Tool List- www.amazon.com/shop/acservicetech Support- www.patreon.com/acservicetech For those that are looking for the tools used in the videos: (Linked Below) Here is the Link for the Yellow Jacket Refrigerant Manifold Gauge Set used in the videos- amzn.to/2aenwTq Here is a link to Refrigerant hoses with valves used in the videos- amzn.to/2aBumVI Here is a link to the UEI DL389 Multimeter used in the videos- amzn.to/2xAdaJf Here is a link to the Imperial 535-C Kwik Charge Vaporizer for Charging Refrigerant- amzn.to/2wFHtBW Here is the link to the Fieldpiece ST4 Dual Temp Meter- amzn.to/2wc1ME3 Here is a link to the Digital Refrigerant Scale used in the videos- amzn.to/2b9oXYl Here is a link for RectorSeal Bubble Gas Leak Detector amzn.to/2ckWACn Other tool links can be found in the video description section. ACSERVICETECH is a participant in the Amazon Services LLC Associates Program, an affiliate advertising program designed to provide a means for sites to earn advertising fees by advertising and linking to Amazon. Check out other videos on the HVACR topics of interest at- ru-vid.com/show-UCOZR-1IqsAer9wzlvFgb4mAplaylists?view_as=public If you want to support the ACSERVICETECH Channel and receive more HVAC content, check out www.Patreon.com/acservicetech
If you want to support the ACSERVICETECH Channel and receive more HVAC Content, Correspond, or Collaborate on your endeavors- check out www.Patreon.com/acservicetech All of the ACSERVICETECH Playlists- ru-vid.com/show-UCOZR-1IqsAer9wzlvFgb4mAplaylists?view_as=public Submit your email to the ACSERVICETECH email updates list at info@acservicetech.com
like all your other videos acservicetech great great great videos man but this one's off the chain...if you can keep making more videos like this one and the one before would be great...I think you are the only one who have videos explaining pressures and the simtoms for the reading pressure....keep it up 👍👍👍
This reminds me last fall I was starting up 2 carrier splits,410a,micro channel condenser with txvs. charge was weighed in and I could not get more than 2 degrees superheat. Took charge out,check for proper air flow and duct sizing,nothing worked. I was told that new units with micro channels run with small superheat numbers for effiency reasons and you wont get 8 to 12 degrees superheat like older units. What have you heard about this?
These units all want to be charged using each manufacturer's instructions using vapor pressure, high pressure, high pressure line actual temp using charts, or subcooling by itself. What was the model # of the units? I am wondering if they have an accumulator and I am assuming you were charging with subcooling with a txv but just checking the superheat for safety for the compressor. Thanks
The subcooling was correct according to manufactures specs.I was thinking about adding an accumulator. I was thinking txv was not feeding properly,I know carrier had the problem with the rust inhibitor used in production was causing issues with txvs and had a massive recall. It was weird with the low superheat though.
I got an r22 unit that when filling the high side will not get above 100 psi but low side is looking around normal at 70psi.. filling took waaaay to long.. like 4 hours for 6 lbs.. i replaced the filter and repaired a blow out at the compressor and drained and repkaced the oil with recommended stuff.. dunno whats up. Im a newbi on heatpumps..
I recently had a low suction and low discharge pressure. Superheat was 10 F and subcooling was way up there at 27 F. I had 64F on return and 44F at supply. filter was clean. TXV bulb was mounted and insulated. I didnt find a temp difference at filter drier. It was a 2 story house and had only 2 returns on main level. I suspect it needs a return on 2nd floor.
What were the pressures and refrigerant type? Also you said it was low suction and discharge. Was it a low temp outside? You already hit part of it right on the head since the return temp was so low. That low of a return temp would put the sat temp on the coil very low.
it was a bit below 65 outside. Odd weather in Colorado for June..All week was 90. It was 410A. Suction pressure was a bit above 50 and discharge a bit above 120
Ive got an R22 system that has 55 degree air coming out of the vents. Low side pressure of 70psig high side pressure of 170psig. I feel like the high side is too low. 85 degree day outside.
I was charging a unit which iam going back sometime this week , I couldn't get the head pressure up as well as the low side ive already cleaned the a coil and the blowerfan motor didn't do a delta t, I suspecting its going to be the orfice I added quite of bit of Freon I should stop a coulple pounds lol live and learn , but now that I think I did raise the head pressure but not the low side
Definitely check the subcooling and superheat as well as the delta t. You may be right with the liquid line restriction but it could also be a clogged evap coil or some other airflow restriction. Check the videos out with the pictures of the gauge sets that say low pressure or superheat on them- ru-vid.com/video/%D0%B2%D0%B8%D0%B4%D0%B5%D0%BE-lpHpfCEq8IY.html
The blue side reads 226 psi, the red reads 75 for r410a (pink), my outdoor temperature on the Liquid line is 82 degrees. My unit requires 14 degrees subcooling. What could be wrong with my unit? Freon was recently added to my unit by a service tech.
The super heat is expected to be high with a restriction or low charge..Low super heat is a low load condition such as dirty filter bad duct design , plugged coil dirt..etc. You could have both problems on old systems hat had not been checked for years.
I replaced my piston # 59 I also have filter drier but forgot recovery machine and couldn't replace due to being inside condenser so while pumped down couldn't do but the first time I tried pumping down it did nothing the second time after closing the high side both sides came down at the same time ?? Compressor issue / I checked everything you asked me to last time and I couldn't find any restrictions in the ductwork and coils clean / also have liquid Refridgerant in low side when hooking gauges up
I'm sorry, Matthew are you talking about the unit that you said has 14-17 degrees of subcooling or the one with what you said you think is negative -45 degrees of subcooling?
acservicetech no this is the one at my House and you told me to check all the things in this video firstThe saturation temperature was below freezing with the correct superheat but I noticed the other day I was having trouble pumping down the refrigerant into the condenser it took a couple times so I don't know if a bad compressor can give you the symptoms in this video
Both sides will come down because the hoses are attached to your lineset with the liquid line closed. That is fine. I think I was saying you are looking at an airflow issue on this one and not a liquid line restriction. I think you are referring to the thermostatic expansion valve video I put out recently and the comments on that one. I don't have any threads from you previously on this video. Thanks Matthew
Yes but I couldn't find any issues with the the evaporator being dirty the only thing I haven't checked was the blower motor yetI looked at it the other day and it is dirty I'm gonna clean it when I get a chance I just noticed with the pump down the first time I tried it wouldn't pump down and also I had liquid refrigerant in my low side when I hook my gauges up and I've never had that issue before
I had a r22 system that showed like 20 degrees in suction side and 200psig on high side. what could that be? I tried adding some to see if it did anything. suction side went up and then dropped immediately. high side didn't move the whole time.
What was superheat, subcooling before and after charging? What was outside and inside temp along with wb inside. Piston or orifice? thanks Sounds like you didn't have enough heat to absorb on the evap coil. How was airflow?
Anthony Johnson I think the refrigeration system on a commercial vehicles, the charge is weighed in. So I would recommend buying coil cleaner and clean your coils.
Yes Ron is right, you would weigh in on packaged rerigerators and even split ones. You could use the liquid line sight if equipped when the receiver is drained at full load to determine if you have a steady stream of liquid present. Thanks