New consumer unit far to close to Gas Meter... 

Mark The Sparky Allison
Подписаться 13 тыс.
Просмотров 4,9 тыс.
50% 1

Bit of a mare on this one to be honest...
Those tricky jobs in a kitchen cupboard close to a gas meter is one every spark will be familiar with. This is no different!
A chance for Nathan to shine with some help from his friends.
See what we come up with and have a chat through the requirements to separate gas/electric.
Professional Electrician seem to suggest different to voltimum and registered gas engineer... BS6891
registeredgase....
www.voltimum.c...
professional-e...

Опубликовано:

 

16 сен 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 24   
@matthewfewings6023
@matthewfewings6023 Год назад
Great video as always Mark. I have the same scenario where everything is in one cupboard in the kitchen. Found this video as part of my research. Not sure I can achieve the 150mm but will give it a go 🙏
@Mc674bo
@Mc674bo Год назад
Hi Mark The real world versus the regs , an argument I’ve been witness to on many occasions . At the end of the day common sense is the best way forward , especially considering what the original installation was like and how much safety it is now . Any NIC inspector worth his salt , would I’m sure agree . As for those old MEM fuse holders , many would have asbestos cloth on them . Yet another problem that the younger lads may in time come across. Happy days 😂 Best wishes and kind regards to you and your staff 👍👍👍
@effervescence5664
@effervescence5664 Год назад
As someone that's qualified in both gas and electrics, 150mm pertains to meters in conjunction with, consumer units/switches/sockets and any other accessory. 25mm pertains to pipe and cables/accessories. There is also guidance stating a non-conductive non-combustible material can be used if the distance is closer than 150mm between a consumer unit and gas meter. Something like cement backer board that you'd use for Solar Installations for instance.
@electrician247
@electrician247 Год назад
That's my take on it as well. But linked some other views in the description
@effervescence5664
@effervescence5664 Год назад
@@electrician247 Yes I've read them before, completely disagree with professional electrician whom obviously decided to either not read the gas literature or not confer with GasSafe before making the article.
@electrician247
@electrician247 Год назад
@Effer Vescence it did seem at odds with what I read. CPD accredited you know is the magazine...
@tonywatson1412
@tonywatson1412 Год назад
look at the twin terminal screws , on the incoming tails....yip...it was,nt all bad...i the old days
@electrician247
@electrician247 Год назад
100%
@adriatikkrasniqi1453
@adriatikkrasniqi1453 Год назад
Well done., good work.,
@electrician247
@electrician247 Год назад
Thanks 🙌
@gassafe9810
@gassafe9810 Год назад
Would be really easy to move that meter to the next cupboard, the only bit that would be anywhere near would be the anaconda pipe on top of the service, I would have done that before the board change to give me better access
@electrician247
@electrician247 Год назад
Gas fitter is on it. Wasn't that hard tbh and we had other issues to resolve that meant the board change couldn't wait. We don't touch gas but apparently it has lead pipe off the meter so fun times all round 🤭
@gregevans8939
@gregevans8939 Год назад
Is the labelling of circuits the final version ? I noticed you have 2 circuits both labelled "Sockets" ?
@electrician247
@electrician247 Год назад
Yes final labels. House is wired with a very mixed bag after conversion of old storage heater points into a ring in the past. Description beyond that both not required and very difficult.
@three-phase562
@three-phase562 Год назад
That is pretty old kit! Whilst there are issues with it according to modern standards, it may well have been a perfectly acceptable install at the time, not sure when the regulations requiring separation from gas and same entry hole for tails first came along.
@electrician247
@electrician247 Год назад
Yeah nothing horrendous about the work. Just due to changes over time. That CU on the right was tiny in terms of wiring room. We are very lucky today
@Ste2023
@Ste2023 Год назад
Absolutely Shocking ..... is that social housing? Installation 🏃🤔
@nigelman9506
@nigelman9506 Год назад
I was an NIC EIC inspector, the workmanship was perfect but was the gas pipes earthed ?
@electrician247
@electrician247 Год назад
Not before we arrived 🤭 but yes when we left
@christopherhulse8385
@christopherhulse8385 Год назад
What came first? the gas or the electricity?
@electrician247
@electrician247 Год назад
Both together I would imagine on the first construction in approx 1970
@rjkelectrical6086
@rjkelectrical6086 Год назад
What is the required measurement from a gas metre to a fuse board? 150mm or 1metre?
@electrician247
@electrician247 Год назад
It's at the end of the video mate. Few varied interpretations from 150mm to 25mm. I think 150mm makes most sense to me.
@jemseed
@jemseed Год назад
Thats a relic lol
Далее
Smart Meter Disaster!!
16:33
Просмотров 375 тыс.
Добрая весть 😂
00:21
Просмотров 269 тыс.
Things to know BEFORE starting on a Switchboard
8:06
British Gas enforcement raid Liverpool takeaway
5:16
How To Box In A Fuse Box. Keeping It Neat And Tidy
11:22
How To Install A Fence From Start To Finish!
10:14
Просмотров 242 тыс.
The REAL Problem with Smart Meters
20:05
Просмотров 429 тыс.
Добрая весть 😂
00:21
Просмотров 269 тыс.