Low Voltage (LV) Cable Termination in Transformers 

Electrical Works
Подписаться 45 тыс.
Просмотров 182 тыс.
50% 1

Low Voltage (LV) Cable Termination in Transformers: A Step-by-Step Guide
Proper termination of low voltage cables in transformers is crucial for ensuring safe and efficient electrical connections. Here’s a detailed process to guide you through the termination:
Preparation:
Safety First: Ensure all safety protocols are followed. Wear appropriate personal protective equipment (PPE) and verify that the transformer is de-energized.
Tools and Materials: Gather all necessary tools and materials, including cable lugs, crimping tools, heat shrink tubing, and insulation tape.
Cable Stripping:
Remove Outer Sheath: Carefully strip the outer sheath of the cable without damaging the inner insulation or conductors.
Strip Insulation: Strip the insulation from the ends of the conductors to expose the bare wire. The length of the exposed wire should match the size of the cable lug.
Crimping the Cable Lugs:
Select Appropriate Lugs: Choose the correct size and type of cable lugs for the conductors.
Crimping: Insert the stripped conductor into the lug and use a crimping tool to secure it. Ensure a tight and secure connection to avoid any loose contacts.
Applying Heat Shrink Tubing:
Position Tubing: Slide heat shrink tubing over the crimped lug and the exposed conductor.
Heat Application: Use a heat gun to shrink the tubing around the connection, providing insulation and protection against moisture and contaminants.
Connecting to the Transformer:
Terminal Preparation: Clean the transformer terminals to ensure a good electrical connection.
Bolt Connection: Attach the crimped lugs to the transformer terminals using appropriate bolts and washers. Tighten the bolts securely to ensure a firm connection.
Insulation and Protection:
Insulation Tape: Wrap insulation tape around the connection points to provide additional insulation and protection.
Cable Management: Secure the cables using cable ties or clamps to prevent movement and reduce mechanical stress on the connections.
Testing and Verification:
Continuity Test: Perform a continuity test to ensure there are no breaks in the connection.
Insulation Resistance Test: Check the insulation resistance to verify the integrity of the insulation.
Final Inspection: Conduct a final visual inspection to ensure all connections are secure and properly insulated.
Re-energizing the Transformer:
Safety Check: Ensure all tools and materials are removed from the work area.
Power On: Re-energize the transformer and monitor the connections for any signs of overheating or abnormal operation.

Опубликовано:

 

12 окт 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 47   
@noelbyrne8735
@noelbyrne8735 Месяц назад
Red, yellow, blue & black = U, V, W & N not W, U, V & N. No cable gland used. Termination enclosure open to ingress and moisture. Wire lugs not crimped correctly.
@drakeZd
@drakeZd Месяц назад
n is nuetral
@noelbyrne8735
@noelbyrne8735 Месяц назад
@@drakeZd it sure is 👏👏👏
@Electricalwrk
@Electricalwrk 26 дней назад
yes
@noelbyrne8735
@noelbyrne8735 2 дня назад
@@drakeZd Sure is.
@atik0781
@atik0781 2 месяца назад
Good job
@Electricalwrk
@Electricalwrk 2 месяца назад
Thanks
@Electricalwrk
@Electricalwrk 2 месяца назад
2 месяца назад
Terminals labeled W V U, cables terminated U V W. Clever...
@felipetvictor
@felipetvictor 2 месяца назад
Top job
@Electricalwrk
@Electricalwrk 2 месяца назад
👍
@АлександрЛужбинин-щ4д
Не хватает термоусадочной трубки для изоляции наконечников.
@Electricalwrk
@Electricalwrk 2 месяца назад
yes
@drakeZd
@drakeZd Месяц назад
bro how many amps do these wires carrry?
@Electricalwrk
@Electricalwrk 26 дней назад
for 1mm 1.4A. 185×1.4= 259A for single cable. (normal temperature)
@drakeZd
@drakeZd 20 дней назад
wow that is alot of amps imagine connecting a 1 amp fuse what will happen
@jakubjk5074
@jakubjk5074 2 месяца назад
Which country do you use this colour of phases?
@Electricalwrk
@Electricalwrk 2 месяца назад
normally use RYB. Arabian County
@dominichueber5646
@dominichueber5646 2 месяца назад
Interesting, I didn't know that. But I kinda like them. We use boring Brown, Black and Grey for phase, and Blue for Neutral
@Electricalwrk
@Electricalwrk 2 месяца назад
@@dominichueber5646 it's depends on country. which country use which colour. but internationally RYB/ BBG both are use commonly
@Dimmik8490
@Dimmik8490 2 месяца назад
Yellow, green, red for phase and blue for neutral in Russia
@dominichueber5646
@dominichueber5646 Месяц назад
@@Dimmik8490 okay, I like them even more. Like traffic lights.
@mrtopcat2
@mrtopcat2 2 месяца назад
What material is the cable made of? I thought I will see copper, but the cable looked shiny silver.
@nickolaspina2970
@nickolaspina2970 2 месяца назад
Aluminum
@Electricalwrk
@Electricalwrk 2 месяца назад
yes.
@raufbond3609
@raufbond3609 2 месяца назад
So in this connection the neutral and the earth are together??
@Electricalwrk
@Electricalwrk 2 месяца назад
yes
@dominichueber5646
@dominichueber5646 2 месяца назад
This is also standart for us in Austria/Europe. And in Germany as far I know
@Le.pecheur-ardennais
@Le.pecheur-ardennais 2 месяца назад
Au Luxembourg, Dans les coffrets électriques, Le neutre et la terre sont ensemble
@x84pav84x
@x84pav84x 2 месяца назад
Напряжение ему включите, веселей работать будет. А так надо всё аккуратней делать и не спеша. Спешка при ловле блох нужна .
@EULZG56117
@EULZG56117 2 месяца назад
Это ускоренное видео и вы это прекрасно видите, но откуда столько злости
@raufbond3609
@raufbond3609 2 месяца назад
Please is it TN-C or TN-C-S
@Electricalwrk
@Electricalwrk 2 месяца назад
tn-c ?
@raufbond3609
@raufbond3609 2 месяца назад
@@Electricalwrk okay thanks
@dominichueber5646
@dominichueber5646 2 месяца назад
​@@raufbond3609 TN-C-S bzw. TN-S ist es oder wird es dann erst beim Verbraucher (zum Beispiel ein Wohnhaus) - wo der PEN im PE und N aufgeteilt wird. ( !! - er darf danach auch nicht mehr wieder verbunden werden!) Bin nicht sicher, aber ich denke Du sprichst Deutsch ;)
@raufbond3609
@raufbond3609 2 месяца назад
@@dominichueber5646 can you please write in English
@amazigh_304
@amazigh_304 2 месяца назад
why the common wire is black and why its connected with the earth
@noelbyrne8735
@noelbyrne8735 Месяц назад
Because they are using the old British colour code where black is neutral and the earth is there to earth/ground the star point of the transformer and to create a PE conductor.
@jackwayne833
@jackwayne833 Месяц назад
bro has terminated wrong phase sequence
@Electricalwrk
@Electricalwrk 26 дней назад
yes. but it's no problem
@SharifUrRehman
@SharifUrRehman 2 месяца назад
W red yellow u blue
@Electricalwrk
@Electricalwrk 2 месяца назад
yes UVW = RYB
@poiuycat
@poiuycat 2 месяца назад
why my motor running reverse 🤣😂🤣😅🤣
@prohladsarmah911
@prohladsarmah911 7 дней назад
Wrong canection
@kyleanderson6201
@kyleanderson6201 2 месяца назад
I think he should stick with magic carpet repair or camel jockeying and stay away from electricity
@Electricalwrk
@Electricalwrk 2 месяца назад
🙄
Далее
这到底是怎么做到的 #路飞#海贼王
00:10
Просмотров 3,5 млн
Input distribution device 2x630A
5:31
Просмотров 5 тыс.
Changing blown transformer!
30:58
Просмотров 389 тыс.
How does a VCR work?
15:00
Просмотров 6 млн
HT Termination 400mm cable
6:25
Просмотров 52 тыс.
HV CABLE TERMINATION
16:33
Просмотров 14 тыс.