Learn How to Lower Gas Bills and Improve System Performance 

Urban Plumbers
Подписаться 40 тыс.
Просмотров 58 тыс.
50% 1

#heatgeek #pdhw #weathercomp
In this video, I take on the task of energy efficiency improvements to a hugely inefficient heating and hot water system in a 4000 square feet house.
Join me on this journey and let's see if we can improve this system and by how much.

Хобби

Опубликовано:

 

15 окт 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 270   
@markcoppersmith
@markcoppersmith 2 года назад
I make hot water cylinders but your knowledge of systems is from another planet. Im impressed.
@CommercialGasEngineerVideos
Yeah he's not from here. Think it's one of the cooler planets where more heat is required.
@RaithUK
@RaithUK 2 года назад
You seem to know your stuff and unlike alot of people i have met you go through every thing and tune it all perfectly.. i wish more gas/plumbing people had your detailed work ethics.
@CommercialGasEngineerVideos
He loves what he does
@MichaelFlatman
@MichaelFlatman 2 года назад
It's a shame there's probably quite a lot of houses wasting so much gas with poor/broken heating controls. Nice job on this one though
@stephendoherty8291
@stephendoherty8291 7 месяцев назад
I think many gas installers "know" gas boilers (otherwise boom goes the property or angry callouts) but as to electrically setting up the system?? That needs an understanding of electrics. Why are most installs not HW priorty?
@k20aa
@k20aa 2 года назад
I can't even begin to imagine the bag of wiring nightmares you had to sort out there well done great job 👍👍
@UrbanPlumbers
@UrbanPlumbers Год назад
it takes time and patience to trace all the wiring, and also what I call thinking 3D - having 3 or 4 different things in your head at the same time to understand how the existing system is wired.
@TheZippyMark
@TheZippyMark Год назад
@Urban Plumbers How do you go about it with a system that complicated? Sometimes I find it easier to just unwire everything and start again when it's a basic house setup, but that would be ridiculous here. The other thing I find helps is trying to create a wiring diagram of what's been done, I'd be interested to know your method!
@zteaxon7787
@zteaxon7787 Год назад
@@UrbanPlumbers It's very impressive to reverse engineer these so efficiently. Of course when you do this job for a long time you can make some argumented assumptions and not everything is a questionmark. Very useful experience. Kudos
@jezzaandrews1940
@jezzaandrews1940 2 года назад
Love your work and thanks for another great video👍Sorry for a rant, but its Sad! They didn't worry about how wasteful they were until it started to really hit them in the pocket. The Government shouldn't be subsidising people like this on their energy bills and certainly not giving them £5K off a heat pump. The subsidises should be, to pay for heat geeks like you, to tweak and help improve the energy effeciencies of the needy.
@haycrossaudio5474
@haycrossaudio5474 2 года назад
Came across your channel a week ago and pretty much binge watched all your videos. It so good to see some who takes the time to design and setup the systems correctly especially on the control side. I'm an electrician by trade but work as a consultant now. Heating controls were always of interest and make all the difference. Love your work. Cheers. Matt
@CommercialGasEngineerVideos
Good shout
@kierancuthbert5416
@kierancuthbert5416 2 года назад
Very rewarding work there. Outstanding results for your customers further down the line. They will make back what you charged them in a few months!
@UrbanPlumbers
@UrbanPlumbers 2 года назад
That is the idea
@nickbea3443
@nickbea3443 2 года назад
Brilliant insight into identifying the system issues and also the solution logics put in place.
@colinfarrell6444
@colinfarrell6444 2 года назад
Brilliant! Got to be the best engineer I've seen,..... bar none Keep up the great work
@samposton9101
@samposton9101 2 года назад
Lovely work! It’s amazing that when people install these systems they don’t think about their efficiency. Your clients are lucky to have you!
@Professional_Youtube_Commenter
@Professional_Youtube_Commenter 2 года назад
money is not a problem for these people.
@samposton9101
@samposton9101 2 года назад
@@Professional_RU-vid_Commenter maybe but it’s irrelevant really. The original installer had the option run the make the system more efficient but setting it up correctly but didn’t
@ma40
@ma40 2 года назад
@@Professional_RU-vid_Commenter Well clearly it is at 10p per kWh, otherwise Simon wouldn’t have the job here. Cheap gas has masked the inefficiencies in the system, but the wastage is insane
@nickbea3443
@nickbea3443 2 года назад
It may be they became out of their depth and took the easy route at the expense of the customer. Current gas prices have now caught up with the situation
@OYET-te2jn
@OYET-te2jn Год назад
This is one of the best HVAC channels I've found. Very very good presentation and detail in these videos. Very informational. I live in Colorado, USA. Good stuff brother! :-)
@UrbanPlumbers
@UrbanPlumbers Год назад
Thank you for watching an a great comment!
@Bob_too
@Bob_too 2 года назад
Be great to see a Video of you changing the Flow Meters on the UHF and see what that can achieve in further Efficiency.
@UrbanPlumbers
@UrbanPlumbers Год назад
it's coming soon, although I do not expect massive gains, and they may be hard to measure accurately
@Top12Boardsport
@Top12Boardsport 2 года назад
Well done. Love people that know what they are doing.
@simonc4810
@simonc4810 2 года назад
Now that gas is so expensive, investing in efficiency is a no-brainer. We converted to Honeywell Evohome controls in 2018 and the 1st year savings more than paid for the £700 investment. I’ve also fine-tuned the heating curve and temp. offset (system has weather comp.) to the point that flow temps are at the absolute minimum required. The only downside is that the motorised radiator controllers sporadically need batteries changed around 1x per year - rechargeable batteries are a must!
@micssticksnpipes
@micssticksnpipes 2 года назад
Love these videos. Great 👍
@loving-plumbing
@loving-plumbing 2 года назад
That one hurt my brain . Well explained and filmed again. 👍🏻👍🏻
@john1080
@john1080 Год назад
Many thanks for sharing this and also thanks to the property owners for allowing their property to be used as a case study. Looking at your proposed saving of 20,000 kWh every year - heat generated within the building has to escape somehow - either the building is maintained at around 30C (unlikely) or they regularly dump heat by opening windows (possible but they probably haven't called you in to close windows for them) or the Ideal Heating boilers are both losing an average of over 1 kW continuously every hour of the day for 365 days a year - assuming they are set up for 90% combustion efficiency the majority of this heat must be leaving the building through the flue. I have an Ideal boiler and I can't work out how it is even possible for it to be so inefficient - they can't just 'lose' heat - do you have any idea how these Ideal boilers can perform so badly?
@Skeletoncrew46and2
@Skeletoncrew46and2 2 года назад
Looking forward to the results.
@avivscrewvalla
@avivscrewvalla 2 года назад
I'm glad you remembered to set the boiler to after the Solar PV diverter's peak generation window during the day :)
@UrbanPlumbers
@UrbanPlumbers 2 года назад
It needs some kind of integration with solar controllers to bring the boiler on on overcast days
@singlendhot8628
@singlendhot8628 2 года назад
@@UrbanPlumbers The Eddi should be able to handle this easily.
@UrbanPlumbers
@UrbanPlumbers 2 года назад
@@singlendhot8628 really? I need to check the manual then.
@shm5547
@shm5547 2 года назад
@@singlendhot8628 Just had a look at the manual, on page 54. The standard Eddi won't do it, you have to buy an add-on relay board, but it doesn't seem worth it. All it seems to provide is the ability to schedule times for heating water using the boiler, which you could just do with an existing control anyway. For this set-up with two immersions, maybe a couple of relays, one for each immersion live, then pass the cylinder stat call for heat through both normal off on each relay. The live call for heat will only then get to the gas boiler if both immersions are unpowered.
@symosys
@symosys 2 года назад
What time do you set the secondary circulation on and what timers are you using?
@AA-lc6yi
@AA-lc6yi 2 года назад
I'm gutted you're not up north, we'd absolutely have you in to do our heat pump. Your videos are phenomenally well done and even me as a plumbing idiot can understand them.
@UrbanPlumbers
@UrbanPlumbers 2 года назад
Google: ‘heat geek elite’ - there may be one near you !
@AltoEnergyLimited
@AltoEnergyLimited Год назад
Well done, Szymon! No doubt the home owners are happy!
@humphreychiu
@humphreychiu 2 года назад
Good luck with the wireless NeoAir’s. I’ve converted from old 12v wired to these with UH8RF wiring centre for a few years now. I regret. The RF signal is really weak and can sometimes fail, causing a 12min an hour firing of the ‘missing’ zone on the wiring centre. The batteries don’t last as long as claimed on the NeoAirs. If you take batteries out for too long, the stat forgets channel and zone setting, you need to set it again. I hope you have left instructions to the owners how to do that just in case it happens when they change batteries. In my small house and normal partition walls, I have had to add a NeoPlug as a signal repeater. I have a question. When you have programmed zone thermostats, do you need weather compensation on boiler? Set it to always condense, each room stat will react individually and won’t use anymore heat than the schedule required.
@smartgorilla
@smartgorilla Год назад
dude you are an amazing light to me. fancy balancing my rads in bedford? the engineer here never bothers. . combi boiler downstairs and drops rads. is it 20 degrees per rad?
@KavanOBrien
@KavanOBrien 2 года назад
You are very good in your knowledge and the way you explain, have seen a few of your videos , do you or can you look or think about doing a small solar system with a small windmill combination to some how heat your home , I have a small house with a large garden and feel a little bit of solar and a small solar system would suit me but not much money available and wondered if you would or could do a do it yourself system to show people that you don’t have to buy a big system that you could do a bit at a time easy add on system, the answer is probably no but you never know if you don’t ask then you always wonder and it might give you a thought to do something different you strike me as a man that embraces a challenge.
2 года назад
Are there many properties spilling that much gas per year which stayed "unnoticed" until gas prices get through the roof ?
@UrbanPlumbers
@UrbanPlumbers 2 года назад
Sadly most of the houses in UK are more or less controlled in this way ! S Plan should be illegal !
@Game0verFool
@Game0verFool 2 года назад
I'll be interested to see what the figures are next year 👍
@mjhmotorsport
@mjhmotorsport Год назад
look forward to the update video ;-)
@kieranmccreedy271
@kieranmccreedy271 Год назад
I am considering secondary circulation. My idea was to have a motion sensor in the bathroom to trigger the pump. That way it’ll only run when you’re likely to use the hot tap.
@UrbanPlumbers
@UrbanPlumbers Год назад
yes, that is not a bad idea. Just make sure it cannot run for longer periods of time.
@gmckayak
@gmckayak Год назад
I've seen that done on a motion sensor. The secondary pump runs for the time it senses motion. hot water is instantaneous at the taps. A nice way without having them run 24/7
@warrenberry3609
@warrenberry3609 Год назад
Brilliant video's, I live in a static caravan with a Morco 24ED LPG combi boiler. I've just installed a hive thermostat as had none before, any advice on how to make more efficient ?
@scottpeters8142
@scottpeters8142 2 года назад
Another great video as always 👍
@pumpkinhead456
@pumpkinhead456 2 года назад
Great job as always! They'd save even more if they lived somewhere more suitable for 2 people; it's a funny world where 6 people live in a 2 bed flat and can't afford to heat it, and others can afford to heat 500 litres of hot water constantly and waste most of it. They might even live just 2 streets apart... looking forward to seeing the results all the same!
@WSMITHify
@WSMITHify 2 года назад
What’s it to you they’ve obviously worked really hard to get what they have, that’s a free market economy not communism that you are advocating
@pumpkinhead456
@pumpkinhead456 2 года назад
@@WSMITHify it's nothing to me. You could argue the market is not particularly free, but this is a simple RU-vid video not an economics debate, and what do we know anyway. Maybe they've worked really hard, maybe not, who really cares.
@yscol1313
@yscol1313 2 года назад
@@WSMITHify ​ the market is most definitely not entirely free but it’s as close as reality will let it be. Yeah we really have no idea how they made/received their money but a waste is a waste, no matter how much value they created for it to then be wasted 😂. It’s hardly communism, right? Just a comment on a video, nobody is suggesting going and turning off their gas mains to save our comrades 😅
@JasperJanssen
@JasperJanssen 2 года назад
Just the size of the gas meter they’re using is astonishing.
@tonystanley5337
@tonystanley5337 Год назад
People like you should be training and monitoring the numpties that put that system in.
@andrewriley4204
@andrewriley4204 2 года назад
Another very good video film. Well done. Unrelated question:- Having seen several of your videos:- Why the Ear Defenders ? You seem to mainly work in Domestic properties, is there a lot of work-based noise ?
@UrbanPlumbers
@UrbanPlumbers 2 года назад
I used to be a gigging musician, so have a habit of protecting my hearing
@andrewriley4204
@andrewriley4204 2 года назад
@@UrbanPlumbers Gotcha. Talented 🙂 Don't tell me that you're also a great cook 😜
@mrraoulfrench
@mrraoulfrench 2 года назад
Absolute Master.. can you do a vid on how to wire the weather comp in to these systems. Would like to start doing this for my customers. My business is based in Bedfordshire. Thanks
@IanFarquharson2
@IanFarquharson2 2 года назад
Monster job for sure. Most plumbers don't like the look of 2 zone valves and an s plan, let alone having to simplify that lot to work properly. Do they still get some reasonably warm water out of the far sinks with intermittent recirc?
@Brijoolz
@Brijoolz 2 года назад
Does the Eddi not have a relay that can be used to interrupt the ‘gas’ system demand? Everything I see about tends to assume that the hot water will only be heated by the ‘free solar’ , but surely the more common use will be along with a primary circuit? Great video. Good to see a guy who cares about these things.
@UrbanPlumbers
@UrbanPlumbers 2 года назад
From what I can see in the manual Eddie can use gas boiler as boost only. I am unsure if it can be used as a timer for an external heat source. Will give it a go when I come back t on the job to repair manifolds.
@Brijoolz
@Brijoolz 2 года назад
@@UrbanPlumbers if you could drop out the heating demand for the wet system, the DHW time clock could stay on during the day, as the Eddi could cut in if the demand was there and, of course, it had a supply from the solar. Great work.
@singlendhot8628
@singlendhot8628 2 года назад
@@UrbanPlumbers It most definitely can but must be specified on purchase i.e. an additional relay is required. Given that it is the best diverter on the market, May deserve its own episode and perhaps you contacting the company to have them feature on your Chanel?
@UrbanPlumbers
@UrbanPlumbers 2 года назад
@@singlendhot8628 I will talk to them soon, as I will be doing PV on new house
@user-gman6059
@user-gman6059 2 года назад
Can you please make your ideal vogue hot water priority video available. I could really do with the wiring diagram. PS your content is unreal. I love your system design and your explanation as to why you have chosen a specific design based on your customer’s needs. Thanks
@UrbanPlumbers
@UrbanPlumbers 2 года назад
I will have to shot it again. There is a mistake there
@user-gman6059
@user-gman6059 Год назад
Sorry for the late response I have been crazy busy. What was the mistake ?. I have fitted the same setup but it’s not wired up yet. I know you must be a busy guy but a response would be great as the job is miles away from my house and I don’t want to make the same mistake and have to go back and correct it. I could not see the issue when I watch the video. Thanks
@UrbanPlumbers
@UrbanPlumbers Год назад
@@user-gman6059 it turns out the vogue video is back up as the wiring was correct there. Ideal in their wisdom has 2 different wirings in heat only and in vogue. Basically heat only needs SL from DHW and CH going to SL1 and DHW off into SL2 Vogue needs to separate SL - DHW to SL2 and CH to SL1 - no DHW off needed - check the manual though as those SL could be other way round.
@user-gman6059
@user-gman6059 Год назад
@@UrbanPlumbers you are the man. Thanks a lot. This really helped me out.
@Skeletoncrew46and2
@Skeletoncrew46and2 2 года назад
Top class video!
@KisssCola
@KisssCola 2 года назад
Did you left the grundfoss pump to run at constant speed. Wouldn't the constant pressure be better
@stephenrichards5386
@stephenrichards5386 Год назад
Love your work and videos. Have you published a video on calculation of heat loss. I used to have an official software for doing it 20 years ago
@UrbanPlumbers
@UrbanPlumbers Год назад
I think it will be the most boring video ever made - but there is so many people asking for it that I may have to do it now. Maybe Adam from @heatgeek reads this comment and does the video himself - he likes doing those boring subjects 😂😂😂
@stephenrichards5386
@stephenrichards5386 Год назад
@@UrbanPlumbers go on! Be bored for a while and I'll send a pint of beer 🍺🍺
@robcoulson6897
@robcoulson6897 Год назад
Been watching your videos for a while now and I like your work quality and attention to getting the figures right and most efficient. I was wondering, would you recommend a system boiler for an S Plan system. I've had an Alpha HE SY25 running for the last 16 years and it's getting tired now. It's used alongside a Heatrae sadia Premier Plus Unvented 150. I'd like to go all bells and whistles but we are moving in the not too distant future but still feel like while winter is on a better boiler may be needed and I'm topping pressures back every now an then. Your advice would be very much appreciated.
@BiohazardX9
@BiohazardX9 2 года назад
speaking on efficiency, I have a hot water Cylinder 'S plan', running on Nest Learning 3 controls (thanks to your videos by the way) - boiler is a Potterton Promax HE Plus but an older model. while it was recently inspected as part of my boilercare plan and came out fine. would there be any benefit in installing a new boiler? this one was installed since flat was built in 2006.... I am thinking perhaps a newer boiler would be much more energy efficient and take less to heat up the tank...
@avivscrewvalla
@avivscrewvalla 2 года назад
100% Yes. Get a Viessmann 200-W. There is no boiler sold in the UK that is more efficient.
@owenattewell3910
@owenattewell3910 2 года назад
Great video Szy! I went to a customer's house with a very similar issue, it took me ages to figure out their system and what was going on, how long did you spend figuring this one out?
@UrbanPlumbers
@UrbanPlumbers 2 года назад
figuring out what was wrong took half a day, fixing it took 3 days
@JC-jv5xw
@JC-jv5xw Год назад
Brilliant analysis and fix Szy. And you managed it without slating ideal boilers! The really depressing thing is how the last plumber (definitely not a heating engineer) managed to leave the system in such a state without even testing that things were functioning sensibly. Was it a complete install or has it been modified over the years to become that complete mess?
@UrbanPlumbers
@UrbanPlumbers Год назад
Looks like things have been done to the system over the years. Last installer just changed boilers
@cappello333
@cappello333 2 года назад
its interesting to see how you work across the pond compared to new york
@timcook2571
@timcook2571 2 года назад
I love that you are using Heatmiser controls. You could have used a Grundfos auto-adapt secondary return pump; it may be worth a try next time. Great work!
@UrbanPlumbers
@UrbanPlumbers 2 года назад
I will look that pump up
@rikvdmark
@rikvdmark 2 года назад
Wow that’s a massive improvement! Question, I currently have a Nefit Topline 30kW boiler for heating and hot water. Would it be beneficial to add a hot water cilinder in the system? Considering energy prices I’d like to get everything as energy efficient as possible.
@flewkit
@flewkit Год назад
Hi what do you think of the VSmart control system. is it the best one to use ?
@normanboyes4983
@normanboyes4983 Год назад
Your customer must be chuffed to bits. Impressive work. Once you get the new flow meters and assuming the original design data sheets are not available - how are you going to optimise the flow rates without spending another couple of days? Excess flow may have been one part of the overshooting issue in any of the heated spaces.
@UrbanPlumbers
@UrbanPlumbers Год назад
Luckily zones are marked on the manifolds - I will just go by pipe centres (thermal camera) and room area plus heat loss that I already have. 1 day job. Maybe even not a full day.
@tsp55555k
@tsp55555k Год назад
again your amazing
@UrbanPlumbers
@UrbanPlumbers Год назад
🤗🤗🤗
@GSMah
@GSMah 2 года назад
I need a new system planning in North Birmingham on a property of this size. You seem to be the oracle of heating. Any advise on where to start?
@piotrwasilewski1826
@piotrwasilewski1826 2 года назад
Heat loss calcs that where the journey starts.
@UrbanPlumbers
@UrbanPlumbers 2 года назад
And then Google ‘heat geek elite’ and hire one
@nmparmar
@nmparmar 9 месяцев назад
Are we due a follow up on this job?
@b21playa
@b21playa Год назад
I think mine has a faulty zone valve on dhw, find pipe going to tank getting warm when no demand on it.
@markellse
@markellse Год назад
So, any updates on consumption, now we've had a few months with significant cold spells?
@UrbanPlumbers
@UrbanPlumbers Год назад
Not yet. I need to go back and talk to the client.
@scottlewis7893
@scottlewis7893 2 года назад
My man’s a genius
@Reakerboy
@Reakerboy 2 года назад
Awesome video! What a set up and love the innovation you brought to the party! I have exactly the same boiler, how easy was the weather comp to fit? Is it good, would you recommend it? Did you use the Ideal version? Cheers
@richardwaller7721
@richardwaller7721 2 года назад
I recently had an Ideal Vogue installed with weather comp and it's been a revelation. House feels so much more comfortable as a result and it does a great job of modulating the flow temp to match the heat demand. Makes you wonder why it's now installed as a matter of routine.
@Reakerboy
@Reakerboy 2 года назад
@@richardwaller7721 thanks for the reply, I'm certainly going to go for the weather comp, just need to track down the electrician now! Cheers
@UrbanPlumbers
@UrbanPlumbers Год назад
@@Reakerboy if it is a heat-only boiler then it is doable but definitely to easy. It may require a relay and also a Normally Closed valve installed - so-called X plan
@Reakerboy
@Reakerboy Год назад
@@UrbanPlumbers yes, I believe it's called a system boiler? We have an unvented cylinder also. So I see the issue is with hot water priority? Is that correct? Thanks for the response, super helpful. 👍🏻
@mgbroadsterJ
@mgbroadsterJ Год назад
Do you do heat loss calcs on these upgrades or do you guess?
@UrbanPlumbers
@UrbanPlumbers Год назад
Full heat loss, always
@mgbroadsterJ
@mgbroadsterJ Год назад
@@UrbanPlumbers You may not know what insulation as been added . You did a nice job with those mixers . with the insulated covers .
@UrbanPlumbers
@UrbanPlumbers Год назад
@@mgbroadsterJ still better than just guessing. I go to the loft and look down the cavity or look into the vent brick. If those are not available I would drill the wall to check if customer permits.
@Bob_too
@Bob_too 2 года назад
How important is it to Drain Down the second Cylinder, in addition to just isolating the 2nd Cylinder Boiler Flow Loop and Cylinder Cold input or Output ?
@UrbanPlumbers
@UrbanPlumbers Год назад
I don't think that keeping water at room temperature in a cylinder that may never get used again is a good idea. 2nd cylinder will have to be disinfected anyway if they want to bring it back online.
@rowanballinger3690
@rowanballinger3690 Год назад
I’ve been a plumber and heating engineer for 20 years you make me look like an apprentice. You don’t learn this stuff from college or other engineers. Please tell me how you learnt make me want to improve!
@UrbanPlumbers
@UrbanPlumbers Год назад
You learn from different sources, but mostly other engineers. Just not on gas chat! Look for people like: Kimbo Betty, Andrew Millward, Adam Chapman and courses by Heat Geek All electrical knowledge I had to figure out myself
@rowanballinger3690
@rowanballinger3690 Год назад
@@UrbanPlumbers thank you I will look into it very good
@rikeshpatel2091
@rikeshpatel2091 Год назад
Hi, Would you be able to wire my underfloor heating, and other zones controls please?
@UrbanPlumbers
@UrbanPlumbers Год назад
email me please though my website
@Divine_Evil
@Divine_Evil 2 года назад
Any tips, on how to save on wooden pellet burner/boiler? I have 2 loops, 1 convection loop in the basement. 1 loop for ground and first floor which has a pump. Hot water is via serpentine, stealing heat, from the relatively small boiler storage. Pump doesn't have an abv... All radiators have a trv, but 1 or 2 are left open... I have a thermostat and automatic outside temp compensated shunt, regulating the pumped radiator temps... i.e. during night, heating is off...
@shm5547
@shm5547 2 года назад
The weather compensation PDHW modifications are only applicable to condensing gas boilers. However, a small efficiency saving could be made on the circulating pump if it's an old one that doesn't modulate it's speed. A modern pump with a proportional pressure curve would reduce the pump power consumption when the TRVs close. But you need expert advice, as wood burners can get very hot and adequate water flow is important for safety.
@Divine_Evil
@Divine_Evil 2 года назад
@@shm5547 Thanks for the reply... Safety of the boiler is ensured, by a thermosensor in the boiler, and by only burning a handful of wooden pellets at a time... Though this didn't help when last February, my open air expansion vessel that is in the cellar, got clogged and there was no over pressure valve... Fortunately, the boiler had spewed water on the electrics, and the RCD tripped, shutting of the boiler. Now the expansion vessel is pressurized and right next to the boiler... And with a opv of 3 bar...
@eliotmansfield
@eliotmansfield 2 года назад
My house is fairly large but I only need to run the hot water circulation for one minute for it do it’s job.
@UrbanPlumbers
@UrbanPlumbers 2 года назад
Most houses are like that. Not this one
@Swwils
@Swwils 2 года назад
What is your go-to contactor/relay if you don't want to swap the HW valve on a S plan when converting to PDHW?
@UrbanPlumbers
@UrbanPlumbers 2 года назад
no preference really - whatever I can find. I hear that there are some nice, small and quiet relays available. I always end up with something loud and nasty :)
@rogerbean393
@rogerbean393 Год назад
Hager do a range of silent relays , very reliable
@Bob_too
@Bob_too 2 года назад
Which wiring Centre and Room Stats did you use for the UFH ?
@UrbanPlumbers
@UrbanPlumbers 2 года назад
Heatmiser UF8
@singlendhot8628
@singlendhot8628 2 года назад
If you had junked the Ideals and installed a single Viessmann 200W, your client's savings would have been even higher and would have paid for the boiler in a year.
@UrbanPlumbers
@UrbanPlumbers 2 года назад
Why waste 2 new boilers though?
@avivscrewvalla
@avivscrewvalla 2 года назад
I think he would prefer burning firewood to installing another V200W ;)
@singlendhot8628
@singlendhot8628 2 года назад
@@UrbanPlumbers Sell them on. With such a massive consumption even after your great efforts, a hyper efficient V200 boiler pays for itself. Not to mention the advanced weather comp and ability to zone built in. You should suggest installing one when you return next year to save them much more. Just my 0.02p
@UrbanPlumbers
@UrbanPlumbers 2 года назад
Next year it goes heat pump and I will keep 1 ideal as a back up. You will not get much benefit of v200 on such a massive house. Ideal with its poor modulation is quite ok on big houses, as with 6kw it already 1/4 of the heat loss so will. It cycle much and run with decent DT.
@singlendhot8628
@singlendhot8628 2 года назад
@@UrbanPlumbers I hope you'll get a 7kWh Arotherm+ minimum for such a big house. The South facing rooms will need influence.
@daveys
@daveys 2 года назад
The big bang theory moment reminded me of a few times switching on cooker circuits.
@LocostR1
@LocostR1 2 года назад
Some cheap smart motion sensors and relays would be a good upgrade for the secondary return, place something like a Sonoff or Shelly motion sensor above the door in each bathroom/toilet and a smart switch controlling the circulation pump then set up a simple automation to run the pump for a couple of minutes when motion is detected. By the time you've finished your business the pump will have run and the water should be hot at the tap ready for use so you get maximum benefit and minimal losses pumping it round when you don't need it. You can also use a button rather than a sensor for places like a kitchen that will be in constant use but doesn't need it recirculating constantly.
@oldcynic6964
@oldcynic6964 Год назад
It's only a good idea if the savings compensate for: - the added cost of the gear and the cost of installation, - the added complexity (pity the next plumber who has to sort out what you had done, and which bit is now broken) - the decreased comfort, if all this does not work in a timely manner. Personally, I believe in Keep It Simple Stupid, wherever possible.
@LocostR1
@LocostR1 Год назад
@@oldcynic6964 Did you mean to aim this at my post in particular or was it intended for the video in general?
@berylwatts3647
@berylwatts3647 2 года назад
This sounds like rocket science to me, an ordinary member of the public. The comments show that you are an exceptional engineer. I wish someone like you had installed my daughter's new boiler. She is on a low income and ill. She applied for a grant and was asked to pay a percentage of the costs. She has an old water tank in the airing cupboard for hot water. Instead of installing a new combination boiler, they replaced it with an older model non combination, which has left her with an old inefficient system. Can you give any advice? She can only get hot water when the heating is on. All summer she had no hot water, and had to boil it in the kettle. The company who installed it didn't explain this and not bring an expert and living alone didn't realise what was happening. They are no longer interested in her as the job is completed.
@harrydavey9884
@harrydavey9884 Год назад
Never cheap out on a gas engineer. There's lots of cowboys out there. I'm doing my training now an looking at the pipework in my own home, it's pretty shocking what people get away with. Would be hard to advise without all the facts. Depende on the size of her property, her budget, her location/outdoor temps, insulation and her existing pipework. My first guess would be, that a combi might be better, since it can so hot water on demand.
@HonzaZalabak
@HonzaZalabak 2 года назад
Do you calculate heat loss of building for the minimal temperature of the year? -2 feels more like a average temperature durung december/january. At least in Czechia we calculate heat loss to -12, -18 depending on the place where you live. I am also confused about energy consumption. If you have 20 kW heat loss, isnt the energy consumtion for one day calculated -> 20kw x 24hours = 480 kwh? But you said, that this house consumes 260 kWh durint a day (and you said it is insane amount), so I am a bit confused. Anyone, please reply and explain this to me. Thank you
@UrbanPlumbers
@UrbanPlumbers 2 года назад
In theory that consumption is correct. You would need a full 24h of -2 and a house fully heated to 21c for 24h In practice however it takes less energy to maintain the property at 21c once the fabric of the building reaches the temperature . Average temperature here is actually 10c in the winter meaning a heat loss of around 10kw for this house and also at night the temperature is set to set back of 16c. On top of that only part of the house is heated up to 21c resulting in consumption of 55kwh per 24h at the moment. I will post more data when it becomes available
@HonzaZalabak
@HonzaZalabak 2 года назад
@@UrbanPlumbers That makes much more sence to me now. I wrongly assumed the -2 C is average temperature just because I live in colder area where during winter -2C is actually average temp. Thank you for your reply. 10kw x 24 = 240. Makes sence now
@plummetplum
@plummetplum 2 года назад
I had no idea hot water and heating systems could be this complicated. Do average plumbers understand these systems, I can't imagine they do?
@BillCarrIpswich
@BillCarrIpswich Год назад
Their system looked beautifully installed, it's a shame it wasn't commissioned correctly!
@cognitivefallacy450
@cognitivefallacy450 2 года назад
Amazing to think that the bill payer was simply paying those huge bills for so long. At least they finally got around to sorting it out but the amount of gas that was wasted is disappointing. And who knows how many other properties are similarly wasteful!
@antoinec1066
@antoinec1066 2 года назад
Very interesting. I consume nearly Kwh 50,000 of gas for a much smaller house (3,000 sqft and approx 500 sqft is not heated). 41kw Worcester Green Star CDI on 67 degrees temp. Despite having evohome on 12 zones I still have a huge consumption 🤔 I am not far from you too 😊
@alcurtis93
@alcurtis93 2 года назад
would be worth getting him round to check that. Seems a mighty large figure
@antoinec1066
@antoinec1066 2 года назад
@@alcurtis93 You are right. I sent Szymon an email and we will see if he can do something 🤞😊
@harrydavey9884
@harrydavey9884 Год назад
Something wrong there, that's utterly insane.
@sammyb99
@sammyb99 2 года назад
I know a way to save money on gas….. take the gas meter out and bypass it or just stick hoover on one end and watch it spin backwards
@bertnl530
@bertnl530 11 месяцев назад
is there a follow up for this episode?
@UrbanPlumbers
@UrbanPlumbers 11 месяцев назад
I have all the data, but no time to shoot a video about it. It saved 20,000 kWh in last 12 months
@bertnl530
@bertnl530 11 месяцев назад
Oh wow, I don't know the price per kWh, but it must be a lot of money.@@UrbanPlumbers
@henrybartlett1986
@henrybartlett1986 2 года назад
Good stuff. Not sure about the background music though; distracting.
@SuperWayneyb
@SuperWayneyb Год назад
🤘😎🤘
@deanchapple1
@deanchapple1 Год назад
Thanks
@UrbanPlumbers
@UrbanPlumbers Год назад
Dean that is too generous! I am buying beers when I get to meet you!
@deanchapple1
@deanchapple1 Год назад
@@UrbanPlumbers it’s no problem! I appreciate the time you take to do the videos!. It would be good if you could show how you wire things up perhaps in future videos? 😊👍🏼
@UrbanPlumbers
@UrbanPlumbers Год назад
@@deanchapple1 what exactly would you like to see regarding wiring?
@deanchapple1
@deanchapple1 Год назад
@@UrbanPlumbers for example, on your most recent video you gave a quick show of the wiring. May be you could slow it down a fraction and show better close ups etc?
@dimabrinza
@dimabrinza 2 года назад
WoW!! Do they mine crypto???
@UrbanPlumbers
@UrbanPlumbers 2 года назад
Or grow ?
@SubStationSparky
@SubStationSparky 2 года назад
that house uses 260 KWH a day???? My house is 3300 sq ft I heat all of it with Mitsubishi Hyper Heat Pumps all ductless, a heat pump hot water heater self contained, a hot tub also. on my worst days in January Im at 125 KWH.. I still have to add fiberglass batts in the attic but i did every upgrade to this house efficiency wise. We used to be electric baseboard heat. that was horrible..
@james123j1
@james123j1 2 года назад
If the heat loss is 20kW @ -2C what is the expected daily heat requirement in kWh? 20*24=480kWh which cannot be correct!
2 года назад
The external temperature is not constant troughout the 24 hours of the day neither throughout all days of the year. There are factors to take into account which are summarized in degree-days and average annual degree-days which allow to approximate the consumption by a rule of thumb. These rules of thumb are locally valid. South-east London is not the same as the Swiss alps ;-)
@UrbanPlumbers
@UrbanPlumbers 2 года назад
Yes it would be if it was -2 outside for 24h and you were heating 100% of the property. However some say that the calculation is 20-30 over and once the property reaches the temp actually less energy is required to maintain it. Lucky we almost never have -2
@Swwils
@Swwils 2 года назад
What has happened to the heating industry this install was very very sad indeed until you.
@UrbanPlumbers
@UrbanPlumbers 2 года назад
Sadly awful lot of installations are like this.
@bovnet
@bovnet 2 года назад
@@UrbanPlumbers Seems to be an issue of a plumber and sparkie install where as someone like you understands both and the logic path needed for the control using zone valves micro switches, relays and signals from stats etc
@samsavino17
@samsavino17 5 месяцев назад
The video was a year ago. Any update 😁😁😁
@lotuselise4432
@lotuselise4432 2 года назад
Damn, I wished you covered W12 as need a Nest unit fitted to an old S Plan system.
@UrbanPlumbers
@UrbanPlumbers 2 года назад
how dare you - I only remove S plan systems :)
@SisterAbdullahX
@SisterAbdullahX 2 года назад
@@UrbanPlumbers 😂
@lotuselise4432
@lotuselise4432 2 года назад
@@UrbanPlumbers - Been in place 30 years at least Potterton Suprema 80L system boiler (replaced logic board myself or repaired as dry joints) just trying to keep it going before a house refurb and times are tight as the whole system would need to be ripped out, the old flat I did up had a Megaflow system. You Polish?
@jasonlewis4686
@jasonlewis4686 Год назад
Two people in a gaff that big!!!!
@robpotter1355
@robpotter1355 2 года назад
Always wondered what Joey Tribiani was doing now😂
@claudiahamminger-stone3274
@claudiahamminger-stone3274 Год назад
Underfloor heating gives you a great chance to use a condensing boiler at super-low condensing temperatures. Unfortunately all gas boiler manufacturers installation manuals wrongly instruct us to set the return temperature to dew point (56ºC) or lower, which is incorrect - it should be the FLOW temperature. Even one of the best boiler makers, Viessmann, shy away from correctly directing the flow temperature to be set below the dew point ! Why do they do it, when customers could save gas bills by making the boiler condense genuinely, instead of spewing white vapour clouds into the garden? They are stupid commercial reasons that lead to this madness. If Worcester Bosch for example told the truth about setting low flow temperatures: 1. Installers would clog the phone lines claiming it was wrong ! 2. Competitors would falsely claim their boilers condense even with return temperatures of 56ºC ! 3. Customers would complain that the lower flow temperature require bigger radiators than a competing boiler, and they might lose sales over it ! So as usual, the unsuspecting customer loses out with unnecessarily high gas bills. The step change of 11% efficiency improvement with gas condensing technology only occurs if the water vapour literally DOES condense on the heat exchanger. Otherwise an old style non-condensing boiler can achieve exactly the same efficiency levels - yes, really. So the entire drive across Britain to install condensing boilers (and their tiresome condensate drains) is wasted. Just wasted. To get anywhere near to that 11% fuel benefit, the ENTIRE heat exchanger must be below dewpoint. There are two critical changes that the installer must undertake, AGAINST the manufacturer's recommendations: a) reset the Natural Gas gas valve from 10+% excess air to around 2% excess air. This raises the dew point temperature back to close to 56ºC making the whole effort more achievable. You can't work sensibly with a dew point of 46ºC, can you? b) set the FLOW temperature as far below 56ºC as you can manage. This engages 100% of the heat exchanger's surface area in the battle to condense the flue gas, instead of chucking that valuable white vapour out into the garden. Here's another glorious example of Vsmn having to drop down to Level Stupid, just to remain competitive in the British market here. This poor sodding German fella Christian Engelke, the Technical Director of Vsmn UK, writes in a frustratingly oblique manner about the need for Class B residual current detectors on ALL gas boilers & tumble dryers (instead of curve B Class AC) here: www.dropbox.com/s/4p7e3rs2fsawsdd/21%20ViessmannTypesRCD.pdf?raw=1 where the boiler's installation manual explicitly states that your bog standard UK RCD type A or type AC will not function for any modern gas boiler. Just think how many gas boilers around the UK are disabling the RCDs around Britain by saturating their magnetic cores. Households are then left unprotected against genuine faults to Earth ! www.dropbox.com/s/apskmekx49xo9vo/21.01%20vdmontageexcerptrcd.pdf?raw=1
@johntonyroche
@johntonyroche 8 месяцев назад
Any update?
@SupremeRuleroftheWorld
@SupremeRuleroftheWorld 2 года назад
why have a boiler run on 50 degrees for underfloor heating? that is a waste of energy as well. and you can remove the pumps and change the manifolds over to pumpless.
@UrbanPlumbers
@UrbanPlumbers 2 года назад
There is many reasons to run flow at 50C for UFH: (this is what this one is set to at design temperature of -2) - carpets or high tog value floor coverings require 5-10C higher flow temps - very long pipe runs to manifolds - wide 200-250mm pipe spacing (as is the case here) Also, the most important reason - the difference in flow rates between the boiler and UFH manifolds. This house is a 21kW load on UFH connected to a 30kW boiler. If you were to set the boiler to the required flow temp of let's say 35C - with the boiler running at DT20 at full load and UFH at DT7 - the boiler would not be able to provide enough energy for the UFH. The reason is simple: UFH flow requires flow of 2600 liters of water at 35C - but the maximum what boiler can deliver at DT20 is 1200L / hour at 35C. You can try to lower DT to 10 at the boiler but you will still be short in this case. There is also a limit of flow that you can put though the heat exhagner. That is the main reason why you have to run UFH at 35C mixed down at 2600L / hour and boiler at 1200L / hour at higher temperature to provide the correct amount of energy required for UFH at full load. If you look at wider DT at the boiler - it is actually still as efficient as running the whole system at DT7 at a lower temp, because the return temps is still lower. Hope this makes sense.
@SupremeRuleroftheWorld
@SupremeRuleroftheWorld 2 года назад
@@UrbanPlumbers the math makes sense yes. especially if you are limited by pipe diameter. but i doubt that such a house of that size actually needs 20+ kW sustained if heated 24/7.
@UrbanPlumbers
@UrbanPlumbers 2 года назад
​@@SupremeRuleroftheWorld 4000sq feet with badly installed UFH at 200mm centers, carpets on the floor, and loads of uninsulated primary pipework in plastic. I would not risk it.
@SupremeRuleroftheWorld
@SupremeRuleroftheWorld 2 года назад
@@UrbanPlumbers i think you are confusing the heat requirement of the home (aka: insulation) with the abillity of the UFH to give off the required heat. the heating capacity of the UFH is dicated by the water temp, not the actual kW rating of the boiler. there is not much need to squeeze 20kW from the UFH with too hot water when the building does not actually need it. that is a waste of energy. that is why i also hate zoned UFH with the fire of 1000 suns. it messes with the abillity of the UFH to give of the needed heat so you must crank the water temp to get any meaningful heating in the few rooms that care calling. its WAY better to spend balancing the system so each room heats equally and you can lower the water temp and use weather based temperatures. its vastly more efficeint than just brute forcing too hot water into a few zones. with boilers its not as much of a problem as they are already so inefficent at low power but with heat pumps it gives massive power savings as they can run at power levels the boilers can only dream about. many UFH installs i modified run at well below 30c and prehaps bump to 35 near freezing outside.
@UrbanPlumbers
@UrbanPlumbers 2 года назад
@@SupremeRuleroftheWorld If it was a heat pump it is a different story - they run at DT5 - but would still need a buffer here and pumps on UFH. No chance to run 20kW without a buffer and additional system pump/pumps. Also, this would require massive primary pipework.
@colinb6035
@colinb6035 2 года назад
Why Ideal Logics?, thought you were a Intergas man!
@UrbanPlumbers
@UrbanPlumbers 2 года назад
I didn’t install them. Just optimised existing set up.
@memecoinmafia2732
@memecoinmafia2732 2 года назад
cool
@NewTechChannel
@NewTechChannel Год назад
sry I stopped viewing the video after you said that the water heater turns on once a day for 2 hours. Why? Why do you need electronic thermostat for that? Why not use a regular thermostat inserted in the water boiler and that one triggers the gas boiler to heat the water when it gets bellow lets say 45 degree.
@davidreece1642
@davidreece1642 Год назад
What on Earth was the previous installer thinking?
@UrbanPlumbers
@UrbanPlumbers Год назад
How to install the boilers quickly, charge and leave .
@davidreece1642
@davidreece1642 Год назад
@@UrbanPlumbers Yes maximum price, minimal effort. Scammers.
@JamesWilson-gw2ij
@JamesWilson-gw2ij 2 года назад
Let me just say, after watching many of your videos, you are working with people who have had no regards to their energy prices until now. Let’s see you do the same in a worker’s home
@singlendhot8628
@singlendhot8628 2 года назад
Utter nonsense!
@rimasp4769
@rimasp4769 Год назад
Hi How I can call you please
@alcurtis93
@alcurtis93 2 года назад
260kwh per day :O
@nevillethumbcatch5691
@nevillethumbcatch5691 2 года назад
Another interesting video! Not teaching you how to suck eggs, but i always fit a pipe stat wired through the DHW circulation pump, so that on a properly installed secondary hot water loop as soon as the pipe stat gets up to temperature it stops the pump, it then runs the pump for very short periods as the temp drops on the stat. You may have done this, just didnt notice.
@UrbanPlumbers
@UrbanPlumbers 2 года назад
I know that. However in those houses the return pipe never even gets warm. All heat is lost before the water makes it back. Had 3 4000 sq feet houses doing exactly that.
@symosys
@symosys 2 года назад
Can you elaborate on the pipe stat for secondary circulation where to get this and how to do this? We have SC and its a pain. I have 2 x 161 l tanks for 3 adults , 2 children. 2 x 24kw boilers into LLH and UFH 4 manifolds. I’ve rewired and added relays to stop all pumps running similar issue as this video. I’ve just realised that the HW call for heat always opens both valves and heats both cylinders together. I’ve split boilers so now have HW boiler range rated to 8.2kw also have solar heating water and set thermostat to 65 on that. The thermostats that link to boiler are set 45 and HW boiler is set to 50 degrees. The UFH boiler is set to 40. Both will still mix in LLH but this should still be fine I think because hopefully solar will compensate. Hoping bills reduce now
@shm5547
@shm5547 2 года назад
@@symosys I think the key phrase here is 'properly installed secondary hot water loop'! The idea is to put a pipe thermostat on the return from the hot water loop. So that once the loop is full of hot water, the circulator pump stops. Then it intermittently comes on/off to replace the water in the loop as it cools. For this to work though, the hot water pipes will need to be adequately insulated throughout the entire circuit. If you had a bit of pipe near the furthest run that wasn't lagged, but the pipes near the return were, then you'd end up with hot water that is not a consistent temperature at the tap for the initial first few seconds of flow. I wonder in these days of home automation systems, a better option would be to put small, battery powered PIR sensors (like the Samsung Smart Things devices) near the approach to bathrooms/kitchen areas. This could trigger the circulator pump to start running if someone is walking towards a bathroom/kitchen, so that hopefully by the time they get there, there is hot water at the taps.
@paulgardner3926
@paulgardner3926 2 года назад
Why do we need hot water priority systems? I have my heating on different times to my hot water.
@UrbanPlumbers
@UrbanPlumbers 2 года назад
Then you have to constantly run to the boiler to change the flow temperature - PDHW and weather comp automated that for you
@paulgardner3926
@paulgardner3926 2 года назад
@@UrbanPlumbers ok think I get it now. Am I right in saying I can’t have PDHW with every boiler
@shm5547
@shm5547 2 года назад
@@paulgardner3926 Your boiler needs to support it. Those Ideal Logic boilers on this job do. There is also a half-way house, where you can run S-plan with weather compensation. What happens in this configuration, is when there is a call for HW, the boiler will put out 80 deg C until the HW cylinder is satisfied, then it goes back to CH only with a lower flow temperature, more like 50 deg C. It's not quite as efficient as PDHW and rads get hotter when there's a call for HW rather than colder.
@bimiuk4051
@bimiuk4051 2 года назад
@@shm5547 sounds like u know what ur taking about. I have system boiler Ideal Vogue Max and a unvented cylinder tank. I also purchased the NormallyOpen zone valve to change it with the NC for HW zone valve. However! There is nobody in North who has Opentherm + PDHW Experience and who have an idea about TADO wireless thermostat EU model.
@bimiuk4051
@bimiuk4051 2 года назад
@@shm5547 thanks man, for now I am after Opentherm and PDHW. Not sure if WheatherComp will work on top of them two, or may confuse it or make it worse or have any huge benefit? I don't have Hive or Nest! It's TADO EU model which hardly anybody know how to wire it up. Besides, been told that for PDHW need to change the CH zone valve to a NormallyOpen valve as well as trace new cable from cylinder to boiler. In my case they are not on both floors :(
@ram64man
@ram64man Год назад
20kwh of energy usage a day man they really need to increase there insulation a lot . It should be no more than approximately 5kwh a day max
@davidw460
@davidw460 2 года назад
Ha ha ha, bang test :)
Далее
Your Underfloor Heating Could Be Better - Here Is How.
12:17
Собираю Маню к осени ✨
00:48
Просмотров 626 тыс.
Wildest 10 SECONDS OF HIS LIFE 🤯 @TomIsted
00:14
Просмотров 2,2 млн
Plumbers from hell left this behind
14:56
Просмотров 76 тыс.
Heat Pump Possible: The revisit
6:12
Просмотров 7 тыс.
Hot water priority with Ideal Vouge boiler
15:28
Просмотров 20 тыс.
How To Get Most From Your Vaillant Boiler.
16:53
Просмотров 44 тыс.
How many boilers does this house really need?
16:52
Просмотров 56 тыс.
Another house saved from a combi
9:47
Просмотров 146 тыс.
14 октября 2024 г.
0:19
Просмотров 575 тыс.
ПРОСТО АТАС
0:23
Просмотров 3,1 млн