How to Setup the Hydro MPC CU 352 Controller for Hydronic Applications Using Two Sensors on Manifold 

Grundfos
Подписаться 27 тыс.
Просмотров 9 тыс.
50% 1

In this video we will show you how to set up the Hydro MPC CU 352 control for a hydronic application. We will do this by using two sensors - one mounted on each of the suction and discharge manifolds - using analog inputs. The goal is to make the proportional pressure influence active in the system.
System Setup
• The system is currently set to constant pressure control mode (factory default).
• We'll switch the control mode to differential pressure and configure the sensors accordingly.
Steps:
1. Change Control Mode:
- Navigate to "Settings" - "Aerotek Primary Controller" - "OK".
- Select "Primary Sensor" - "Differential Pressure Pump" - "OK".
- This changes the system from pressure boosting to differential pressure control.
2. Configure Sensors:
- We'll clear an existing system alarm later in the video.
- Go to "Settings" - "Analog Input" - "OK".
- Change "Sensor 1" settings:
- Select "Measure Input Value".
- Choose "Differential Pressure Pump High" for measurement.
- Set the sensor range according to your specific sensors (consult the manual for details).
- Repeat the process for "Sensor 2" using "Differential Pressure Pump Low" for measurement.
3. Enable Proportional Differential Pressure Control:
- Go back to "Settings".
- Select "Proportional Pressure" - "OK".
- Enable proportional pressure control.
- Leave "Adaptation" set to "Squared".
- Adjust "Influence at Zero Flow" to 50% (you can adjust this value based on your needs).
- Verify "Max Flow Rate at QP Max" uses the existing pump curves.
4. Disable Unnecessary Functions:
- The current alarm indicates "water shortage." This is because the system hasn't started yet.
- Disable the stop function: "Settings" - "Secondary Functions" - "OK".
- Select "Stop Function" - "OK" (currently enabled) to disable it.
- You can watch a separate video on how to set up dry running protection (optional).
- Go to "Operations".g Protection" - "OK" and choose "Disabled".ctions" - "OK".
- Select "Dry Running Protection" - "OK" and choose "Disabled".
5. Set System Setpoint:
- Go to "Operations".
- Use the "+" button to increase the setpoint to your desired value (e.g., 15 PSI).
- Use the "+" button to increase the setpoint to your desired value (e.g., 15 PSI).
- Select "Normal" to initiate system operation.
6. Start the System:
- Select "Normal" to initiate system operation.
- Go back to the home screen.
Confirmation:
• The system should now display "Proportional Pressure Influence Active".
This video provided a basic overview of setting up proportional differential pressure control on a Hydro MPC system. Learn more about Hydro MPC: product-select...
#HydroMPC #ProportionalPressure #DifferentialPressure #ControlMode #SensorConfiguration #Grundfos

Опубликовано:

 

17 сен 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 7   
@nagarajnicholas4637
@nagarajnicholas4637 6 месяцев назад
Nice explaining sir thank you.. I have one doubt I'm also using Same Grundfos pump cu352 pv numbers not increase what to sir sv3.3 , pv0?? I training I want to interest please help me.
@grundfos
@grundfos 6 месяцев назад
Hello! Thank you for reaching out to Grundfos. Please contact our service team for questions on products at gfos.ly/6059pzz6b Thank you!
@user-yn8gm4xb2d
@user-yn8gm4xb2d 7 месяцев назад
Hi, is this settings applicable to all cu325? And my cu325 is newly installed the problem is we can't set correctly. Is this video I can copy the parameters?
@grundfos
@grundfos 7 месяцев назад
Hello! Thank you for reaching out to Grundfos. Please contact our service team for questions on products at gfos.ly/6059pzz6b Thank you!
@abdelrahmanalaa7558
@abdelrahmanalaa7558 8 месяцев назад
Hello, i have the same exact system, but i have a problem. This system is connected to 3 pumps, 3rd one i have shut off. And working on the other two pumps. The problem is that the controller does not switch between the pumps, i mean the 2nd pump is only working while the 1st isnt. While i have put both pumps on automatic and both pumps are same. Is the system designed for only one pump work while ?
@grundfos
@grundfos 7 месяцев назад
Hello! Thank you for reaching out to Grundfos. Please contact our service team for questions on products at gfos.ly/6059pzz6b Thank you!
@jonewatt
@jonewatt Год назад
How to alarm list A riset
Далее
Как мы играем в игры 😂
00:20
Просмотров 527 тыс.
Grundfos Webinar on Controls
4:35
Просмотров 7 тыс.
Grundfos UPS3 Variable Speed Pump - Plumber Install
7:14
Refrigeration: Low Pressure Control As Temp Control
25:22
Grundfos Dedicated Controls
3:51
Просмотров 718
#Danfoss VLT Micro Drive FC-51 Parameter Settings
8:01
Ремонт Grundfos scala2
4:13
Просмотров 8 тыс.
ENSAMBLAJE DE BOMBA VERTICAL MARCA CNP SERIE CDM
6:19