This was an overtime Saturday night service call on a kitchen ac that was not working. I found that the line 2 fuse was blown and there were a few issues that could have caused that, I got the unit running than I found that the indoor blower motor was going bad too. So I got them thru the weekend and we will submit a quote to repair.
To support my videos please visit either of the links below
For Patreon / hvacrvideos
For Streamlabs streamlabs.com/hvacrvideos
TOOL LINKS
Yellow Jacket stubby High side gauge amzn.to/2MoiM5G
Yellow Jacket low side stubby gauge amzn.to/2JYBKxV
FieldPiece JobLink probes amzn.to/2WfQTRI
Samsung Tablet amzn.to/2EOYL1U
Fieldpiece SC660 Wireless Swivel Clamp amzn.to/2JXji7I
For Optimizing my videos I use Tube Buddy
www.tubebuddy.com/HVACRVIDEOS
Please consider subscribing to my channel and turning on the notification bell by clicking this link goo.gl/H4Nvob
Social Media
Facebook / hvacr-videos. .
Instagram / hvacrvideos
For any inquiries please contact me at hvacrvideos@gmail.com

Опубликовано:

 

18 сен 2019

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 253   
@July4.1776
@July4.1776 4 года назад
This is by far the best HVAC channel on RU-vid!
@HVACRVIDEOS
@HVACRVIDEOS 4 года назад
Thanks so much bud! I dont know everything and there are many other techs out there better than I
@July4.1776
@July4.1776 4 года назад
I work in Ventura County and there is a huge shortage of technicians. Any company out here would die to get a hold of you. I own a very small company and technicians like you are very few and far between. Keep up the good work!
@DJSubAir
@DJSubAir 4 года назад
Chris you know why they say you are the best, its your attitude towards problems and your editing style is really good and through and easily understandable explanations of why you do things the way you do. Lately I have always been hearing in my head while I'm working away you saying "look at the bigger picture" lmaooo anyways thanks for all the hard work to bring us these videos
@hvacir9176
@hvacir9176 4 года назад
well there is no doubt, i have learned lot from him. he is the best
@lorensolares6277
@lorensolares6277 4 года назад
Yup his and hackfreehvac are the only 2 channels I consistently watch .. invaluable information
@SPIKEAdventure
@SPIKEAdventure 4 года назад
Man a chest mounted gopro would probably make your job easier by freeing up a hand. Keep the videos coming im loving them!
@fw1421
@fw1421 4 года назад
SGTGS I was thinking the same thing. A chest or head camera would be better.
@HappilyHomicidalHooligan
@HappilyHomicidalHooligan 4 года назад
Head cam would be better for us, we would automatically see whatever he's looking at as he's looking at it...
@jojomorgan8556
@jojomorgan8556 4 года назад
Yeah that would be nice for us but it would be a lot more editing and storage requirements on his end.. I'd rather have more videos than the better perspectives if it's a choice
@HappilyHomicidalHooligan
@HappilyHomicidalHooligan 4 года назад
@@jojomorgan8556 Not really, we are talking about replacing his tripod mounted camera with a chest or head mounted one. Same amount of video for Chris to edit, but his work would be much easier due to having both hands free while filming... We would also get better viewing angles since we would be able to see things from Chris's perspective without Chris making a better door than he does a window (no Insult intended Chris)...
@jojomorgan8556
@jojomorgan8556 4 года назад
@@HappilyHomicidalHooligan you must think he leaves the camera on constantly like a head or chest mounted gopro usually is.... I don't think he does... it would be more recorded footage due to the cam being always on ....
@Ligerty
@Ligerty 3 года назад
I'm an Hvac Engineer in the midwest and I just wanted to say your videos are so helpful. I've been a journeymen for only 2 years and there is still so much to learn. I don't work on Kitchen equipment but your general knowledge and tips are going to help me improve my trade and make my job way easier. Thank you uploading!
@jarheadshooter6452
@jarheadshooter6452 3 года назад
Pro tip, with the size of fuses you pull you really should use the smaller end of the puller. Once used to it, it will allow you more firm dexterity with the fuse. The large side of the puller are for fuses 1 inch or larger diameter.
@dantx4545
@dantx4545 4 года назад
You have a great work attitude "If you want something done right. ...." I am the same I would rather just do it instead of waiting for others
@tyhuffman5447
@tyhuffman5447 4 года назад
At 18:20 the belt is being sucked down into the sheave, replace the sheave and belt. The belt should never touch the bottom of the sheave, and that will ruin the mtr bearings. Almost forgot, memorize that sound, that is the sound a belt will make when it is riding too low in the sheave.
@proamlito07
@proamlito07 4 года назад
Thanks
@jojomorgan8556
@jojomorgan8556 4 года назад
Have to say that changing all 3 fuses is always a great idea I had someone who came to service our 3phase system change only the bad fuse and the compressor failed a week later... come to find out one of the "good" fuses was only passing half it's rated amperage and low-speed the compressor into a burnout (internal coils melted together from overheating)
@jth1699
@jth1699 4 года назад
What burns me about this type of call is that the unit went down on Friday about noon - then they wait till late in the day on Saturday to call ??? That usually triggers my aggravation surcharge...
@Ki113dbysw0rd
@Ki113dbysw0rd 4 года назад
No doubt. Luckily our company has a hilarious emergency call rate that keeps most of these at bay. One such occasion is that I had to go get 2 security cameras back online, only to find out once onsite (1.5 hour drive one way) that they had been offline for over a month. I guess their daily checks aren't so daily.
@miscbits6399
@miscbits6399 3 года назад
We used to get this all the time when I was a telco RF tech. Landmobile customers would have something fail on Tuesday but call it in 4pm Friday as they were leaving for Pizza, demanding it be fixed by Monday morning. I got paid overtime, but a 200 mile round trip against weekend traffic (all the shitty drivers come out to play on weekends) used to irritate me.
@lwangajohn3257
@lwangajohn3257 4 года назад
I get excited every time you upload, great video
@Maxxarcade
@Maxxarcade 4 года назад
Even though HVAC is not my field, I always enjoy these videos. Partly because it's electrical/mechanical tech, and also because it's nice to watch someone work that actually cares about what they are doing. It's a rare trait nowadays.
@mq1991
@mq1991 4 года назад
Whoa! Hey man! I havent seen a video from you in a long time. Long time fan! Hope all is well! Crazy to see you on this channel for some reason. lol
@Maxxarcade
@Maxxarcade 4 года назад
@@mq1991 LOL ya, I seem to bump into my fans on various tech channels a lot. I guess it just means we all like the same stuff. For the past couple years, I've been having to work a lot more than I used to in order to keep up with the rising cost of living. So I haven't had much time for hobbies. RU-vid has also gotten so strict with copyright stuff that I can't use random music and video clips that I enjoy to demonstrate equipment anymore. It's taken the fun out of making videos.
@inothome
@inothome 4 года назад
Stumbled across your channel about a year ago and it was very refreshing to see a professional that takes pride and actually tries to find the cause of a problem and not just throw parts at it. One quick note: always check a disconnect (or any device) for volatage to ground as well. Not just phase to phase. If that disconnect had one stuck blade you wouldn't have known that checking for voltage phase to phase.
@HVACRVIDEOS
@HVACRVIDEOS 4 года назад
Great point, I will be going live on RU-vid this evening 11/25/19 @ 5:PM (pacific time) to discuss my most recent uploads, and answer questions from email’s , RU-vid comments, and the Live chat come on over and check it out if you can. ru-vid.comlive
@texasrob1000
@texasrob1000 4 года назад
I try to let run for a bit and re amp because sometimes it looks good, then after it runs and I've left guess what the problem was a motor that amped good at first because it was cool from being off ..Great vids
@benjamintimmins1656
@benjamintimmins1656 4 года назад
I like how yall give back to the hvac community by uploading your hvac videos. It gives us techs something to go by and learn from. Thanks
@cranium33333
@cranium33333 4 года назад
Your approach to diagnosis is impeccable! Thank you for the great vids!!
@philliprivera7554
@philliprivera7554 4 года назад
I've been following you now for bit. Looking to get into the field after 15yrs of industrial maintenance experience. Noticed you are really knowledgeable, thorough, and meticulous in your work and explanations of all your work. I appreciate all the knowledge and experience you share with us. Keep doing what you doing. Thanks!!
@EverydayProjects
@EverydayProjects 3 года назад
I'd have a hard time not writing up a quote for just about everything on that unit. I realize that customers usually don't care if a unit is dirty or if the covers are bent (they just want it to work) but as a bit of a perfectionist myself, I'd want to walk away from each unit in pristine condition, including clean, neat and tidy. I'm not an HVACR technician, my skills lie elsewhere, but I've seen similar attitude from customers. They don't usually understand the equipment, and aren't concerned with aesthetics...just "is it working?" Great channel!
@jonosterman2878
@jonosterman2878 4 года назад
Every time I watch your videos I am struck by how well you teach. Info convey and delivery is not easy, depending on personality. I have had so many awful teachers in my life, seeing a good one is always striking to me.
@josephsantos7047
@josephsantos7047 4 года назад
Super excited for class to start next fall. I’m going to continue watching your videos until I start school, and during school try and help navigate through these systems with you! Thanks a lot!
@Losangeles1980
@Losangeles1980 4 года назад
You're the best instructor, I truly enjoyed watching your videos. Thank you!
@chriscooley906
@chriscooley906 4 года назад
Great stuff Stephens, I’ve been watching your channel for a while now and I totally appreciate your consistency and mythological approach to service, You mentioned a nearly 2 psi drop across the suction line drier which I was taught at 2 it’s time to change, I could also hear the bearings in that blower motor explaining the higher head pressure, GREAT WORK AS ALWAYS YOUR A ROCKSTAR!
@albertastorms
@albertastorms 4 года назад
How does a rooftop unit get so banged up like that? It is as if they somehow took it to a demolition derby!! As someone who is fond of keeping older units running as long as possible, this one needs replacement!
@GoatzombieBubba
@GoatzombieBubba 4 года назад
Could be hail damage...and old age.
@EnderMalcolm
@EnderMalcolm 4 года назад
If you think this unit is bad, my cousin worked at a Burger King, and they got the AC units replaced because they were shot. When the units were lifted off the roof with a crane, they literally fell apart like a cartoon. Every panel popped off and the guts of the units rolled off the flat bed going everywhere. If that wasn't bad enough, the newly installed units didn't work.
@buckwilson4167
@buckwilson4167 4 года назад
Man I don't know what it is with RTUs but they do get beat to hell. I work at a movie theater built in 04 and the RTUs are already worn more than logic would imply. 3 story building, no trees or anything else around, very limited roof access to personnel, and yet they just look like someone took a baseball bat to em.
@marcuscompton2375
@marcuscompton2375 4 года назад
Banged up likely from careless service techs I’ve discovered removing & mis-handling panels ... They have been know to also cause roof damage / leaks by this improper handling by drop corners on roof to end up cutting the roof materials ... Customer ultimately calls a roofer when it was likely actually caused by the initial careless hvac tech 😩👀😤
@jarheadshooter6452
@jarheadshooter6452 4 года назад
This is why my guys always carry a can of contact cleaner! Any resistance or capacitance can raise temps!
@samparnell2242
@samparnell2242 4 года назад
As an apprentice in the trade in Australia your videos are an awesome training resource. Yeah our voltages are different and we use Celsius but the fundamental idea is the same when it comes to things like fault finding techniques as shown in this video.Keep going with this awesome content, I for one will continue watching!
@tomh6779
@tomh6779 4 года назад
Yeah, that disconnect is junk. It’s resistive and heating up. It’ll probably burn up another fuse next time that unit is heavily taxed. Great vids! Keep em coming..
@IronWarrior1316
@IronWarrior1316 2 года назад
Nothing a little bit of maintenance couldn’t clear up. Some emery cloth to remove old grease and corrosion, some penetrating oil to lubricate the pivot points and dried grease, and new grease on the knife blades. 5-10 minutes of work and it would be fine.
@frankjackson2439
@frankjackson2439 4 года назад
Yes! Finally watched one of your videos right when it came out
@robertarnold6672
@robertarnold6672 4 года назад
Neat tip using the temp gun to measure temps at the terminal lugs on the disconnect. I will be adding that one to my bags of tricks. Yep, after watching many of your videos I have learned to never just flip a breaker on without making a few checks first. Another great tip on the fuses too. I didn't know about the bands becoming discolored when they overheat.
@johnsharkey1151
@johnsharkey1151 4 года назад
Love your videos amigo. Im coming up on 2 years in the streets and your "big picture" diagnostics are helping me a lot. Greetings from SW Florida!
@angelomacareno5392
@angelomacareno5392 4 года назад
John Sharkey same! Southwest florida!! 👍🏽
@johnsharkey1151
@johnsharkey1151 4 года назад
@@angelomacareno5392 who are you with?
@angelomacareno5392
@angelomacareno5392 4 года назад
John Sharkey modern services at the moment. Been with them for over 5 years.they’ve allowed me to get my hands on refrigeration and I’ve watched Chris for about 2 years and they’ve helped me a lot!!
@johnsharkey1151
@johnsharkey1151 4 года назад
@@angelomacareno5392 Yep I like the big picture diagnostics. I know a few guys who used to be at Modern but are elsewhere now. Im with TWC.
@hunterriley9904
@hunterriley9904 4 года назад
This guys pretty damn sharp if ya ask me. Know his stuff well. Keep up the good work!😎
@sergiobost4891
@sergiobost4891 4 года назад
Thanks. I always learn a lot from your videos
@HVACRVIDEOS
@HVACRVIDEOS 4 года назад
I will be going live on RU-vid this evening 10/14/19 @ 5:PM (pacific time) to discuss my most recent uploads and answer questions from the LiveChat, RU-vid comments, Emails, and Facebook comments come check it out if you can. ru-vid.com/video/%D0%B2%D0%B8%D0%B4%D0%B5%D0%BE-tB11ZTSHhhE.html
@burningdust
@burningdust 4 года назад
Glued to your vids for the past year. You have me considering a career shift from electrical to HVAC! One thing to point out about the disconnect. Though it's not a distribution breaker, still; when operating the switch, especially after a protection failure make sure the arc shoot covers as well as the cabinet door are closed and latched before attempting to close the switch. Good on you for operating it left handed. If it were a flashy new system I'd suggest a NEMA4 vs 3R disconnect considering the location and duty. Thanks again for the awesome content! Cheers!
@mr.c3928
@mr.c3928 4 года назад
Dang dude I learned something new !
@Aersix105
@Aersix105 4 года назад
My favorite ac guy uploaded a new one :)
@xelaju8
@xelaju8 4 года назад
Learning a lot, thanks. That was an old unit. Change out coming soon.
@JuanTodoli
@JuanTodoli 4 года назад
100% agree the way you conduct the business.
@icantsaywhat
@icantsaywhat 3 года назад
Man I wish they had that measure quick setup when I was doing hvacr everyday That is a nice setup andhelps out a lot
@watermanone7567
@watermanone7567 4 года назад
Great diagnosis. I am surprised that the local utility does not bear some responsibility for the low voltage. I worked for a Utility company in Mass for many years and we would not have gotten away with it. Also the variable adjustment sheaves should be done away with. After balancing a unit it is best to put solid sheaves on a unit. Many of them fail and get loose on the threads. I have done many of these in the past. Good call on the disconnect. That also can be caused by low voltage causing heat. You have great video's and are very thorough.
@donnierobertson3088
@donnierobertson3088 4 года назад
Great job again like always
@Aersix105
@Aersix105 4 года назад
Scotch brite works wonders on corroded contacts in various apparatus. Served well many years using them on the contacts and blades in 14.4 and 27kv distribution breakers :) there’s also a paste we used I can’t remember what it was. Looked like Vaseline. Kept them clean until the next maintenance schedule.
@incandescentwithrage
@incandescentwithrage 4 года назад
Dielectric grease is the Vaseline looking paste. It's job is to prevent further oxidation / corrosion. Your suggestion of scotchbrite is better than the idea of putting dielectric on the hot contacts. Scotchbrite will remove the oxidation, lower contact surface resistance and the excessive heating seen as a result. Dielectric is for use after the fix, not a fix in itself.
@Aersix105
@Aersix105 4 года назад
IncandescentWithRage exactly it’s for after the fix itself. We used that grease on the contact surfaces for distribution breakers plugging into 1200+amp bus bars. The aluminum was a whole different story. Penetrox is nasty stuff 😂😂 I got hazed a lot by a guy that wouldn’t let it go after I was there for a year. Dumped a pint of penetrox in his toolbag. Never messed with me again 😂😂😂
@Aersix105
@Aersix105 4 года назад
IncandescentWithRage all the stuff we used was from DOW. I think the part number for the grease was 111 can’t remember.
@Ki113dbysw0rd
@Ki113dbysw0rd 4 года назад
Definitely, always gotta cover your butt and not just "throw in a fuse and see if it blows again"! Doing something very different myself, I took out an entryway lighting circuit once by mistake. Luckily I had records of my whereabouts and the timeline of events, because a few weeks later a call came in from corporate about that location, saying that I had blown the main breaker and all personnel had to evacuate. That obviously didn't happen, but corporate had no idea. Only thing I can think of was that it was a holiday weekend (another FMF) and they wanted to head out early. They had started trickling out long before I had popped that one circuit, and the last of them actually kicked me out at about 3pm because "they were looking to close up early that day". Some places just see a target painted on your back lol. Love the videos!
@HappilyHomicidalHooligan
@HappilyHomicidalHooligan 4 года назад
NEVER just "Replace the Fuse/Reset the Breaker and just see what happens"! Fuses/Breakers blow because Electricity is going somewhere it shouldn't be in a hurry (Short/Ground Fault/Dead Short) and that is going to either damage equipment, start a fire, Hurt/Kill someone or some combination of All-of-the-Above! Always use a Circuit Tester/Multi-Meter to find the problem before Reseting the Breaker/Replacing the Fuse... I speak from Painful Personal experience, an "Electrician" reset a Breaker without finding out why it was tripping at a place I briefly worked and I got tossed 15 feet. I rested my hand on the case of a Deli Slicer as I turned it on (my way of making DAMN Sure my hand was nowhere near that blade) and it had a Dead Short in it...I got tossed 15 feet and ended up in the ER for observation, the breaker blew again, the slicer got even more damaged from the internal arc and the Idiot "Electrician" got fired for Negligence...
@studyallthetimeallthetime8473
@studyallthetimeallthetime8473 4 года назад
When I grow up in HVAC I want to be just like you. 1st year apprentice, unfortunately my school is not hands on.
@analogmoz
@analogmoz 4 года назад
I finished school in June 2019 -- they tried to make things as hands-on as time and curriculum would allow-- but while you're in school just absorb what you can. The hands-on is waiting for you in the field in huge amounts!
@milwaukeephil2548
@milwaukeephil2548 4 года назад
Chris. With the service panels off you are not getting correct airflow (pull) through the condenser coils. The air will take the path of least resistance and that’s not through the coils. That accounts for your high head pressure issues. Before I start talking restrictions I’d run the unit under design conditions which is completely sealed up panels.
@milwaukeephil2548
@milwaukeephil2548 4 года назад
History ... Also, I limited (no longer in the biz now) my run time without the panels in high ambient temps. In the old days of belt driven compressors (which I had my share of repairing and replacing with Hemetics), the motor's heat energy was not mixed in with the freon, so high temperatures and moisture levels were manageable and at worst resulted in frozen TXVs. Once we combined the high temps of compression + windings within the same shell, the reaction of H2O and CCL2F2 (R12) started to create HCL and there were a lot of early compressor failures due to the lack of proper understanding of dehydration and the acidification of oil. Those earlier guys I worked with used old refrigerator compressors as vacuum pumps or simply purged out the air. It was thought early on that the Hemetics were the failure point. But once compressor manufacturers starting analyzing compressors coming back for warranty replacement, they identified the acidification of oil issues, and the industry responded with better training methods of dehydration and 2 stage vacuum pumps, micron-meters, changing filter/dryers once opening the system, limited exposure time left open. When I taught HVAC I no longer referred to it as "evacuation" but instead used the word "dehydration" as that in fact is what we are doing. Anyway, long way of saying, minimum time of that compressor being exposed to high head temps saves oil life and seized compressors down the road. It's good to watch someone like you who understands what he's doing and not just swapping out parts. So many of the field techs who came in for my classes (usually sheetmetal HVAC guys) had no understanding of what they were doing from an analytical standpoint.
@dand5593
@dand5593 3 года назад
12:20 an amp measuring on each one was nice to see
@analogmoz
@analogmoz 4 года назад
Yes! New content! This series is, (hopefully,) lowering the time I am super-ignorant at commercial refrigeration.
@palamidi13
@palamidi13 4 года назад
You are the BEST!
@miscbits6399
@miscbits6399 3 года назад
Electrolytic caps tolerances are generally -20 +100% = meaning if it's only 10% down I wouldn't worry about it. They're primarily there for power factor correction
@fighkb
@fighkb 4 года назад
Good video
@lwilton
@lwilton 4 года назад
I suspect the main problem in blowing the fuse was a dirty or arcing knife in the disconnect switch. All three of those fuses were hot on top, and the insulation on the wires into the disconnect, especially the center one, looked like they had been really hot. Obviously there were other problems that may have contributed.
@alvaroleguizamon1303
@alvaroleguizamon1303 4 года назад
also, the suction pressure its always different from one stage to the other, in some carrier, most of them, there is a top evap coil and a bottom coil, one of them , mostly the bottom one has a lower suction due to poorer airflow. that unit wasn't low in freon or had any restriction. all electrical, check the downstairs breaker.
@joestinson7195
@joestinson7195 4 года назад
great video
@newls1
@newls1 4 года назад
amazing tech. wish you were local to me
@lsx_moe
@lsx_moe 4 года назад
I cant wait to get out of residential and jump into a internship for a large commercial refrigeration company this year
@alexanderlewis239
@alexanderlewis239 4 года назад
A few years ago i did this kind of work,, mainly TRANE package heat pumps,,, a job i miss,, it was very enjoyable,,.. i experienced all sorts of problems on units much older than these,, some problems were caused by people, like reconnecting the phases the wrong way , causing the fan to turn the wrong way and delivering much less air.. Another problem that stuck in my mind,, having a kitchen exhaust fan blowing , geasy air onto the condenser coil , insulating it with grease , reducing its effectiveness in the summer....i could go on,,,R22 has gone now, ,, i am not too sure what has replaced it in new units,, probably R32 ,, certainly not R407C which had problems of it own..... Thankyou for the video very enjoyable...
@EnderMalcolm
@EnderMalcolm 4 года назад
My dad was the kind of guy who, when we blew a fuse at our old house, he replaced it and turned the breaker right back on without bothering to check why it blew, which happened to be because the power consumption of both an air compressor and the florescent lighting was too high for the fuse. Needless to say the second fuse blew instantly, and so on until we were out of fuses. it was only after we had to make a trip to the hardware store and buy new fuses that I finally stopped him, unplugged the compressor, and then let him replace the fuse. After that I made sure the lights were off before the compressor was plugged in. Surprise surprise, the fuse didn't blow. I think new fuses cost us 20$ or more, but the look on his face was priceless when I got the thing working by turning off a lightbulb.
@700up700up
@700up700up 4 года назад
Noticed a wire in front that had the insulation rubbed off, probably shorting against the cover
@DeeJaySpy
@DeeJaySpy 4 года назад
I know anyone would have already mentioned it but ... as you test the disconnect switch to be really dead , you should test to ground , not to other phases. Because if one phase still remains powered and the other two would be disconnected you dont get a closed loop. Therefore (like you would be ground while touching) better test to ground.
@denisohbrien
@denisohbrien 4 года назад
when you checked the disconnect@7.35 .. check both sides of the fuse!! I have been caught out before where some idiot has wired the feed into the fused side of the disconect . (Here in the UK , and it was a MEM disconect where you cant open the cabinet without swinging the handle to off.) luckily my paranoia caught it with a meter before I stuck my fingers inside :)
@cademitchell8897
@cademitchell8897 4 года назад
First😎 haha but for real tho I love your vids I'm an apprentice rn and watching your vids help me to learn and impress my boss keep up the good stuff!!
@engineer1793
@engineer1793 4 года назад
I had the same issue Chris. Blown fuse condenser fan motor was no good and the terminals in the disconnect were lose
@GradertJ
@GradertJ 4 года назад
You can also measure voltage drop across the disconnect to determine if it's causing a problem.
@GerryMetrillo
@GerryMetrillo 4 года назад
The best! 👍
@SurRon-GLE
@SurRon-GLE 4 года назад
Bro your the man
@HVACRVIDEOS
@HVACRVIDEOS 4 года назад
Thanks bud!
@broderickclayburn
@broderickclayburn 4 года назад
I love ❤️ your video
@i8twizlers
@i8twizlers 4 года назад
Temperature rise and temperature drop across the coils is the only other thing I would have done. Good work my brethren!
@i8twizlers
@i8twizlers 4 года назад
Low suction could have been the bad motor bearings and pulley+belt, and don’t forget the return grills. Slightly high head could be the condition of the unit as you said.
@sparkydave2783
@sparkydave2783 4 года назад
Always, always, always change all three fuses on a three phase system. You can be sure that AT LEAST two fuses have carried some degree of fault current where star (wye) or delta connected loads are concerned. In the absolute worst case, during a fault, the ‘sand’ in the HRC fuse can start fusing together to form a ‘tunnel’ of glassy sand but the element doesn’t break. Imagine you replace only the ‘failed’ fuse, but leave the ones with the forming glass ‘tunnels’. Next time the fuse is called to clear a fault, the element ruptures but the sand cannot fall in to quench the arc. Now the fun begins..........the arc can (and does) burn out of the fuse body and very quickly (within a couple of cycles) propagate into a full three phase arc flash within the disconnector. Imagine you were just flicking the equipment back on to test and a fault remained in the plant. Now you are facing an ‘arc in a box’. Always replace all three fuses. Always close the gear before energising.
@sparkydave2783
@sparkydave2783 4 года назад
Thanks Chris! I sent you an email on the same topic too 😉
@44R0Ndin
@44R0Ndin 4 года назад
Arc flash is no joke, at best it's a good way to make you feel like your eyes were sandblasted, at worst it can kill you. Never seen one in person, but I have seen the videos. It's literally a constant explosion fueled by electricity. Some rocket engines use this phenomena to heat propellant, they're called Arc-jets. Mostly it's thought of as a low-thrust system for propelling satellites in the vacuum of space (too much power needed to create enough thrust to push something off the ground, but just putt-putting around in space is easy with a few 10s of kilowatts of solar power). The best part is that you can use just about any liquid as propellant, provided it won't freeze or boil in the tanks and is somewhat chemically neutral. I think there's a company designing one that runs on Water, but you could use Ammonia or Hydrazine if you wanted a little more performance per kilogram of propellant.
@HVACRNorth
@HVACRNorth 4 года назад
good vid
@HVACRVIDEOS
@HVACRVIDEOS 4 года назад
Thanks!
@marcuscompton2375
@marcuscompton2375 4 года назад
When you initially turned the unit on, it did squeal a second as if a belt or bearing had an issue and sure enuf you were lead back to re-check ... Great Job ... Also, when you temp checked the center fuse I wonder if that high temp was ultimately being generated by the blower components ?
@MoraFermi
@MoraFermi 4 года назад
The US electrical code, especially the connectors and fuses give me heebie-jeebies. This whole thing would be completely illegal in EU.
@EnderMalcolm
@EnderMalcolm 4 года назад
It's not exactly a brilliant setup, but at least there actually is a fuse and a disconnect. Sadly stuff is either imported or so cheaply made that it hinders the progress of safety around electricity. You could get safer systems, but it would cost you more money.
@HappilyHomicidalHooligan
@HappilyHomicidalHooligan 4 года назад
Basic Electrical Circuits are simple. Just remember, power must always return to the panel for a Circuit to work properly [leaves on the Hot (Black) and returns on the Neutral (White) for 120V circuits and leaves on Line 1 (Black) and returns on Line 2 (Red) in 240V circuits]. Remember that and you should be able to use a good How To book/You Tube video to wire any circuit in your home safely and to Code (If you're the Home Owner, get a Permit from the City and the Inspectors will insure that it's done Legally and Safely)... It's when you get into Programmable Logic Controller (PLC) and/or Relay Logic circuits and 3 Phase Motor Control that it can get confusing...
@keepthinking2666
@keepthinking2666 4 года назад
Hahaha at 1:30 I was like blown fuse, from bad compressor, 🤣😭 I have 7 of these units on my roof and they suck
@mysock351C
@mysock351C 4 года назад
Pretty amazing how long some of those will keep trucking for. Even seen some older Carrier and Lennox units out by the coast keep going even after just about all the fins have rotted off the condenser. Just a bunch of bare copper tubes and rust.
@skasy8440
@skasy8440 4 года назад
even though i dont understand squat, keep them comin...*
@davidgiroux1652
@davidgiroux1652 4 года назад
Hi there, I think you are doing a great job with your informative troubleshooting videos! I would just make one request. Would you mind avoiding tightening live electrical connections on your videos where possible? I find many people become complacent or loose focus while diagnosing live electrical and it is always better to take a few minutes to shut down the power upstream of a disconnect beforehand. I'm in Ontario and we are required to wear high voltage gloves while doing any sort of live work (including voltage testing). We still have fatalities due to electricution each year in most of our major cities, usually with the high voltage gloves found on or near the unit they were servicing. Keep up the good work!
@caseygearhart2227
@caseygearhart2227 4 года назад
Dude i envy your intelligence. I work with a few different leads and youve shown me there is such a thing as qaulity of intelligence
@Kowalskithegreat
@Kowalskithegreat 4 года назад
I really enjoy these videos. I've been looking into getting into this field from auto mechanics, I already do a lot of reefer and its one of my favorite kinds of repairs/service, I enjoy finding and solving complex problems I just think automotive is kind of a BS field. would love to get into a union somewhere or something and do their whole apprentice>journeyman deal. i know atleast that the electricians union here is doing apprenticeship's and classes etc i need to link up w whatever union does this kind of work in my area
@FlyEaglesFly19111
@FlyEaglesFly19111 4 года назад
Ahhh..back to the old weathermakers..the suspense is killing me..
@5280guy
@5280guy 4 года назад
The condenser door where you were testing was still open some, couldn't that drive the head pressure up since its not fully pulling through the condenser when you dont have the door on all the way?
@treverkirk8110
@treverkirk8110 4 года назад
thorough troubleshooting for sure, excellent vid man. I do have to ask though, did you expect nothing less than for those contactors to look new? lol
@Eddy63
@Eddy63 4 года назад
Your vid is exactly one strong Bloody Mary long ... Which is perfect ... Lol ... Good one ...
@fnordingers
@fnordingers 4 года назад
I would like to see a Video about the fieldpice device. How to they work? Do they pinch the tubes or detect it thru the copper? What Do they measure? I'm not a hvac guy, just some random tech interested dude who like to see you diagnose some random machines :)
@danbrit9848
@danbrit9848 4 года назад
Ok so I've bin watching your channel for a week of bing ...I love machanical stuff and electrical and em at a hobby level of skill...shuld I go to school for this...the only thing is I don't want triangle roofs ...can you only work flat roof stuff by chance
@HVACRVIDEOS
@HVACRVIDEOS 4 года назад
We need all the help we can get in this trade I will discuss your question on my Livestream tonight , I will be going live on RU-vid this evening 12/16/19 @ 5:PM (Pacific Time) to discuss my most recent uploads and answer questions from emails, the chat and Facebook come on over and check it out if you can. ru-vid.com/video/%D0%B2%D0%B8%D0%B4%D0%B5%D0%BE-_20hGnjjK44.html
@danbrit9848
@danbrit9848 4 года назад
@@HVACRVIDEOS thank you I'll be there :)
@abpishark1973
@abpishark1973 4 года назад
Mentioned putting dielectric grease on it at 13:06 to make a better connection, though wouldn't that do the opposite? Used to think dielectric grease would improve the connection, though I've heard it can only help lubricate and protect connections from corrosion or arcing. Would be good to hear your experience with using dielectric grease on connections.
@HVACRVIDEOS
@HVACRVIDEOS 4 года назад
It's a temporary solution to the disconnect knives not making connection. I personally feel that the grease will attract sand and cause more problems in the long run
@keepthinking2666
@keepthinking2666 4 года назад
Put your black lead in the screw hole and work one lead in the hand
@johnbennett6826
@johnbennett6826 4 года назад
I hope you are going ok with this Coronavirus going around
@andyg5004
@andyg5004 4 года назад
System of lugs is bad and bare wires tightened is not good. I prefer to use ferrules and crimp them and then tightened into the lugs.
@edgardotorres7551
@edgardotorres7551 4 года назад
I’m still learning and HVAC kind of scares me lol
@keepthinking2666
@keepthinking2666 4 года назад
Always got to split those, if you think those have allot of problems you should see mine lol, they make those look new
@carl_h
@carl_h 3 года назад
Corrsion on the middle input terminal
@shadowsiren3058
@shadowsiren3058 4 года назад
Looks like that unit haven’t been touched in a long time
@adamuser5657
@adamuser5657 4 года назад
Can you do a video with examples on how you quote repairs
@tommyscottii9265
@tommyscottii9265 4 года назад
I see there is an issue with getting fuses out, along with blades making good contact. I have been an HVACR tech for over 15yrs now. I have been a plumber for 10yrs. I have been in electrical and the manipulation of the electron as a hobby for my life. The biggest issue an electrician taught me with boxes like that one, rather it be a breaker or disconnect, is that there is no protection from the elements. I carry dialectical grease for all fuse and disconnect blades. The biggest issue is corrosion between points of contact. Even if the blades are not all the way in front of each other. They may be still fully engaged. Just to much corrosion.
@martinschuessler1936
@martinschuessler1936 4 года назад
If you're worried about the disconnect switch: Why didn't you measure voltage drop across the various terminals or check the current on each of the 3 legs of the incoming current for each phase? I know nothing about A/C, but electrical engineer in me is curious. ;)
@user-wd5sm7ri5c
@user-wd5sm7ri5c Год назад
Gotta look at the filters that unit needs to breathe and is the economizer open? Great vids thanks
@jrsmyth9761
@jrsmyth9761 4 года назад
Maybe you did, but did not mention it or show it. You replaced the bad capacitor, but left the other one. Usually you replace multiple items when you replace one, like multiple fan motors, the fuses, or contactors. As you state, it would be cheaper to replace the cap now rather than on another service call.
@throttlebottle5906
@throttlebottle5906 4 года назад
i'd be thinking the fan motor reversing wires are rubbed through on a grill since they're stuffed through and all the vibration.
@joelwatts8951
@joelwatts8951 4 года назад
Despite the pitted contactors, they still have zero voltage drop across it, i know you're looking for preventative measures but they still fine to me
@actechformallyyomama746
@actechformallyyomama746 4 года назад
joel watts the points are what give contactor s the rating. When the points which are made of silver get pitted the contacts can arc closed or give a bad contact. Changing a contactor beats the shit out of changing a compressor.
@tomh6779
@tomh6779 4 года назад
I also get anxiety about calls or installs that I worry I didn’t cover everything. Same with calls that come in over the weekend. The wife thinks I’m crazy but she is probably correct.
@HVACRVIDEOS
@HVACRVIDEOS 4 года назад
Yeah I am definitely crazy
@amoshadad3657
@amoshadad3657 4 года назад
This is airflow issue %100 as soon as you will replace that motor superheated will go up cuz sub cool was ok I had same problem before
@keith_5584
@keith_5584 4 года назад
0:40 I do see a real link between those "anxiety," feelings and a real ability to know when it is justified. I would put money on the subconcious knowing something you do not, but I can vouch that it is a useful curse. Still a curse, but it makes you a better tech, engineer, or whatever logic based field apllies here. Might work for other stuff, but I can only confirm what I have seen and documented.
@wonderhomie2011
@wonderhomie2011 4 года назад
Getting close to 50% of a new unit with all the work needed on that machine to get it back to mfg specs. Are you going to quote them a replacement? And it would be a surprise if your low suction was due to the issues with the blower motor bearings and a dirty fan.
@thephantom1492
@thephantom1492 4 года назад
At 7:17... You made a major mistake: you checked phase to phase. If only a single phase was on, you would have mesured zero as there is no return path to any other phase. The proper way would have been to check to ground, or to a known good phase (before the disconnect). This way you would have mesured something if only a single phase was stuck on. You could have got zapped bad. Fortunatelly it is 'just' 208V...
@Edward-ud8hd
@Edward-ud8hd 4 года назад
Correct me if im wrong, but if one leg was stuck closed, you would have 120V on that leg. If the other 2 legs were not energized, then there would be 0V. Therefore, if you tested voltage from the stuck hot leg to the other non energized leg, you would read 120V.
@thephantom1492
@thephantom1492 4 года назад
@@Edward-ud8hd You are right on the 120v part, but not on the energised to not.. Let say that phase 1 knife make contact, but not 2 and 3. 2 scenarios. First, fuses are intact. Phase 1 loop throught the equipment and back at the fuse 2. Fuse 2 therefore read 120v at phase 1. Voltmeter see 0v difference. Scenario 2. Fuse is blow. 120v phase 1 is present at the bottom of fuse 2, but can not reach the top. The phase 2 knife is open. Therefore, the top is floating and no current can flow. Meter still read 0v. In both case, 120v is present. We have both scenario here...
@ickipoo
@ickipoo 4 года назад
You really need to test both phase-to-phase and phase-to-earth - there are scenarios where only checking one is unsafe (eg only checking phases-to-ground with a bad ground)..
@thephantom1492
@thephantom1492 4 года назад
@@ickipoo a bad ground in such setup is very improbable, close to impossible due to how and where it is installed (indirect ground in multiple location) bit not null, so yeah, you are right.
@ickipoo
@ickipoo 4 года назад
@@thephantom1492 I agree, but that's the problem with Internet advice - someone can take it, and apply it in another context (say, a disconnect in another location), and come a cropper.
@royamberg9177
@royamberg9177 4 года назад
It's almost completely shot. Disconnects give lots of trouble fuses do funny things. I've had them open up when they have current going through them then check fine with multi meter the covers are sure tore up
@m0fr3sh90
@m0fr3sh90 4 года назад
Roy Amberg I always check voltage drop across fuse while unit is running, anything over .5 to 1 volt and that fuse is getting replaced regardless off continuity check with fuse removed.
@royamberg9177
@royamberg9177 4 года назад
@@m0fr3sh90 you didn't get what I was saying. You can ohm a fuse and it will ohm fine. Once you put current on it it opens up. Example. Single phase system. No power after fuses. And power before. Disconnect is on so fuse will show open with a volt meter. Turn power off it ohms fine. Had this happen before. Several times
@m0fr3sh90
@m0fr3sh90 4 года назад
Roy Amberg gotcha
Далее
ONE THING LEADS TO ANOTHER
23:34
Просмотров 114 тыс.
THE DINING AC IS NOT WORKING
33:05
Просмотров 107 тыс.
다리에 힘이 풀려버린 슈슈 (NG Ver.)
00:11
Просмотров 700 тыс.
THE KITCHEN AC IS LEAKING WATER IN THE BUILDING
24:29
HURRY EVERY AC IS DOWN......
31:56
Просмотров 340 тыс.
LENNOX PACKAGE UNIT WITH BAD BEARINGS
43:11
Просмотров 83 тыс.
HVAC Scam failed again on 2nd opinion call
18:59
Просмотров 107 тыс.
THE AC KEEPS TRIPPING THE BREAKER
35:03
Просмотров 506 тыс.
GROUNDED COMPRESSOR AND AIRFLOW PROBLEMS
22:34
Просмотров 88 тыс.
THE FAMILY DINNER HAD TO WAIT
20:11
Просмотров 34 тыс.
다리에 힘이 풀려버린 슈슈 (NG Ver.)
00:11
Просмотров 700 тыс.