HVAC: What Is A Intermittent Pilot Ignition Control Module/Sequence Of Operation/Troubleshooting 

Jumper man Tech
Подписаться 100 тыс.
Просмотров 37 тыс.
50% 1

HVAC: What Is A Intermittent Pilot Control Module & How Does It Work? Intermittent Pilot Control Module For Gas Furnace/Boilers Explained
How to wire and install an ignition control HVAC
Intermittent Pilot Ignition Control Module Sequence Of Operation
HVAC Ignition Control Troubleshooting
=================================================
Sequence of Operation (Utec 1003-600a Series)
1. Call for Heat: The thermostat contacts close,
powering Terminal 2 on the G600.
2. Pilot Flame Checking: If the G600 detects the
presence of pilot flame (from the flame sensor)
when there should not be (i.e., before the call for
heat), the G600 will not operate.
3. Vent Damper Actuation: On models electrically
interlinked with a vent damper, the G600 powers
the vent damper motor. Once the vent damper
reaches its open position, the motor stops, and the
G600 is allowed to begin the prepurge (prepurge
models only) or trial for ignition.
4. Prepurge: The appliance prepurge fan or relay is
energized through the thermostat contacts. The
control delays for the 4-second prepurge before
simultaneously opening the pilot valve and
supplying a continual spark at the pilot burner
(models with prepurge only).
5. Trial for Ignition: During the trial for ignition, the
G600 energizes Terminal 1 and the spark
transformer, which opens the pilot valve and
activates the spark in an attempt to light the pilot
burner. If the G600 detects the presence of the
pilot flame within the trial-for-ignition time, it
proceeds to the run state. If the G600 does not
detect the presence of the pilot flame within the
trial-for-ignition time, it de-energizes all outputs
(locks out) and remains in this condition until the
thermostat is recycled. The G600AX and G600AY
have infinite trials for ignition and spark
indefinitely.
6. Run: If pilot flame is detected within the trial for
ignition, Terminal 3 is energized and the spark
transformer is de-energized, which opens the main
valve and shuts off the spark. The pilot valve and
main valve are kept open throughout the run state.
The control remains in the run condition until the
call for heat ends or until a flameout occurs.
7. Flameout: If, during the run state, the control
detects the loss of pilot flame, it de-energizes the
main valve within 0.8 second (flame failure
response time). The pilot valve is kept open, the
spark is re-established, and another trial for
ignition begins.
=================================================
Honeywell S8610U Universal Intermittent Pilot Module
Field service replacement for most Honeywell, Robertshaw, Johnson, and UTEC (HSC) Intermittent Pilot Ignition Modules. Provides electronic control of most intermittent pilot ignition systems used on gas-fired furnaces, boilers, and other heating appliances.
• Provides ignition sequence, flame monitoring and safety shutoff for intermittent pilot central furnaces and heating appliances.
• Provides 100 percent pilot gas shutoff if pilot fails to light; after 6- minute delay, trial for ignition is repeated. Ignition trial/delay sequence is repeated until the appliance lights or call for heat is removed.
• For use with Natural or LP gas.
• For use in single rod or dual rod/remote sense applications. Includes relay contacts for use with any intermittent pilot gas control string with maximum 1.0A pilot or 2.0A main valve rating; Honeywell VR8204, VR8304 or VR8345M combination gas control recommended.
• Functional equivalent of S86, S8600, S8610 and S90 modules.
• Includes spark cable adapters to allow field replacement of both Honeywell and competitive controls without replacing existing spark cable.

Опубликовано:

 

6 сен 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 90   
@rubensabeast
@rubensabeast 2 года назад
I understood how to troubleshoot these before the video but it was just steps never a meaning behind it, literally the best anyones ever explained this control lol love the vids
@JumpermanTech
@JumpermanTech 2 года назад
That is so awesome to read. Appreciate the feedback very much🙏 Glad you love the vids 🙃 Stay tuned for new videos every week! 🔧⚡
@stasanoffstasanov9224
@stasanoffstasanov9224 Год назад
@@JumpermanTech скажи какое напряжение подается на mv.pv?
@teklesenbetgebreamlak7365
@teklesenbetgebreamlak7365 Год назад
You are make it easy to understand how to troubleshoot, l have no enough words to say thanks, you are the best thankyou again
@pcakes1878
@pcakes1878 Год назад
ive been a licensed gas tech for years, but i only work on this stuff in the winter. Supermarket refrig keeps me busy all other times. its nice to have a refresher every now and then
@tylerr8083
@tylerr8083 Год назад
Excellent video. I was trying to understand this control and you made it so clear. Will help with troubleshooting. Cheers
@jasonjohnsonHVAC
@jasonjohnsonHVAC 2 года назад
The Honeywell S8610U does also have a separate flame sensor terminal. It is the spade terminal below the sparker. It has a little black wire coming from the controller and pre-wired to the terminal already. You remove it for a separate flame sensor and spark rod, or you can use the spark/ flame sense terminal as you described. It depends on the set up you have.
@dudemann8654
@dudemann8654 Год назад
Thank you! I've been searching for an answer for what to do if you have separate lines for spark and sense and you answered it. You're awesome!!
@zacharynolder3385
@zacharynolder3385 9 месяцев назад
Just wired one in today, was kind of confused while I was there, had no trouble with the diagnostic. But swapping a 2902 with one of the Honeywell controls had me a little stumped. Good call on that because I said the same thing.
@cruzruelaz
@cruzruelaz 4 месяца назад
Found a new resource, thank you
@Infowarrior-1776
@Infowarrior-1776 15 дней назад
Great video and clear explanation!
@mrtrek64
@mrtrek64 10 месяцев назад
Great viddeo, thank you. On the Honeywell control you remove the black jumper to use with 2 rod systems. Keep it in place for single rod.
@gregord2759
@gregord2759 7 месяцев назад
well done--it's a great explanation for the novice and pros.
@JumpermanTech
@JumpermanTech 7 месяцев назад
Thank you very much! Stay tuned for new videos every week 🔧⚡️
@chris27289
@chris27289 2 года назад
I tried to find info on this a while back. I'm planning on a custom project and this will help a lot.
@JumpermanTech
@JumpermanTech 2 года назад
Awesome! Glad you found this video helpful & good luck with your future project. Stay tuned for new videos every week⚡🔧
@flexortiz92
@flexortiz92 2 года назад
MY BROTHA BACK AT IT AGAIN! Keep doing a great job at this RU-vid my friend I’ve been in the field lemme show the channel some love
@JumpermanTech
@JumpermanTech 2 года назад
My brother Ortiz! Appreciate your support over all this time & thank you! Respect✊️ Stay tuned for new videos every week⚡🔧
@eriktorres9861
@eriktorres9861 Год назад
Thanks man, you're an excellent teacher.
@JumpermanTech
@JumpermanTech 7 месяцев назад
You're welcome & thank you! Much appreciated 🙏 Stay tuned for new videos every week🔧⚡️
@thesilentonevictor
@thesilentonevictor 2 года назад
Multi talented tech
@JumpermanTech
@JumpermanTech 2 года назад
My brother! Thank you! Appreciate the feedback & you watching 🙏⚡
@HalfPro
@HalfPro 6 месяцев назад
Flame sense signal (uA) comes on sense wire and not on ground terminal as said in the video. Sense current flows only if the ground wire is properly connected to chassis.
@williamserver4332
@williamserver4332 Год назад
Great video. I wish I had this info many years ago when I was new to HVAC.
@easyon12
@easyon12 Год назад
I'm 20 years into the biz and I say the same thing everyday!
@jmead6121
@jmead6121 7 месяцев назад
Thanks very Much I have the same model # ignition control on an York 300k gas rooftop unit only difference is the labels of terminals .mine shows MV - mv/pv - R1 rollout - TH - gnd buner - 24v gnd - sense - spark so ian assuming TH is my 24 v call Thanks again now i can go back fin trouble shooting no heat call
@lloydrmc
@lloydrmc Год назад
Thank you so much! My controller is a "UT" that looks almost identical to your example.
@JumpermanTech
@JumpermanTech 7 месяцев назад
Thank you! Stay tuned for new videos every week🔧⚡️
@playmusic972
@playmusic972 9 месяцев назад
hey this video was very helpful, well explained the operation. thank you so much.
@JumpermanTech
@JumpermanTech 7 месяцев назад
You're very welcome & thank you! Stay tuned for new videos every week🔧⚡️
@olivasurueta
@olivasurueta 9 месяцев назад
VERY GOOD EXPLAINED, ONLY IF YOU CAN PUT EXAMPLE IN LIVE
@JumpermanTech
@JumpermanTech 7 месяцев назад
Thank you! Stay tuned for new videos every week🔧⚡️
@jrh86
@jrh86 9 месяцев назад
Excellent 👍👍👍💯
@JumpermanTech
@JumpermanTech 7 месяцев назад
Thank you! Stay tuned for new videos every week🔧⚡️
@wd8557
@wd8557 2 года назад
Very well explained.
@JumpermanTech
@JumpermanTech 2 года назад
Thank you! Much appreciated. Stay tuned for new videos every week🔧⚡️
@spongklong508
@spongklong508 2 года назад
Thank you. Very imformative.
@JumpermanTech
@JumpermanTech 2 года назад
You're very welcome & thank you! Glad you found this video informative. Stay tuned for new videos every week⚡🔧
@shytown2406
@shytown2406 Год назад
OUTSTANDING very informative. What a main compoent on my Weil Mclain Gas Boiler that will go bad . for my home
@izzybell11
@izzybell11 2 года назад
Excellent presentation and tutorial. Job well done JMT.
@JumpermanTech
@JumpermanTech 2 года назад
Thank you very much! Glad you enjoyed the presentation. Appreciate the feedback🙏 Stay tuned for new videos every week⚡🔧
@marksiegfried
@marksiegfried Год назад
Excellent video, thanks for posting..
@JumpermanTech
@JumpermanTech 7 месяцев назад
Thank you! Stay tuned for new videos every week🔧⚡️
@zipperdingo6385
@zipperdingo6385 Год назад
Great explanation👍
@JumpermanTech
@JumpermanTech 7 месяцев назад
Thank you! Stay tuned for new videos every week🔧⚡️
@veganord047
@veganord047 10 месяцев назад
Thank you.
@JumpermanTech
@JumpermanTech 7 месяцев назад
You're very welcome! Thank you! Stay tuned for new videos every week🔧⚡️
@brandonpaul26
@brandonpaul26 8 месяцев назад
Excellent explanation 👌
@andrewfordpics
@andrewfordpics Год назад
Great helpful video...Thankyou
@JumpermanTech
@JumpermanTech 7 месяцев назад
Glad you found this video helpful 👍 Thank you! Stay tuned for new videos every week🔧⚡️
@leonlin4714
@leonlin4714 5 месяцев назад
Why does my boiler stop working when I plug in wire GND (burner)? But it works without plugging in this wire for long time.
@andreagate542
@andreagate542 2 года назад
Thank you for another great video…..So for flame sensor you want to try And achieve 3 µA corrrect??? The next step is A signal hast to go back to bored via the intermittent pilots burner ground In order to open the main valve???Is that same signal in Micro amps???? Many Thxs
@TitoGomez-ue8jw
@TitoGomez-ue8jw Год назад
Very well explained!!!
@JumpermanTech
@JumpermanTech 7 месяцев назад
Thank you! Stay tuned for new videos every week🔧⚡️
@raviyadav8743
@raviyadav8743 Год назад
Very helpful video 😊😊
@JumpermanTech
@JumpermanTech 7 месяцев назад
Glad you found this video helpful! Thank you! Stay tuned for new videos every week🔧⚡️
@luvdogsandhorses
@luvdogsandhorses 2 года назад
Nice explanation
@JumpermanTech
@JumpermanTech 2 года назад
Thank you! Appreciate the feedback. Stay tuned for new videos every week🔧⚡️
@yungchan8914
@yungchan8914 2 года назад
Thanks extremely helpful
@JumpermanTech
@JumpermanTech 2 года назад
You're very welcome & thank you! Glad you found this video helpful. Stay tuned for new videos every week🔧⚡️
@powerstroke1914
@powerstroke1914 9 месяцев назад
Is there a way to jumper the utec control to see if module is bad
@odishoodisho4904
@odishoodisho4904 9 месяцев назад
Thanks for sharing your experience… if we want to change the module we have to put the same module number or there is a universal module work with all? Thanks in advance
@ddteamrc6461
@ddteamrc6461 2 года назад
Question, why wouldn't the ignitor be clicking?
@salvenezia1817
@salvenezia1817 10 месяцев назад
My control only lights burner if I disconnect my 24vgnd. Then the burner light then shuts off after a sec
@odiferousmusky1299
@odiferousmusky1299 2 года назад
thanks Jumper Man!
@JumpermanTech
@JumpermanTech 2 года назад
You're very welcome & thanks for watching! Stay tuned for new videos every week🔧⚡️
@abelurrutia1192
@abelurrutia1192 2 года назад
Great video.
@JumpermanTech
@JumpermanTech 2 года назад
Thank you! Stay tuned for new videos every week🔧⚡️
@jasonjokiel7188
@jasonjokiel7188 Год назад
Great video!!!!!!
@JumpermanTech
@JumpermanTech 7 месяцев назад
Thank you! Stay tuned for new videos every week🔧⚡️
@litesp
@litesp Год назад
I have an early-90s Carrier 58GSC furnace that does not spark or flow pilot gas when the thermostat calls for heat. There is 28V going to the Ignition module. Could the problem be the Ignition module, igniter, electrode, electrode wire, gas valve. I'm thinking to start at the ignition module, but I'm not sure how to isolate and troubleshoot that. Would pilot gas flow if there is no spark? Please advise.
@MarioDallaRiva
@MarioDallaRiva 2 года назад
Bravo! You’re a natural at instruction. Very clear and thorough 👏🏻 ? Is that micro Amps listed on the unit cover (square waves)?
@RockoRocko-rz7kx
@RockoRocko-rz7kx Год назад
Yes
@Bolshevik337
@Bolshevik337 2 года назад
Thanks you so much.
@JumpermanTech
@JumpermanTech 2 года назад
You're very welcome & thanks for watching! Stay tuned for new videos every week🔧⚡️
@aifrisyad7491
@aifrisyad7491 Год назад
hello there, for the GND burner and 24V wire…where should i connect them from module into…thanks man
@mikepotter3802
@mikepotter3802 Год назад
How/when do you check the voltage across MV/PV and PV for 24V? During spark? At any time? What if you have no 24V (instead 4.0V) across here? My system is sparking but does not light pilot. I forced sense with a lighter and got MV to light briefly.
@isonlynameleft
@isonlynameleft Год назад
Awesome!
@JumpermanTech
@JumpermanTech 7 месяцев назад
Thank you! Stay tuned for new videos every week🔧⚡️
@alialhisnawi5673
@alialhisnawi5673 Год назад
Wonderful
@JumpermanTech
@JumpermanTech 7 месяцев назад
Thank you! Stay tuned for new videos every week🔧⚡️
@MB-zk7pz
@MB-zk7pz 11 месяцев назад
I'm sure I'll still forget when the homeowner is standing behind me slurping coffee w anxiety of wondering if I know what I'm doing n how much it's gonna cost n then his brother n dad come in too.
@JumpermanTech
@JumpermanTech 7 месяцев назад
😂😂😂 Stay tuned for new videos every week🔧⚡️
@jyphc1679
@jyphc1679 2 года назад
Hi JMT Can you do a AAON’s initial module ? Please thank you
@JumpermanTech
@JumpermanTech 2 года назад
Hello, I will look into that & try to make a video. Haven't came across that yet but I might be able to make a video using some photographs and wiring diagrams. Stay tuned for new videos every week⚡🔧
@user-hw6ws2cn9j
@user-hw6ws2cn9j 9 месяцев назад
What is terminal th-w on other control?
@CAn-hn1xz
@CAn-hn1xz Месяц назад
That's exactly what I want to know, reading abbreviations is impossible
@jesustommy4009
@jesustommy4009 2 года назад
👏🏻👏🏻✍🏻✍🏻✍🏻
@JumpermanTech
@JumpermanTech 2 года назад
🙏🙏🔧⚡️
Далее
Crucial Knowledge To Heat Pump Troubleshooting
14:15
Просмотров 29 тыс.
Fake watermelon by Secret Vlog
00:16
Просмотров 4,7 млн
How a Furnace Works - Furnace Sequence of Operation
17:51
Gas Furnace SPARK IGNITION Operation and Testing!
17:07
Honeywell Intermittent Pilot Training
14:15
Просмотров 84 тыс.
Gas Furnace Spark Ignition Control Troubleshooting!
10:48
Diagnosing a Locked Compressor 3D
10:02
Просмотров 60 тыс.