Omron/Yaskawa V1000 VFD remote mode control, 2 wire control and 3 wire control. Parameter set up and speed control with potentiometer. For manuals, parts and related videos please see below.
Direct contact on Linked in: / ingus-sudints-1b2a2517a
Omron V1000 drive: igselectronics.co.uk/products...
Website: igselectronics.co.uk/
eBay store: www.ebay.co.uk/str/IGSElectro...
Omron/Yaskawa V1000 inverter drive local control, parameter set up, Factory reset: • Omron/Yaskawa V1000 in...
Run a 3 phase motor on single phase power, basics: • Run a 3 phase motor on...
Single phase to 3 phase VFD drive home setup: • Single phase to 3 phas...
Omron V1000 manual, Quick Start Guide: assets.omron.eu/downloads/man...
Omron V1000 manual, Full: omron-russia.com/doc/inverter/...

Опубликовано:

 

5 ноя 2020

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 8   
@vladimirseparovic
@vladimirseparovic Месяц назад
Thank you for video,i i have V1000 connected to the fan touch panel controler,but when i am trying to run the fan from the control panel it is not working even i can see/change controls on the touch screen and on v1000 drive i can see that freequecy is matching the input on the touch panel/controller...but fan is not working...the only possibility is to run the fan by pressing/changing V1000 the local and then change frequency....is there any video that may help me please?Thank you!
@renew6255
@renew6255 19 дней назад
Hi Ingus, I have been following your RU-vid for quite a long time now. I have a challenge recently on Yaskawa v1000 vfd. It was initially on source mode and was later changed to Modbus when the machine electronic board got burnt. The owner of the washer(Atoll 350) sent the vfd to Germany for reprogram to a new upgraded electronic board. Now, the upgraded board and the vfd came and it was installed but it is not working as it should, the motor rotate very sluggishly and pausating as if there is serious friction but when rotated by hand it's very free. I tried to gain access to the inverter all to no avail, only A1-01 and A1-04 could be accessed. What can I do and what parameters will I adjust as there is no handy manual. Thanks.
@germona
@germona 3 года назад
Ingus, is it possible to wire-up only the input mains (R,S,T) , and not the output wires to the motor (U,V,W), to program or setup the drive? Thanks. Jean
@IGSElectronics
@IGSElectronics 3 года назад
Hi Jean. Yes, you should have no problem with that, if you try to start without motor connected, it might come up with error no motor or current rush, or something like that.
@germona
@germona 3 года назад
@@IGSElectronics Thank You.
@TheRumbman
@TheRumbman 2 года назад
Hello, I have got J1000, running in 2wire mode. I want to add emergenscy stop, but my switch is normally closed and works in opposite way, can i change it behavior? Thanks.
@IGSElectronics
@IGSElectronics 2 года назад
Am not sure about this drivemy friend. Some drives allows you to that some don't, you need to check manual for that information. Usually comes under i/o section.
@TheRumbman
@TheRumbman 2 года назад
@@IGSElectronics Thanks, I downloaded FULL manual, instead of Quick starter guide. And reprogrammed input S3 from external fault to Fast Stop N.C. It's H1-03 = 17 (it was 24). And changed stop speed on C1-09 to 2sec. Now it works nice.
Далее
Редакция. News: 128-я неделя
57:33
Просмотров 1,8 млн
How to Wire-Up a Yaskawa V1000 AC Drive
5:20
Просмотров 248 тыс.
Yaskawa vfd 3wire control
5:19
Просмотров 192
How to wire a  VFD / variable frequency drive
5:02
Просмотров 704 тыс.
yaskawa V1000 Remote control
3:30
Просмотров 4,3 тыс.