire just before they join up with your plastic clips with an inch or so of white or gray electrical insulating tape and I think you will be up to code. Couple of pennies of tape and a minute of your time for each yellow wire connected. Especially if you have to pull an electrical permit with the county or city where you live.
@user-wc9gr6zs9d
@user-wc9gr6zs9d Год назад
I do not think an non matching wire color really matters 4 a D I Yer if it is a common conmection
@FixthisCD
@FixthisCD 4 года назад
Should have shown a comparison of Fluorescent current draw before replacement
@BenjaminSahlstrom
@BenjaminSahlstrom 4 года назад
I did test it before and after but on the entire bank lights. 5amps before and 6.5amps after. I should have tested one individual fixture like you said though!
@FixthisCD
@FixthisCD 4 года назад
@@BenjaminSahlstrom Oh sorry I missed it.
@BrianFullerton
@BrianFullerton 3 года назад
@@BenjaminSahlstrom So if each new tube uses less watts (90 vs 95 on labels), and there are the same number of tubes, and the line voltage is still around 121VAC, why more branch amps after than before? Power factor? Ballast limiting current to the old tubes? Startup rating vs operating current in steady state?
@bradr8806
@bradr8806 2 года назад
some white tape at the ends or a bit of white paint is an easy way to clarify for the next guy
@jonanderson5142
@jonanderson5142 3 года назад
You should Identify the yellow with white tape...
@oswaldjh
@oswaldjh 4 года назад
The color of the wire can be technically changed by wrapping electrical tape of the proper color at each end of the wire.
@BrianFullerton
@BrianFullerton 3 года назад
Depends on the code you are under. Not always.
Далее
Каха бизнес-класс
00:48
Просмотров 1,5 млн
Swapping Fluorescent Garage Lights to LED
18:07
Просмотров 356 тыс.
How To Wire a Multiple Gang Switch Box Rough In
24:23
Просмотров 842 тыс.
Каха бизнес-класс
00:48
Просмотров 1,5 млн