How to diagnose a locked rotor compressor 

grayfurnaceman
Подписаться 158 тыс.
Просмотров 368 тыс.
50% 1

This one covers determining if a compressor has failed due to locked rotor.
This video is part of the heating and cooling series of training videos made to accompany my websites: www.graycoolingman.com and www.grayfurnaceman.com to pass on what I have learned in many years of service and repair. If you have suggestions or comments they are welcome.
If you are a homeowner looking to repair your own appliance, understand that the voltages can be lethal, the fuels are highly flammable and high pressures are used. Know your limits.

Опубликовано:

 

29 сен 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 222   
@grayfurnaceman
@grayfurnaceman 11 лет назад
LRA means locked rotor amps. This is the amp draw when the rotor of the compressor is stuck. RLA means run load amps. This is the maximum amp draw while the compressor is operating. GFM
@irvanbukhori2439
@irvanbukhori2439 4 года назад
What's the meaning FLA
@grayfurnaceman
@grayfurnaceman 11 лет назад
I should have been more explicit. Yes. If the compressor locks, it must be replaced. You can try a hard start, but even if it works, the compressor will have a limited life. The locked rotor is the best case if you must have a failure. A burnout is the worst, as the system is then contaminated with smoke and burned winding insulation. Thanks for the heads up. GFM
@aguilar858
@aguilar858 4 года назад
Great info.
@jacobbell1934
@jacobbell1934 3 месяца назад
Thanks a lot. I didn’t even know what the LRA was. So if I see that it’s possible to put a hard start kit on give it some more time before they replace? I’m now very concerned about what you said with the system being contaminated from burnt motor. I’ve replaced a few compressors(I just went from install to tech in March). I did replace the refrigerant and filter dryer when doing that, but could I’ve messed up the system for those customers if the motor was burnt?
@grayfurnaceman
@grayfurnaceman 3 месяца назад
@@jacobbell1934 Hard starts are a short term fix that could be useful in some cases. If you get a burned smell from the refrigerant in the system, I would recommend installing both a liquid line and suction line filter with replacement of the driers after a few days operation. GFM
@Pretzel114
@Pretzel114 10 лет назад
Hi GFM, good video. Being a newbie I was wondering what is the Johnson Control A419 control for? Thanks.
@grayfurnaceman
@grayfurnaceman 10 лет назад
1290457 In this application, its used as an outdoor thermostat to shut off the heat pump at lower outdoor temperatures. GFM
@Pretzel114
@Pretzel114 10 лет назад
Ok, I was kind of leading that way. Thanks for the reply.
@grayfurnaceman
@grayfurnaceman 11 лет назад
There is no backwards compatible R-410A unit to R-22. It can be done but will not work without a change in expansion device and no manufacturer that I know of recommends it. GFM
@grayfurnaceman
@grayfurnaceman 11 лет назад
That don't sound like a locked rotor. Sounds like burned windings. Also sounds like money. GFM
@michaelmiller3183
@michaelmiller3183 11 лет назад
My son is learning to be a tech and i want to say you are the best at teaching him!!!! thank you
@jeanJenner
@jeanJenner 8 лет назад
I actually got a locked AC compressor to run after hitting the top of it with a rubber mallet. Three years later it still running....
@na6273
@na6273 7 лет назад
Agreed.This had happen to me once.But very rare.For 3-Ph compressors,we can release the rotor lock by reverse rotation.
@gabworld2446
@gabworld2446 6 лет назад
Anand Gbk how can on reverse the rotor rotation?
@HighVoltageMadness
@HighVoltageMadness 6 лет назад
gabriel peter by swaping any to phases going to the compressor.
@Polarcupcheck
@Polarcupcheck 6 лет назад
I might need to learn what the hell you mean.
@Clamjammer
@Clamjammer 6 лет назад
By switching the start and run leads going to the compressor you can reverse the direction of the compressor thus freeing the locked rotor. Then switch the leads back to normal and try it again. Only for three phase motors!!
@grayfurnaceman
@grayfurnaceman 11 лет назад
Compressors start very quickly. Locked rotor amps is only present for a fraction of second. If you push in the contactor and it does not start, you have 3 to 5 seconds before the overload goes off so a short try will tell if it is going to run. Hope this helps. GFM
@grayfurnaceman
@grayfurnaceman 11 лет назад
Check out the "test meters" playlist on my channel. It may have something to help. GFM
@grayfurnaceman
@grayfurnaceman 11 лет назад
Thanks for the support. GFM
@grayfurnaceman
@grayfurnaceman 11 лет назад
Thanks for the support. GFM
@ThePharris16
@ThePharris16 11 лет назад
Thanks for the video. Shouldn't the compressor draw LRA for a few seconds anyway? Could you push in the contactor and determine if the amps drop off, or were you saying too long would trip the overload
@na6273
@na6273 7 лет назад
All the compressor manufacturers will recommend minimum oil quantity that should always remain inside the compressor for lubrication.If your refrigeration line circuit is larger,then the oil takes more time to get back to the compressor.In that case,we must charge more oil (10% of total quantity). Try the above,definitely the compressor failure problem will be solved.
@martineucza486
@martineucza486 2 года назад
Best hvac instructor ever. Thank you!
@grayfurnaceman
@grayfurnaceman 11 лет назад
The replacement of the evap indicates there was leak in the system. That can cause overheat of the compressor. Also, the outdoor fan replacement means the fan was not running which can also cause overheat. I can't say about a company's integrity. Sometimes when major repairs are done, other failures pile up. GFM
@mechanicwarrior20
@mechanicwarrior20 11 лет назад
Good video.... I am looking forward to your capacitor trouble shooting video, I knew a guy who replaced a compressor thinking it was bad and when he replaced it, it still kicked off on internal overloads. He then later figured out that it was a bad run capacitor and he regrets ever replacing the compressor because it was just a bad run cap the whole time.
@grayfurnaceman
@grayfurnaceman 11 лет назад
That's the defrost board. This is a heat pump. The light is a diagnostic light. Hope this helps. GFM
@thebigd6249
@thebigd6249 Год назад
LRA (Locked Rotor Amps) is an electrical measurement of current for starting a motor, compressor, or any inductive load. It is referred to as in-rush. It is when the rotor starts from a stopped position and draws between 5 to 7 times more amps to start the load when compared to RLA. Also, in order to properly measure in-rush, you need a clamp meter that can read in-rush. In-rush occurs within the 1st-2, to 3 cycles of the 60hz frequency. Only specialized meters can read that quickly and they range from $500 on up.
@natashaburrell7615
@natashaburrell7615 Год назад
Harbor freight CM1000a clamp meter measures in rush for 100 bucks. Not the kind of meter you can brag about to your friends but still better than nothing.
@newstart49
@newstart49 10 лет назад
Not exactly how I would have done it, but to each their own. Voltage and wiring to compressor to verify would be a last "to be sure" check. Now- why did the compressor go to lock rotor? Ohm the windings to see if one winding may be weak. Was it due to a dirty indoor coil, blower motor cycling or quitting, system overcharged, crank heater failure, voltage problem, restriction in metering device and loss of oil in compressor- etc. Good video.
@grayfurnaceman
@grayfurnaceman 10 лет назад
Thanks for the thoughts. GFM
@chrism7275
@chrism7275 5 лет назад
you must of been new when you wrote this comment. dirty indoor coils not going to lock your rotor up, crank case heater failure could cause valve issues but i highly doubt rotor locking, system overcharge not going to lock your rotor and restricted metering device is not locking the rotor, usualy the causes for your rotor locking is an electrical issue whether bad capacitor or potential relay, low voltage, phase loss or simply motor seizing
@grayfurnaceman
@grayfurnaceman 11 лет назад
It was replaced due to the owner wanting current efficiency equipment. GFM
@grayfurnaceman
@grayfurnaceman 11 лет назад
This one managed to get stopped. It is a good product line though. GFM
@na6273
@na6273 7 лет назад
For LOCKED COMPRESSOR ROTOR - We have 3 different scenario. 1.Rotor Locked,but winding is good and no short to ground. 2.Rotor Locked-winding failure,but no short to ground. 3.Rotor Locked-winding failure and short to ground. Major reason for all the above symptom is possibly Low Compressor Lubricating oil inside the compressor.Just flush out the system and collect the oil from the ref.lines and also measure oil remaining inside the compressor.Sum up both collected quantity and compare it with compressor total oil quantity.
@shahrukhchikhalkar7026
@shahrukhchikhalkar7026 6 лет назад
Hi boss thanx for information
@stephanedoyon8531
@stephanedoyon8531 11 лет назад
Tanks you for this tutorial. It's vert nice. What's différence LRA and RLA?
@SamsClub427
@SamsClub427 5 лет назад
You helped me out so much! I changed my capacitor but it would not start, only made a buzzing noise. I started it manually pushing the button that you pushed and it cranked up!!!! Thank you Sir and GodBless
@DJKiDDKlashez
@DJKiDDKlashez 11 лет назад
My compressor exploded the other day. Green liquid came out of it with horrible odor. Everything started well but the compressor took 10-15 mins to start. Now, I'm here in Texas with no AC. Sucks
@lavenderaqi1866
@lavenderaqi1866 9 лет назад
Oh crap thought this was porn, this is a video, porn is mostly a video, that means i can relate to this.
@melizzagonzalez6049
@melizzagonzalez6049 8 лет назад
lmfao me too!!
@johnc4876
@johnc4876 7 лет назад
Liquid slugging washes lubricant off of cylinders causing mechanical seizure.
@mikemc8495
@mikemc8495 5 лет назад
Doesn't locked rotor amperage occur every time you start the compressor?
@grayfurnaceman
@grayfurnaceman 5 лет назад
It does but it is for a very short time and usually cannot be measured even with most peak hold meters. GFM
@ghosthunter4007
@ghosthunter4007 6 лет назад
Great job explaining the LRA and how the Comp is locked up and why.
@grayfurnaceman
@grayfurnaceman 6 лет назад
Thanks for the support. GFM
@timmo6113
@timmo6113 6 лет назад
if i ohm out the compressor and have open circuit between start and run, open between run and com, this would rule out open overload correct? the overload is on the common line
@grayfurnaceman
@grayfurnaceman 6 лет назад
Yes, you have a dead compressor. GFM
@joehead1294
@joehead1294 2 года назад
Arc flash from hard start kit @5:32. Why the tape covering holes in control section? Why the A419? For low temp strip heat lock-out?
@grayfurnaceman
@grayfurnaceman 2 года назад
The spark is from the contactor contacts opening. The start kit has no contacts inside. The tape is factory from Trane. The A419 locks out the A/C when ambient is below 60F. GFM
@joehead1294
@joehead1294 2 года назад
@@grayfurnaceman OK.. Thanks.
@aliastalkss
@aliastalkss 6 месяцев назад
On a call right now & with forgot how to check just windings without ohming fan motor you a a great guy , going try out a jump cap hope it works
@al.e123iis7
@al.e123iis7 4 года назад
Hello gfm.. have you had an rtu unit that doesn't have voltage in one leg from the box. I replaced the switch box fuse, and the fuse box inside. Nothing no power?? So compressor doesn't come on
@Kaibil66
@Kaibil66 10 лет назад
Great explanation GFM you are the best!!!!!!
@SombraLocs
@SombraLocs 10 лет назад
What would the standing pressures be if you hook up your gauges to it?
@grayfurnaceman
@grayfurnaceman 10 лет назад
The pressures should correspond to the ambient temperature for a saturated vessel. Hope this helps. GFM
@SombraLocs
@SombraLocs 10 лет назад
The compressor was reading high suction pressure and low head pressure. The compressor sounded like it wanted to start, but then it would just turn back off. I checked the capacitor it was good, I checked the compressor windings also and they were good. Do you think I should install a Hard Start?
@jerrymullins5252
@jerrymullins5252 10 лет назад
SombraLocs if a hard start does not work take a piece of wood and put it on the compressor and hit it with a hammer, Might sound stupid but i have unlocked a bunch of them that way. Then the hard start will give it enough boost to start without locking up.
@scrowin
@scrowin 9 лет назад
+Jerry Mullins thank you! It's 1am and this compressor has been stuck all day on the hottest day in history in San Diego. Couldn't sleep it's so hot tonight so I was hunting for answers. Good ol crack in the ass on that compressor with my rubber Mallet and it started right up. It's been locking up on and off for a couple years now. Usually it will start up if I shut it down for a day or so. I skipped all the trouble shooting and went straight for the slap. I did pay an AC tech to come check it out but by the time he got here it started fine. He topped off the gas, checked the capacity and couldn't find anything wrong. I guess this thing is on the way out. Glad it's cooling my room down tonight.
@flaplaya
@flaplaya 9 лет назад
+grayfurnaceman Pressures on a "Locked Rotor" are static... 150 on both gauges... Are you paying attn?
@DJKiDDKlashez
@DJKiDDKlashez 11 лет назад
What would cause this? Can trust these AC companies around my area because their all a bunch of scams. The company changed my evaporator coil and added freon. Then all of a sudden my compressor delayed. Changed my motor fan outside but still conutined to delay(my compressor) did they add too much freon? I thinking they purposely tampered with my outside AC unit. So frustrating
@jixia676
@jixia676 Год назад
Hi, how to diagnose an inverter compressor if it's locked or not? Thanks sir
@heatpumphvac3150
@heatpumphvac3150 11 лет назад
the name plate is like the old tranes from the 80s so id say at least a 1993 model because in 1994 they started using the other name plate you know not the old metal name plates but the paper name plates i call it
@DJKiDDKlashez
@DJKiDDKlashez 11 лет назад
Just horrible. I'm planning to upgrade the Outside unit completely to the new system r410 that's backwards compatable with r22, minus well. When compressor exploded it melted the coils too. So I have replace everything.
@mychoclabwinston
@mychoclabwinston 10 лет назад
Digital flash on the 419' is because the power was reset, has a built in time delay, you do not use those 419s, very expensive, used for refrigeration, thermal disc, or fossil fuel kit, way cheaper
@FromTheDeepSoil
@FromTheDeepSoil 11 лет назад
hey the uei voltmeter you use is there a video that you have to learn how to use it or a website you can direct me too i have the very same one but is not to good in it yet
@doingstuff76
@doingstuff76 7 лет назад
hello I have a Comfortmaker 10 that when you turn it on the fan may come on but the compressor does not come on my local AC guy says that the compressor is needs to be replaced, does it?
@MrBg2000
@MrBg2000 11 лет назад
it could be LRA That happen to me too what happen is the high pressure lock the rotor. check the cap if its not good then change it if its good then u have to jump start it
@utube9139
@utube9139 10 лет назад
Unit running A OK, came back to find out lose low voltage connection @ A/H.unit. Thanks you for sharing your valuable time, resources and knowledge to help us new tech. Learn st new everyday out the field.
@mychoclabwinston
@mychoclabwinston 10 лет назад
Awfully exspensive ambient temp sensor lol, the a419
@15901111
@15901111 11 лет назад
So the compressor is mechanical broken . So that mean you have the replace the compressor?
@chileheadcraig
@chileheadcraig 3 года назад
I had a tech put in a good capacitor, use one of those hard starts and diagnosed a locked rotor, but I wanted to go through my warranty company. Had their tech come out and they change the capacitor and it started working? How can that be? I believe the first tech, but how can it be locked and then not locked anymore? Told the first tech what happened and he said sometimes they free up, but if it ever stops in the same spot again, it will probably lock up again. Anyone experience this?
@grayfurnaceman
@grayfurnaceman 3 года назад
It has been my experience that if a compressor stops running, it will stop again, regardless of capacitor replacement. You may get some extended time out of it, but the compressor is failing. GFM
@fordman1776
@fordman1776 Год назад
Great explanation. Straightforward and to the point.
@mychoclabwinston
@mychoclabwinston 10 лет назад
I hate those condenser coils, garbage, pure garbage,
@dannyhiggins2502
@dannyhiggins2502 7 лет назад
the problem is large line is cold and the small line is cool it should be hot (any ideas )
@randytorboli
@randytorboli 3 года назад
I have a package ac unit that recently had a condenser fan motor replacement done on it and the original condenser fan motor was a 1/8 horsepower 1100RPM motor and the one my repairman installed is a 1/2 horsepower 1075RPM motor and so far it's been working good so far do you think that over time it will cause damage because the unit itself is à 20 year old unit and he couldn't get the oem part because they don't make the same brand as what motor originally came in the unit
@grayfurnaceman
@grayfurnaceman 3 года назад
It should not cause any damage, in fact it may reduce the head pressure a little. GFM
@randytorboli
@randytorboli 3 года назад
@@grayfurnaceman that is a good thing
@richardmiller3808
@richardmiller3808 3 года назад
You are assuming the windings are good. I would have put a megometer on the unit to verify the windings first.
@grayfurnaceman
@grayfurnaceman 3 года назад
If you want to play with your megger, go for it. The point of this video is to determine if the compressor has a locked rotor. If the windings are good, and the rotor is locked, it still has failed. GFM
@richardmiller3808
@richardmiller3808 3 года назад
@@grayfurnaceman LOL if you know that already why bother with beating around the Bush then? Just tell the customer the news and go from there. My reasoning for megging out the windings is to have a root possible cause for the customer information. I don’t function like many HVACR folks. I like to have all the information before I give someone bad news. Just saying.
@grayfurnaceman
@grayfurnaceman 3 года назад
@@richardmiller3808 Not a bad way to be. GFM
@heatpumphvac3150
@heatpumphvac3150 11 лет назад
did you get this old trane xe1000 heat pump fixed or a new unit just wondering
@Ztr7
@Ztr7 4 года назад
Straightforward as always thank you so much
@CeaserOreo
@CeaserOreo 9 лет назад
The PTC thermistor start assist is weaker than a potential relay and start capacitor in regards to the compressor. How do you know the start kit was bad? If you send power to Common and start rather than common and run, it will reverse the compressor which can free it up, however it will still be bad if so. Ohming the compressors terminals they should all add up! Example Common to Run = 3 ohms Common to Start = 5 ohms then you better read 8 ohms from Run to Start which is both windings. If it adds up they usually run unless worn tight, if electrically it ohms out put a potential relay and start cap. Bump start by using a 300 mfd start cap touching the run cap briefly then take the BEMF, say 300v for example 300v x .50 = 150v min 300v x .80 = 240 v max 200v x 1.20 = 360v continuous this is how you size the potential relay.
@grayfurnaceman
@grayfurnaceman 9 лет назад
***** Thanks for the good info. GFM
@sparkyks
@sparkyks 11 лет назад
Its hard to stop a Trane... :) Thanks for another informative video.
@formerlyyours4295
@formerlyyours4295 3 года назад
I have a goodman unit with a comfortnet thermastat that says locked rotor. My ac man was not sure what was wrong. We flipped the breaker off and let it rest for 30 minutes and then flipped the breaker back on. The unit ran fine after that for about a month. Then the locked rotor screen came back on and so I flipped the breaker on and off and it worked for about a week and then locked rotor screen again. Tech said the issue may e the breaker size, does that make any since? Any advice is appreciated. This is a new unit put in within the last years time frame.
@grayfurnaceman
@grayfurnaceman 3 года назад
If the breaker is not kicking off, there is no problem with the breaker. You could have a compressor failing. GFM
@ScottDLR
@ScottDLR 3 года назад
Not the case here but Hard start kits are great until the standard cap dies. When that run cap dies, the Hard start cap takes over but ultimately kills the compressor motor because it's not designed to do the job. That's why I dont use them.
@grayfurnaceman
@grayfurnaceman 3 года назад
You are correct. Hard starts are not supplied from the manufacturer, except in certain circumstances, so they are not needed. GFM
@SarjanaObeng
@SarjanaObeng 5 лет назад
Does a faulty capacitor also draw amperes near the LRA value?
@electriccar3253
@electriccar3253 5 лет назад
If the capacitor is open, yes. If the capacitor is shorted, the amp draw will be higher. GFM
@islandreefdivers5299
@islandreefdivers5299 7 лет назад
Hi GFM.I live in the Caribbean and we have a little resort and maintain all my own equipment as there is no one here to do so.I was in the HVAC business years ago so still pretty knowledgeable .Yesterday our walk in Freezer compressor kept starting and stopping after 15 seconds.Pressures are good condenser and evap coils clean fairly new compressor .I noticed the compressor common was drawing 13 amps and the Run was drawing 2 amps then all of a sudden it started working fine again any thoughts ...Thanks and great videos.Very helpful
@grayfurnaceman
@grayfurnaceman 7 лет назад
Are you sure the compressor was starting and changing the pressures? I am thinking you had a locked rotor. Also, the amp draw of run should be higher than you read. GFM
@utube9139
@utube9139 10 лет назад
Thanks GFM. What can go wrong , if LRA is below data name plate, compressor ohm check out is good, dual cap is good,230v voltage present at the comp terminal, any advice what I am missing. Thank and love your video!
@grayfurnaceman
@grayfurnaceman 10 лет назад
First, what was the original problem? Does the compressor not run? Does it run and not pump? GFM
@utube9139
@utube9139 10 лет назад
It was running yesterday after changed out the dual cap.( reading below spec.) Got call back this morning unit not running at all. Can it be a HPS OPEN. Thanks for your advice. I am a newbie tech.
@grayfurnaceman
@grayfurnaceman 10 лет назад
The HPS (if it has one) is a low voltage control. The contactor should be deenergized if it is open. GFM
@hg2.
@hg2. 11 дней назад
Wow ... I'm sure that could flummox the journeyman HVACer. Thanks for making.
@stevennahulak6768
@stevennahulak6768 7 лет назад
Since you measured around 90 amps LRA and you stated that if you held in the contactor in, the thermal overload of the compressor will trip. I understand that, but why does't the circuit breaker trip?
@grayfurnaceman
@grayfurnaceman 7 лет назад
The circuit breaker is a slow opening circuit protection because it is normal for the compressor to draw 3 times RLA on startup. The internal overload is mounted in the windings of the motor, so it senses the overload (on the compressor only) very quickly. Remember the breaker is sized for the total ampacity of the appliance +25%. The overload is sized only for the compressor. GFM
@earthsign28
@earthsign28 4 года назад
Have you seen a locked rotor compressor trip the breaker? I checked the windings on the compressor and they weren't grounded and the compressor wouldn't start. The capacitor was good as well.
@grayfurnaceman
@grayfurnaceman 4 года назад
Yes. Sometimes the overload opens, sometimes a fuse or breaker kicks off. GFM
@clintoneal
@clintoneal 10 лет назад
Yes but it wasn't cut off on low pressure gauge pressure 70/240 odb=80f r410asystem pulling 168lra rate at 158
@grayfurnaceman
@grayfurnaceman 10 лет назад
Are you sure it is not going off on low pressure? That low side is pretty low. If the pressure switch opens, the contactor will open and close rapidly if there is no short cycle control and the compressor will probably not start due to unequal pressures. The amp draw is close enough to LRA to be a locked rotor and not shorted windings. Hope this helps. GFM
@clintoneal
@clintoneal 10 лет назад
I had a similar problem yesterday but my compressor was drawing over the LRA and it was short cycling on and off on and off to the point where it's about to cause premature failure to the contactor so what's the deal there GFM?
@grayfurnaceman
@grayfurnaceman 10 лет назад
Do you mean the contactor is short cycling or the compressor overload? GFM
@hardcooling
@hardcooling 11 лет назад
I like the way you explained that Keep the good vids coming . Thanks for sharing
@waltonpha
@waltonpha 11 лет назад
For the most part you are very good a helping us new guys learn how to do thing right but. Ok Locked rotor compressor meads new compressor?
@davidl112
@davidl112 5 лет назад
Yes
@AllEnemiesForeign_AndDomestic
@AllEnemiesForeign_AndDomestic 8 лет назад
I digress and agree with the information in the video my comments were only for open forum discussion not a direct criticism of the video or it's instructional value it was a great video and the quickest way to trouble shoot a compression problem
@grayfurnaceman
@grayfurnaceman 8 лет назад
Thanks for the thoughts. GFM
@gerardomireles122
@gerardomireles122 8 лет назад
cool thanks again only one that question to that effect where is the C from the compressor connection on the contactor on t1 or t2 let me know because in different ways connect in t1 on other ways the C connect on t2 is difficult understand I need to know there is the right thanks
@grayfurnaceman
@grayfurnaceman 8 лет назад
Depends on the manufacturer. C is often not disconnected by the contactor. There is no right or wrong way. GFM
@olzhasbekzhanov5216
@olzhasbekzhanov5216 6 лет назад
What if I replace compressor with 84 LRA to lower 45 LRA compressor?
@grayfurnaceman
@grayfurnaceman 6 лет назад
Why? The replacement compressor is 1/2 the size. GFM
@CHRISDOESHVAC24
@CHRISDOESHVAC24 Год назад
9years later great video !
@jamespalmer7325
@jamespalmer7325 7 лет назад
Trouble shoot tv parts.
@pinoyinvegas
@pinoyinvegas 9 лет назад
what if the reading on LRA is higher than 92 let say 120 what does it mean.
@grayfurnaceman
@grayfurnaceman 9 лет назад
blue moon Probably, there is a defect in the compressor windings. GFM
@Froggability
@Froggability 4 года назад
2:20 he's immune to electric shock by the looks :)
@naturestrail2296
@naturestrail2296 Год назад
He didn't get shocked because he didn't touch the metal contact 🤔
@mpurecat4155
@mpurecat4155 3 года назад
Boosters or hard starts that are aftermarket i despise. Some units come with one already on it, but in my experience if you need to leave an aftermarket booster in the unit the compressor is done. If after the one or two boosts you turn power on and off and each attempt with the boost not attached the compressor starts then that’s fine, it’s possibly just been many months the unit hasn’t been operational. my experience with aftermarket boosts being left attached, if it’s the only thing between a compressor operating and not operating, you’ve already crossed that point where the compressor should have been replaced. anything at that point is going to be a downhill decline of the performance efficiency of the AC unit. maybe you extend the life of the unit by 1 or 2 years, but from my experience, the system efficiency is gonna have dropped before reaching that point, and having that boost on might cause it to operate but you’ll be noticing the unit is running a few to several hours more each day of use for that 1 to 2 years.
@grayfurnaceman
@grayfurnaceman 3 года назад
I would certainly agree that the use of an aftermarket start kit has limited value. It is extending the life of a unit close to replacement. As for the loss of efficiency, I see very little change from the equipment efficiency when new. Usually, the failure to start is from bearing wear that has some, but very little relation to system efficiency. GFM
@mpurecat4155
@mpurecat4155 3 года назад
@@grayfurnaceman the efficiency i speak of would be related to secondary issues that may have caused bearings wearing out faster, i.e. refrigerant charge, dirty/contaminated refrigerant, high head pressure, etc. what i mean by lack of efficiency is more of the unit as a whole. if the compressor bearings wore out because it was pretty old then yeah not generally gonna see efficiency issues, but if the unit is maybe less than 12 years old in an environment where it’s only used for maybe 3 months of the year and if capacitor and electrical are ok, then chances are secondary issues caused the compressor to prematurely wear. For instance a unit that was grossly overcharged one year by some other company and for the next 4 years the tenant mentioned the unit was running non stop but never bothered telling the landlord. Head pressure was very high, compressor running non stop and high compression ratio was putting more stress on the compressor as well. the unit would give just enough cooling to be ok but it would run almost all day vs. before where it would only run for 3 to 5 hours. I do agree with your statement about efficiency, but I think it would be more of a case by case basis. more often than not i get caught up with failed compressors that aren’t that old, i haven’t come across many service calls for older ones so that’s also affecting my answer.
@celestialdream49
@celestialdream49 4 года назад
Great video - Thank you. Please make more videos
@grayfurnaceman
@grayfurnaceman 4 года назад
I do at least one a week. GFM
@Guyhakverdi
@Guyhakverdi 8 лет назад
Can compressor have locked rotor and be burn out? I was troubleshooting a unit 2 weeks ago ,and I checked the unit was pulling LR amps. First, I checked the windings with my fieldpice ohmmeter numbers did not quite match. Second, I used my Supco insulation tester which showed bad. Fieldpiece ohmmeter did not shown any continuity to ground. I ended up replacing the ac , and flush the system with R11 and put suction line filter. But I actually was not sure whether it was a burn out or not. I tried to smell but it was not really strong.
@grayfurnaceman
@grayfurnaceman 8 лет назад
I can. The internal overload allows the compressor to start every time it cools down. This puts a load on the winding insulation. Eventually, it has to break down the insulation. I would have done what you did. GFM
@almnetx
@almnetx 8 лет назад
Most of the time, when windings are not giving good ohm numbers, the compressor needs to be replaced. Yesterday i had a case like that where the compressor was giving bad winding lectures and the capacitor was bad too. I replaced the capacitor, switched on the A/A. One of the terminals overheated, maybe because locked compressor, gone loose and made contact with the piping, making short circuit with the grounded piping and leaking all the gas. The compressor didnt show continuity to ground or short circuit between terminals, just did not show known ohm values.
@jameswestii454
@jameswestii454 2 года назад
I’ve got a 10 year old Rheem heat pump that as soon as it gets the call for heat or cool, it pops one of the two fuses in the disconnect or trips the breaker. The outdoor fan gets barely enough power to turn the blades a 1/4 turn. I replaced the contractor and same problems. I take the outdoor fan motor out of the loop completely and same problem. Ohm out compressor at its plug and it’s fine (OL).
@grayfurnaceman
@grayfurnaceman 2 года назад
You have a dead short to ground. Baring a wire contacting ground, I am betting the compressor is shorted to ground. Unplug the compressor wires and check again. GFM
@jameswestii454
@jameswestii454 2 года назад
@@grayfurnaceman - That was the very first thing I did. Run, start and common pins on compressor to ground and all (OL). In fact I rechecked it yesterday. I have checked every single wire in the outdoor unit thoroughly.
@grayfurnaceman
@grayfurnaceman 2 года назад
@@jameswestii454 Remove and isolate all wires to the compressor. Then turn on the power. Ohmmeters do not always tell the tale. GFM
@truthfiend6909
@truthfiend6909 6 лет назад
love your videos sir!....why did it not trip the breaker tho with that very high amperage?...does it mean it tripped the thermal overload before the breaker ?... thanks !
@grayfurnaceman
@grayfurnaceman 6 лет назад
Breakers are delayed action devices. Especially the HACR ones for A/C units. Usually, the internal overload will cut off first. GFM
@truthfiend6909
@truthfiend6909 6 лет назад
thanks again for the knowledge :)
@mohammedkratos4352
@mohammedkratos4352 7 лет назад
hello grayfurnaceman... some compressores don't wrote the LRA??? like Hitachi model 1000EL what can I do????
@grayfurnaceman
@grayfurnaceman 7 лет назад
If it is drawing 5 times the rated load, it is locked rotor. GFM
@mohammedkratos4352
@mohammedkratos4352 7 лет назад
grayfurnaceman thank you.. how can I know ohming 3ph compressor and ground short???
@grayfurnaceman
@grayfurnaceman 7 лет назад
3 phase will have the same ohm reading on all 3 windings. Check from winding to shell of compressor. Should be no continuity. GFM
@zack9912000
@zack9912000 5 лет назад
Hard start kits are a sign of a dying compressor
@grayfurnaceman
@grayfurnaceman 5 лет назад
Agreed GFM
@EVILMADBASTAD
@EVILMADBASTAD 11 лет назад
Another great video, thanks GFM
@sajidrehman860
@sajidrehman860 6 лет назад
Good Explanation dude thanks ❤️
@grayfurnaceman
@grayfurnaceman 6 лет назад
Welcome GFM
@Mobileunit6
@Mobileunit6 9 лет назад
great video
@ugenziring
@ugenziring 5 лет назад
The best
@Ihandledit
@Ihandledit 6 лет назад
lol
@tspriggsabq
@tspriggsabq 9 лет назад
Why check anything else once you know you have Locked Rotor Amps? Just sayin.'
@grayfurnaceman
@grayfurnaceman 9 лет назад
+Tim Spriggs You could have a failed run cap. Also, the compressor is a very expensive part. Be sure you have checked everything. GFM
@tspriggsabq
@tspriggsabq 9 лет назад
gotcha! I'm just studying HVACs on my own. it's fascinating. One of the best inventions too!
@b-riair9114
@b-riair9114 6 лет назад
grayfurnaceman I hope the one drawing 119 amps the other day didn’t just have a bad run cap .. live and learn I guess I never knew that would case locked rotor amps they never mentioned that in school
@octobertravler1965
@octobertravler1965 9 лет назад
thanks love your vidios
@grayfurnaceman
@grayfurnaceman 9 лет назад
+Andrew Riner Welcome GFM
@AllEnemiesForeign_AndDomestic
@AllEnemiesForeign_AndDomestic 8 лет назад
And why is that compressor LRA? I see all these videos trouble shooting but nobody knows why it fails let me tell you something my friend those compressors last forever if installed and maintained correctly and that's the true answer! That's real trouble shooting diagnosing the whole problem and in the end your changing out the whole system with duct system and upgrading return air and the system is running like a champ piece work nowadays is terrible long term customer service anything from the 90s is outdated get ride or it
@grayfurnaceman
@grayfurnaceman 8 лет назад
Most compressors fail LRA. The 2 reasons for this type of failure are: Copper plating from air in the system (obviously poor install or service) and low charge that allows the oil to be pumped out of the compressor resulting in lubrication failure. I have worked on equipment that was installed from 1945 to present and I find that in most cases, the later equipment (of course with some low end exceptions) is better in quality. I would certainly not consider equipment made in the 1990s to be outdated. GFM
@AllEnemiesForeign_AndDomestic
@AllEnemiesForeign_AndDomestic 8 лет назад
+grayfurnaceman I was speaking in terms of the install not so much the machine almost every system has an undersized return in volume and surface area what we knew about airflow was wrong back then when it comes to flex duct plus these new high efficiency systems are real sensitive and you dig a real deep hole real fast when you try to piece them back together using 410a 14/16 seer coils and compressor technology not arguing just saying soon we won't even be using capacitors and contactors it will be inverter drives and variable speed
@stephanedoyon8531
@stephanedoyon8531 11 лет назад
Tanks
@Billy-rr7re
@Billy-rr7re 7 лет назад
what amps do you get when the capacitor is defective?
@grayfurnaceman
@grayfurnaceman 7 лет назад
Amperage will be locked rotor.because if the capacitor has failed, the compressor will not start. GFM
@Billy-rr7re
@Billy-rr7re 7 лет назад
thanks GFM
@jackslater230011
@jackslater230011 10 лет назад
What's a run-wire?
@grayfurnaceman
@grayfurnaceman 10 лет назад
There are 3 terminals to the compressor. One is common. One end of both the run and start winding is connected there. The other end of the run winding goes to R. The other winding is the start winding which has its end connected to S. Start is primarily there to start the compressor. The run winding has the majority of the electrical load as it powers the motor when running. Hope this makes sense to you. GFM
@Guyhakverdi
@Guyhakverdi 8 лет назад
Excellent demo!
@rocker8692
@rocker8692 9 лет назад
Good vid bud
@carlosmejia5728
@carlosmejia5728 11 лет назад
That coil looks clogged too !
@graycomputerman5946
@graycomputerman5946 10 лет назад
Actually it is quite clean. GFM
@clintoneal
@clintoneal 10 лет назад
Both GFM.
@grayfurnaceman
@grayfurnaceman 10 лет назад
Does the unit have a low pressure switch? GFM
@TJBandmore
@TJBandmore 10 лет назад
This is a great video. I'm pretty sure my compressor has a locked rotor - it has been making extra womping noise during startup for several months and now it just hums and overloads. Interestingly, I have a XE 1000 like the one in this video... should I replace it with the exact OEM compressor, or do people install new and improved compressors/controls in this case? Thanks!
@grayfurnaceman
@grayfurnaceman 10 лет назад
Go with the original on this one. GFM
@lohengrinknight
@lohengrinknight 7 лет назад
In the end, I couldn't understand what the problem was. I have that same problem with my compressor right now, it doesn't start. It stays cool to the touch after five minutes of the fan working. capacitor's fine and contactor is fine as well.
@grayfurnaceman
@grayfurnaceman 7 лет назад
If the capacitor is good, and power is available, the compressor is mechanically locked up. Most common failure of compressors. GFM
@lohengrinknight
@lohengrinknight 7 лет назад
grayfurnaceman Thanks for your reply. I hit it with a hammer, but it didn't start. I tested it with my meter and I get continuity in all three pins. Is there any other why I can try to unlock it and make it work? I read about some people using a rubber hammer, but I'm not sure if you need to hit it when the unit's working or when everything's off. Thanks!
@grayfurnaceman
@grayfurnaceman 7 лет назад
For 35 years I have tried using a hammer on a stuck compressor. Rubber, 16 oz, 8 pound. Never worked. The only possibility is to install a hard start kit. GFM
@jonathanthechristian5558
@jonathanthechristian5558 6 лет назад
grayfurnaceman I just installed a new compressor and this is occurring. How could this be?
@lucho3410
@lucho3410 6 лет назад
kiyonexus im facing same issue. Wondering if replacing booster pack will do the trick. Is there a way to test a booster pack?
Далее
HVAC compressor crankcase heater wiring
5:16
Просмотров 29 тыс.
Locked Compressors
20:13
Просмотров 115 тыс.
Watermelon magic box! #shorts by Leisi Crazy
00:20
Просмотров 32 млн
Это нужно попробовать
00:42
Просмотров 437 тыс.
HVAC AC Compressor Locked Up ( LRA )
9:25
Просмотров 119 тыс.
Troubleshooting and testing the HVAC contactor Part 7
5:13
How To Check & Replace An Air Conditioner Capacitor
8:52
Diagnosing a Locked Compressor 3D
10:02
Просмотров 64 тыс.
Diagnosing Locked Rotor Compressor
3:11
Просмотров 137 тыс.
Watermelon magic box! #shorts by Leisi Crazy
00:20
Просмотров 32 млн