Repairing a 20 Year Old Rheem Heat Pump!  

HVAC GUY
Подписаться 66 тыс.
Просмотров 39 тыс.
50% 1

In this video I return to the system that had a leak where tow pipes had rubbed together! #hvacguy #hvaclife #hvactrainingvideos #hvac #airconditioner #hvactechnician #furnace #hvactroubleshooting #heatpump #hvacinstall #leakrepair ‪@ruud‬ #skilledtrades #bluecollarpride #vatodeclimatizacion
Merch Store : hvac-guy-2.cre...
Here are links to the tools I use, And it costs you nothing extra to buy from this list:
Makita Wet/Dry Vac: amzn.to/3VVHpsz
Veto OT-LC: amzn.to/3wSK1Nj
Appion AV760: amzn.to/3OkrwHC
Fielpiece SC680 Clamp Meter: amzn.to/33rhxvE
Fieldpiece SC480 Clamp Meter: amzn.to/33kfgCB
Fieldpiece SMAN 480 Digital Manifold: amzn.to/3twfVvA
Fieldpiece DR58 Leak Detector: amzn.to/3nt1TXw
Fieldpiece JL3KM2 Bluetooth Manometer set: amzn.to/3blMrJR
Fieldpiece Bluetooth Scale: amzn.to/3Gzveab
Fieldpiece SDMN6 Manometer: amzn.to/3qwk9RP
Yellow Jacket Tubing Expander: amzn.to/3sjuK3a
Milwaukee M12 Impact Driver: amzn.to/37xXkqk
DIY Vacuum Attachment for drains: amzn.to/3tDpfNU
Fieldpiece Smart Probe Kit : amzn.to/34NG3HL
Klein Heavy Duty Wire Strippers : amzn.to/3I8YNzT
Klein Needle Nose Crimpers/Stippers: amzn.to/3fuwXlw
Klein Knee Pad: amzn.to/3cy6FB0
Klein 7in1 Flip Socket: amzn.to/3bpabwG
Klein Journeyman Pliers: amzn.to/3tvB60w
Milwaukee Slim Packout On My Torch: amzn.to/3KeLm3j
Aluminum Packout Wall Mount on torches : amzn.to/3Kf9hQg
Milwaukee Tool Box: amzn.to/322iyK9
Veto Pro Pac Tech MCT: amzn.to/3nwwQdA
Milwaukee Hook Blade Knife: amzn.to/33F3m5T
Testo 300 flue gas analyzer: amzn.to/3IcS3Bd
Western Nitrogen Regulator: amzn.to/3rmdKrx
Klein Canvas Bucket: amzn.to/3FyzKVf
Flag Velcro Patch Kit: amzn.to/3K8Eswx
Supco Magnetic Door Switch Holder: amzn.to/34IcXcL
Milwaukee Magnetic Light: amzn.to/3FulCfF
Milwaukee Rechargeable Headlamp: amzn.to/3nuXsvf
SS2 Float Switch: amzn.to/3K7LJMW
3-Amp Breaker: amzn.to/3nxaSXJ
Appion Valve Core Removal Tool: amzn.to/33CFArw
Appion G5 Twin Recovery Machine: amzn.to/33Dvd6C
Yellow Jacket Large Tubing Bender: amzn.to/3qwJv1U
Similar Small Tubing Bender: amzn.to/3fJsziJ
Fluke Twist Guard Test Leads: amzn.to/3216R6j
Honeywell T-4, 2-Heat, 1-Cool Programmable Thermostat: amzn.to/3qtIuaX
Kidde Carbon Monoxide Alarm: amzn.to/3qtIIyP
SolderWeld Flame Resistant Magnetic Blanket: amzn.to/3qtJ4Wb
Malco 1/4 - 5/16 flip bit : amzn.to/3nr67yU
Quick Check Acid Test: amzn.to/3GA2XAy
Wiha Torqe Screwdriver : amzn.to/3u1swH6
Wiha Torqe Screwdriver 1/4” adapter: amzn.to/3IH22Pw
Compressor Tote: amzn.to/3H8xHst
Inspection Mirror: amzn.to/3r9PERV
Wiha TorqueVario-S 10-50 in/lb Torque Screwdriver : amzn.to/3GbKAku
1/4” adapter for Wiha Torque Screwdriver : amzn.to/3u8g0pq

Опубликовано:

 

10 сен 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 256   
@billyk5107
@billyk5107 3 месяца назад
I was at a job yesterday and the guy told my customer he needed new equipment he couldn’t get the unit to run . He had wired the capacitor wrong and when I turned, the unit on the fan was running backwards I rewired the capacitor the right way, and the unit came on and is running fine. No need for new equipment ya baby
@joshcade918
@joshcade918 3 месяца назад
No parts required!
@1985230ce
@1985230ce 3 месяца назад
Probably did it on purpose so he could sell a new unit.
@billyk5107
@billyk5107 3 месяца назад
@@1985230ce yeah right I wouldn’t doubt it
@adamrspears1981
@adamrspears1981 Месяц назад
If a unit is out of warranty, I give my customer both options & let them decide how to spend their money: For this price, I can repair it. For this price, I can replace it. Which one do you want to do?
@danburch9989
@danburch9989 3 месяца назад
Other than the compressor, evap & condenser coils and motors, I can't see the need to replace an entire unit just because it's 20 years old unless parts aren't available. I would have to budget $100/mo to cover the cost of two heat pump units for my home. Probably a little more to account for 15 years of inflation. In my previous home, I paid $3000 for a roof top heat pump. I never had it serviced. To maintain the 10 year warranty, I had to have it serviced 2x/yr (cooling & heating seasons). I didn't have it serviced. That saved me $50 x2 per year on service costs. It finally failed in its 11th year. Cost of repair $495. My current home with two heat pumps needed 2 motors and two capacitors over the 20 years we've been living in the homo. Annual service would not have prevented those failures. I keep the filters changed and the coils clean.
@jthonn
@jthonn 3 месяца назад
I didn't think that was going to happen. I guess it is still cheaper than a new install, if it holds up for a while. Nice work
@HVACGUY
@HVACGUY 3 месяца назад
Thanks
@alandahlstrom7213
@alandahlstrom7213 Месяц назад
In all my years of HVACR one unmistakable truth is, no one is more critical of a service tech than another service tech. There is sometimes more than one right way to do a job properly and I have to say that after watching a few of your videos, I like the way you do things. Nothing made me happier than when you cleaned out those leaves and washed the coil. So many techs would not have bothered cleaning out that debris and it is this attention to detail that sets you apart.
@a.v.3726
@a.v.3726 22 дня назад
Way to go the extra mile, the mark of a good technician 👍🏼
@user-qd6ir5qg2v
@user-qd6ir5qg2v 10 дней назад
@@alandahlstrom7213 the job being done is no better than the person doing that job, no matter what fanciful company they call out to fix the problem
@lazyjack8081
@lazyjack8081 3 месяца назад
Tough place to braze. Had an old hand back in day tell me "Solder down and braze up". Took me a few time to get the hang of it, but way better . You get the hidden part done first, before eyes are watering from the brazing fumes.
@kelvinandrewssr9194
@kelvinandrewssr9194 2 месяца назад
As a residential roofer over 33 yrs , yes the price exactly right. When we disturb or move these old units causing damage to the lines.
@props-model-shop
@props-model-shop 3 месяца назад
I have had mutiple Rheem units lasting over 35 years. They were built like tanks back in the day.
@STho205
@STho205 3 месяца назад
Not this one. This model is a lemon.
@joshcade918
@joshcade918 3 месяца назад
@@STho205 Yup nailed it on the head... Only been over 20 yrs running... Replaced the caps and had to repair a line that rubbed against another component. If my eyes don't know what a lemon looks like, they sure do now!
@STho205
@STho205 3 месяца назад
you don't know how often this thing has been repaired. I had one on a property that had to be repaired every 2 to 3 years for it's life. It chewed through capacitors regularly, overdrew power, loud as hell even when new, burned out a blower fan twice, the top fan once....and the coil lines also wiggled and rubbed on each other causing leaks that got brazed and refilled three times. Being a Pkg unit it is hard to replace with anything better as only a couple of companies make them...and then brand names get riveted on. Most Pkg units are crap built for old mobile homes, school portables and construction trailers To put in a competitive traditional unit a complete re-ducting gut job is needed to the house...as well as finding an air closet for the inside handler. This is why people keep patching it. The $6000 duct work atop a new $4000 unit. As to this job, He's awfully high as it is a 1 yr patch....but he was really trying to sell one of 2 or 3 new unit quotes (likely over $8000 each). The $2000 repair was to nudge him. However he didn't have the cash or will to drop another $10k on this aging house....so he got it repaired and agreed to the quote If someone tells you they'll pay $2000, few AC companies say ..ahhh kidding, it's just $500
@STho205
@STho205 3 месяца назад
@@joshcade918 if good multizone mini splits existed 40 to 25 years ago, then these underhouse bad duct units should have never been installed in old houses that didn't have ducts originally.
@glennschlorf1285
@glennschlorf1285 2 месяца назад
@@STho205 its still crooked way to manipulate
@jamminwrenches860
@jamminwrenches860 3 месяца назад
Positive pressure when sanding. That hole was big enough for debris to enter the system.
@markbeiser
@markbeiser 3 месяца назад
He set up his nitrogen purge before he started sanding.
@panamacitybeachbum
@panamacitybeachbum 3 месяца назад
Sweating in a drier that close to the TXV can be detrimental. Applying heat sink gel, or wrapping the TXV with a wet rag just makes sense.
@Mapdotgolf
@Mapdotgolf 3 месяца назад
Yeah crazy how much heat he got and brazing like that next to txv 🤣
@Harold-si7eh
@Harold-si7eh 3 месяца назад
Brush on and heat sodder gel get where you can not see!
@jamesbaker429
@jamesbaker429 2 месяца назад
You could see that rad covered in dried grass so a third of cooling compromised taking off the covers and doing it properly is another job adding to bill ,service seems to have been ignored on this old installation,hence it's cost them more to run then if service had been done.
@Eric-696
@Eric-696 2 месяца назад
Man that thing was dirty!!!😅
@dperreno
@dperreno 3 месяца назад
Glad to see that you were able to patch that up and get it running again.
@billsimpson604
@billsimpson604 3 месяца назад
I've been running a 4 ton R22 unit without a dryer for 12 years. Worse, the people who installed the new condenser unit never evacuated the system. They just blew some nitrogen through it and charged it with R22. I expect failure any day, so I got one of those portable AC units, so I don't die waiting to get it replaced when it does go out. I noticed that it wasn't level, but decided that trying to level it after years of running the scroll compressor like that might mess it up, or crack the copper lines going into the brick wall. So I left it alone, remembering the saying, 'If it ain't broke, don't fix it'. Once the capacitor running the fan motor failed while I was cutting the grass. The motor got so hot that it boiled off the water when I first tried to hose it down. That was about 6 years ago, and the motor is still running. It was made in India. They made a good motor !
@SkilledLabor
@SkilledLabor 3 месяца назад
They most likely sweeped it with R-22 instead of pulling a vacuum.
@TxGuitarPlayer
@TxGuitarPlayer 3 месяца назад
Best tools in the business. Sure enjoy watching you. I almost try to climb through my screen to help sometimes lol😅. Especially on those self tapping screws mounting those capacitor straps 😂
@billybobosullivan7084
@billybobosullivan7084 3 месяца назад
me too. I had to jump forward a couple of minutes during that. I couldn't look, it was too painful.
@staind288
@staind288 3 месяца назад
I'm so happy that you did this for the customer.
@frarob6139
@frarob6139 3 месяца назад
A voiceover explaining what you are doing, kind of gases being turned on and off, etc would give you a wider audience for your videos. You do a great job having the camera pointed at what you are doing.
@pogonomyrmexrugosus6240
@pogonomyrmexrugosus6240 2 месяца назад
This isn't supposed to be a tutorial. You do a great job at bitching about content you're not paying for.
@robalexander7348
@robalexander7348 3 месяца назад
Nice repair Curtis, this will keep it running for a few more years 👍 Au
@HVACGUY
@HVACGUY 3 месяца назад
Hope so
@stevencossaboon3237
@stevencossaboon3237 3 месяца назад
Nice work Curtis. Another one brought back.
@HVACGUY
@HVACGUY 3 месяца назад
Thanks
@rcf8367
@rcf8367 3 месяца назад
Great job keeping that running Curtis!
@OcRefrig
@OcRefrig 3 месяца назад
Good video ! Rheem units - nothing better !!! curtis - anything under 299 is ok on old r-22 systems remember head was 30 over in those days.
@danobrien3109
@danobrien3109 3 месяца назад
Nice save on an old unit Curtis.👍👍🇨🇦
@HVACGUY
@HVACGUY 3 месяца назад
Thanks 👍
@thepoopsoup
@thepoopsoup 3 месяца назад
New units cost less than 1/2 on energy cost to run
@AaronPowellvox
@AaronPowellvox 3 месяца назад
Now they have at least 2 degrees less cooling capacity. I just hate those replacements but they are necessary for jobs just like this. The cost of R22 would not have made sense to use. Great work as usual.
@justincrafton6105
@justincrafton6105 3 месяца назад
For what he charged to repair that unit, he should have put R22 instead of R438a. If I'm not mistaken, the repair quote was $2000 ! Way overcharged for that repair, in my opinion !
@joshcade918
@joshcade918 3 месяца назад
@@justincrafton6105 Not sure if it is in my area... A new neighbor thought they got a wonderful deal on an entire replacement of their HVAC system, ductwork and all, for 20k. Their current system was functioning too... But apparently they decided to shop around and replace everything anyway after moving in. Fascinating, isn't it.
@DWNTWN-iu8vf
@DWNTWN-iu8vf 3 месяца назад
I gotta say that you really keep your tools & equipment well organized!
@woodystokes1543
@woodystokes1543 3 месяца назад
Tech tip for the hoses appion makes a plastic threaded piece that will keep it clean.
@abtechgroup
@abtechgroup Месяц назад
The bottom of the meter is a bar graph representation of the numbers (the 4 blocks on the left side are the Negative side - the 3 blocks on the right are the Positive side) - and it has 3 different views 1) the 10 second average of the change in pressure per minute; left side blocks are filled would be decreasing; right side blocks filled would be increasing; and no blocks filled means no change. 2) the non averaged real time change. 3) graphical view of the measurement - all blocks on is no vacuum - all blocks off is lowest possible vacuum. These 3 views are selected in rotation with the "next" button. Fieldpiece is a great little tool. Love your videos
@mikephillips8648
@mikephillips8648 Месяц назад
I have no idea why I like this channel but I do !
@moshemoshe-yy8hj
@moshemoshe-yy8hj 3 месяца назад
Very funny everybody has an opinion you doing the right job keep giving it an option
@alejandromata825
@alejandromata825 11 дней назад
I had a very, very small stress fracture on a compressor’s piping in a condenser split system on a roof that I just couldn’t pin point and had to use dye like a goober and then drape a bunch of drop cloths over it like a really hot Indian sweat lodge to make it dark enough to see the dye. Lost so much water that day I had to deal with leg cramps at night.
@orinmangar2333
@orinmangar2333 3 месяца назад
Sometimes it is nice to bring the old unit back to life. They r built like tanks.
@kg4muc
@kg4muc 3 месяца назад
Great job on the fix!!
@HVACGUY
@HVACGUY 3 месяца назад
Thanks 👍
@DavidJohnson-yd2jw
@DavidJohnson-yd2jw 3 дня назад
After 40 years as an HVAC owner and tech, the biggest killer of any heat pump is Green Slime, when moisture gets into the unit and mixes with the compressor oil due to a refrigerant leak when during low pressure it will allow the sucking in moist air into the unit. This unit will probably die this summer or during next winter. You should have condemned this unit, Next time using a torch near the expansion valve use a wet rag to keep it cool, it does not take too much heat to damage it. You did use a bi-flow filter this was correct. Were you able to check the air filter?
@ricardocastaneda4541
@ricardocastaneda4541 3 месяца назад
Idk if anybody else has mentioned it but I appreciate the fact that your always changing/improving your work bags etc , I’ve been disliking my Victor tote & been looking for an alternative , ima give what your using a try. Awesome videos , I enjoy watching on my lunch break sometimes 🔥
@abcdefghi2175
@abcdefghi2175 3 месяца назад
curtis please wear gloves you know what they say neglected infected disconnected LOVE YOUR VIDEOS
@joshcade918
@joshcade918 3 месяца назад
What?
@FrankCastle-he8fl
@FrankCastle-he8fl 19 дней назад
My I suggest a shop vac for cleaning up all the debris and not catching anything on fire when you are brazing
@shermanmaddoxrcpc774
@shermanmaddoxrcpc774 3 месяца назад
0:58 I guessed a jbweld fix. Of course I could be wrong 😂
@stephenhubbinett1287
@stephenhubbinett1287 3 месяца назад
great job
@HVACGUY
@HVACGUY 3 месяца назад
Thanks
@jasonwood7340
@jasonwood7340 27 дней назад
I liked your video, you may want to double check your acetylene regulator pressure. In the red ain't good.
@thesilentonevictor
@thesilentonevictor 3 месяца назад
Great job under this situation just want to know could you not find any other location to place the dryer and the discharged line
@darongilliam3585
@darongilliam3585 3 месяца назад
Why didn't you use a two-way filter made for a heat pump?
@toddhodges4914
@toddhodges4914 Месяц назад
He did
@justincrafton6105
@justincrafton6105 3 месяца назад
Can someone please explain why this repair cost $2,000 ?
@anthonylewis8733
@anthonylewis8733 3 месяца назад
I’m not an HVAC guy but I assume labor was about 2 or so hours total for about $300, parts of $50 or so and the rest Freon cost. Freon had to be completely refilled and Freon is never cheap.
@CarlosTorres-tf6il
@CarlosTorres-tf6il 3 месяца назад
Finding a leak, welding a leak, vacum and charging the unit. These repairs are not cheap. 2000 is a fair price.
@CarlosTorres-tf6il
@CarlosTorres-tf6il 3 месяца назад
I'm in los angeles California area. Most companies will just try to sell you new equipment for $20,000.00 dollars
@robertwittenburg6143
@robertwittenburg6143 2 месяца назад
@@CarlosTorres-tf6il Bullshit. There should be a labor rate per hour and looks like this guy's rate was over $400.00 an hour. R22 replacement refrigerant costs about $30.00 a pound so at most $300.00 for that system. Total ripoff. Ignorance on the homeowners part for agreeing to that price.
@glennschlorf1285
@glennschlorf1285 2 месяца назад
​@@robertwittenburg614330 a pound for refrigerant really... R22 has been discontinued its in short supply
@browntigerus
@browntigerus 3 месяца назад
That is very sweet nitro regulator.. Good job in a very tough spots.
@franciscotejeda1461
@franciscotejeda1461 3 месяца назад
Good video Mr Curtis
@HVACGUY
@HVACGUY 3 месяца назад
Thanks
@NoahbHvac
@NoahbHvac 3 месяца назад
Just worked on the same unit but had an audibly leaking evap. Customer wants to replace it…
@a.v.3726
@a.v.3726 22 дня назад
He charged for his time, experience, overhead, parts and labor. $2000? In New York, this would have been $5000+. Keep up the good work, brother 👍🏼
@johnhovorka3062
@johnhovorka3062 4 дня назад
Flux around the tubing should have pulled that solder in.
@user-su5ft8lc9q
@user-su5ft8lc9q 3 месяца назад
Another Great repair under your belt and bucks in your pockets. Repair made by the GEORGIA EXPERT OF HVAC.
@edtruax7721
@edtruax7721 2 месяца назад
Enjoyed watching!
@Hvacnc
@Hvacnc 3 месяца назад
I say anything below 1000 microns is good. I was taught 500 in school but when I replaced some trane compressors they would say anything below 1000 is good 🤷‍♂️
@brianward2250
@brianward2250 3 месяца назад
I did like the video. Nice work man.
@michaelhancock9098
@michaelhancock9098 3 месяца назад
Your knowledge is impressive
@gaoutdoor4372
@gaoutdoor4372 3 месяца назад
Good job my friend! What camera do you use , video quality very good.
@HVACGUY
@HVACGUY 3 месяца назад
GoPro 12
@woodystokes1543
@woodystokes1543 3 месяца назад
Nice 😊 work 😊
@tkonzl6059
@tkonzl6059 3 месяца назад
I realize that the leaking areas need to be cleaned, but are there particles getting into the pipes? If so, do they need to be cleaned out? If so, how does this happen?
@buffalobobbayoushow6040
@buffalobobbayoushow6040 3 месяца назад
Some times an old evaporator will begin leaking after you pull the system into a vacuum. The coil has been at positive pressures for years and the copper turns can’t take the contraction that the vacuum creates. Make sure the customer understands this can happen when making the decision to repair or replace!
@gabrielstern4992
@gabrielstern4992 3 месяца назад
Nice job Curtis I guess you must put a little more MO 99 in as a replacement for r 22 to compensate for the capacity loss or put the factory amount in first of the mo99 to get the system running then add the amounts of extra mo99 as needed until the pressures and temps read like it did when it had r 22 in it and sweats back properly. While monitering the high and low side pressures. Also I hope mo99 is not one of the refrigerants bieng phazed out I know 407 c is and honestly if the custumer wanted to pay extra you could have dumped out the mineral oil and replaced it with poe 32 and put 407 c in it but the again what refrigerant would have made a good replacement for that unless mo 99 can work with poe oil. They just made it too complicated when the switch to 410 a happened when they should have just switched to 407c and instructed hvac techs to dump out the mineral oil and replace with poe and flushed out the linesets and evap coil then vacaum for 40 minutes to remove the residual flush solutions and replace the receiver dryer or filter I see you replace often on the linesets just like when the switch on cars happened in 1994 from r 12 to 134 a and Curtis the instructions on cars were dump out all old mineral oil flush linesets out flush the condenser and evap using nitrogen or compressed air and flush solution until it comes out clear the add Ester oil to compressor and new reciever dryer. Then hook up vacaum out system for 40 minutes then let sit for 20 minutes to make sure it held the vacaum the charge up with r 134 a and those same concepts should have been applied to residential hvac not all this extra mumbo jumbo and use this refrigerant that refrigerant it's about what works. And converting should have been done 15 years ago. Not like what's happening now anyway good job as usaul
@HVACGUY
@HVACGUY 3 месяца назад
It almost always takes a little more than factory charge. That’s just a starting point.
@gabrielstern4992
@gabrielstern4992 3 месяца назад
@@HVACGUY thanks Curtis as I am considering maybe studying for hvac and taking the tests just so I can do my own stuff in my condo community. But first I need to finish getting this lyme desease out of my body which could take several months as it had went after my eyesight which is now really starting to come back but also ended up rupturing my ear drum which is still healing and caused a lot of swelling and inflammation in my feet and all over my body. I just wish more techs were like you and took the time to do just do what the custumer needs and wants without pushing constantly new systems on them. As they can't always afford them right away.
@gabrielstern4992
@gabrielstern4992 2 месяца назад
@@hilljack6765 you were lucky did you use an ester oil charge or a, pag oil charge. But if you converted you should have disconnected the lines removed the compressor dumped compressor oil out and either filled with pag 100 or ester oil. Then flushed out the line sets condenser and evaporator and used pressurized air from a compressor to blow until clear. And that's do to possible sludge and debris. That's why you do it that way on a old scholl car the new style car condensers you cannot flush out but they are only around 100 dollars. Maybe it's just me but I don't like cutting corners
@gabrielstern4992
@gabrielstern4992 2 месяца назад
@@hilljack6765 I know that but you still have to dump out the mineral oil from the compressor and disconnect the lines then do a, system flush then vac for 40 minutes then you can do the charge otherwise it's acid city.
@jimlarimer2104
@jimlarimer2104 2 месяца назад
I never make negative comments but this $2000 repair gives new meaning to the old phase Highway Robbery.
@TheMongoose69
@TheMongoose69 2 месяца назад
It's only highway robbery when you don't know what you do and you're charging people and exorbitant amount for doing crappy work if you're trained and perfect at what you do or at least close you're charging for your knowledge not the hours
@Lividash
@Lividash 2 месяца назад
he qouted a fix and a replacement. this is what they went with. customers choice here, no highway robbery.
@hoktang1
@hoktang1 2 месяца назад
You have to take into consideration that unit used r22. R22 runs at 150 to 200 a pound. Depends on how many pounds he has to replace. That is most of the cost of the repair. I think atleast 1400 of the bill is for the r22. Or they could have went with newer models to have a cheaper refrigerant in uses.
@gregdouglas5405
@gregdouglas5405 2 месяца назад
Why would it cost 2000 to braise this.
@hwesson75
@hwesson75 2 месяца назад
@@hoktang1 He used r438a, not r22. That's more like $20/lb.
@davidca96
@davidca96 3 месяца назад
Hope that lasts a while for them, sure isnt what id want with a system that old but old stuff was made better so, he may get a lot out of it. Curtis gets paid either way so 😁
@garypoplin4599
@garypoplin4599 3 месяца назад
15:13 - Oooh! _That_ doesn’t sound good!!
@christopherdelon3026
@christopherdelon3026 3 месяца назад
So that unit come from the factory without a filter dryer?
@HVACGUY
@HVACGUY 3 месяца назад
Yes
@ivanbg5167
@ivanbg5167 3 дня назад
Why is the dryer pointing the wrong direction in cooling mode? I see you installed a bidirectional dryer.
@garfieldwood8315
@garfieldwood8315 25 дней назад
14:40 "I didn't want that to get in the dirt" (Gived it a quick puff of air instead of flushing the line out with the bottle) 15:00 Proceeds to connect line to vacuum pump 15:15 "Great! Got dirt in it" )Turns vacuum pump on, alliwing dirt to be drawn through the vacuum pump) Wonders why his vacuum pump is worn out...
@badger305
@badger305 10 дней назад
Who makes the carry case for your oxy acetelyne tanks and hoses? It looks like some type of canvas tote.
@dondesnoo1771
@dondesnoo1771 3 месяца назад
There was a alcohol could be added yrs ago when a dryer was impossible dont know about today legal w new refrigerants
@butlerstouchHVAC
@butlerstouchHVAC 3 месяца назад
what tool bag model is that for the torches?
@davidwaite3420
@davidwaite3420 23 дня назад
Just remember that he is not setting the price his company is!!
@Always1fisherman
@Always1fisherman 12 дней назад
It would have been nice if the debris had been cleaned out.
@adamrspears1981
@adamrspears1981 Месяц назад
You might of burned that TXV. I hope you didn't though. I recommend using Viper Wet Rags.
@Alex-kv8zy
@Alex-kv8zy 3 месяца назад
do you wear shaded glasses for brazing? should i as someone new in the field
@bobward7489
@bobward7489 Месяц назад
Yes, nothing super dark, the darkness of regular sunglasses does the trick
@user-wn8mg2jh1d
@user-wn8mg2jh1d 3 месяца назад
I never understood why people don't maintain their outside units
@bobbysmith1439
@bobbysmith1439 6 дней назад
2k seems pretty steep to braze 2 lines and recharge
@donmarion8808
@donmarion8808 24 дня назад
The customer had the option of getting more bids based on what this gentleman estimated. This is what he accepted. Could he have gotten it cheaper? Maybe, maybe not. You pay for quality. In Arizona, it would have been expensive.
@edenmolinar2086
@edenmolinar2086 3 месяца назад
A portable shop-vac would be handy... and a bud light girl to keep you cool in that hot weather.😁
@mkl5448
@mkl5448 3 месяца назад
To everybody complaining about the money, nobody made the customer agree to the repair. He could have shopped it out, got three different estimates, and still went with this guy. Maybe that's the going rate in his area, yes it seems a little pricey, yes I'm not sure I would have put the money into it, but at the end of the day it's not my money. So everybody is simply relaxed and enjoy the work.
@hvachacker586
@hvachacker586 2 месяца назад
Whats your subcool (TEV system)? Whats the point of having a four port manifold if your purging refrigerant? Where is your scale? Also installing a biflow drier per most units should be on mixed gas side in heating mode. You now will run her starved on gas in the highest compression ratio mode of that unit. Last please wrap the TEV with a wet rag.
@jamesstumpff5877
@jamesstumpff5877 Месяц назад
Is he replacing that with R 22 or bluon ?
@Sattracer
@Sattracer 3 месяца назад
You do know that you can put some lab grade alcohol in your charging line as you add coolant and it will aid in preventing icing inside a line that has been open to the air and had to be resealed? I've seen that done many times in south Mississippi. It must be pure alcohol, the purest. It prevents the drier from clogging with ice.
@1985230ce
@1985230ce 3 месяца назад
What kind of alcohol?
@Sattracer
@Sattracer 3 месяца назад
@@1985230ce 99% Isopropyl Alcohol just fill your hose on the low side and fit back onto your gauges. Open the line and fill with coolant.
@churchlj8055
@churchlj8055 2 месяца назад
You guys complaining about the repair. This refrigerant costs more than gold these days.
@jimdavis6833
@jimdavis6833 2 месяца назад
Curtis, that's a bi-directiional drier. Sorry, I had to say it.
@philiphusain3923
@philiphusain3923 3 месяца назад
It’ll live a few more years ! What was your torch tip ?
@garfieldwood8315
@garfieldwood8315 25 дней назад
16:50 WHERE IS YOUR CORDLESS SHOP VAC?
@user-qd6ir5qg2v
@user-qd6ir5qg2v 15 дней назад
Was that the 2000 dollar zip tye
@jeremyfogt6798
@jeremyfogt6798 3 месяца назад
Looked like a bi flow dryer, so why would it only work in cooling mode? I like the fix, for some reason I thought you would cut out and put new pipe in. I guess the nitrogen keeps it from going in the pipe.
@JustinMiales
@JustinMiales Месяц назад
We used to buy these Rayovac pool heaters now Rheem bought them out, is there a good units to mice don't get in there and show all the wiring up but they just need to be cleaned every season, diesel gas heaters for swimming pools not the heat pumps.
@randyprentice9292
@randyprentice9292 29 дней назад
Why would you not change the schrader valves while the system was empty? Those tools are for a fully charged systems. You made it harder than you needed to. And yes that old system will still outlast a brand new one.
@JustinMiales
@JustinMiales Месяц назад
I know automobile air conditioning is it the same where you have to vacuum purge the unit to get any contaminants out ?
@chuckmayerchak3071
@chuckmayerchak3071 3 месяца назад
I watch a lot of your videos, yesterday you said it was a 2,000 dollar repair. I'm just trying to figure how you justify that price. Parts and misselanius expendables your cost giving a wide margin for error 400 dollars. 60 percent mark up total 640 dollars service call 175 dollars? 4 hours labor?? Doesn't seem to add up.
@Mapdotgolf
@Mapdotgolf 3 месяца назад
Cause when you run a business you have more thing to pay for. You got van maintenance, gas oil tires, you got insurance for your business and your self. There a lot you don’t understand until you run a business and understand why we charge what we charge.
@Mapdotgolf
@Mapdotgolf 3 месяца назад
If he did that job for 1000 or less. He ain’t make any money.
@chuckmayerchak3071
@chuckmayerchak3071 3 месяца назад
All I know is I was a service Manajer in a Ford dealership for 50 years. If we made 40 % on parts and 150 dollars per hour on labor we were living large!!! And people call dealerships crooks!!! I was in the wrong profession!
@Mapdotgolf
@Mapdotgolf 3 месяца назад
@@chuckmayerchak3071 you sit in ac all day and we’re suit, not much to do selling a car. We work hard in heat and way more then you think. Most people can’t last doing our job
@homecraftsolutions3506
@homecraftsolutions3506 3 месяца назад
3 hours labor at 150/hr is 450. 50 in parts. 200 for freon at most. 50 trip charge. 750 to 1000. you must be a pretty good salesman. I have run a carpentry and a handyman business for the last 10 years and this seems like a rip to me. I know we need to make money but we don't have to make it all on one job.
@altechy7304
@altechy7304 2 месяца назад
Great job and video as well. What was the last part you installed like you inserted a cylinder in a pipe. Why install it if it wasnt there originally? Thanks for sharing with the world
@randyjennings9853
@randyjennings9853 2 месяца назад
I believe R22 is over a hundred dollars a pound.
@dcj2045
@dcj2045 24 дня назад
I love it how people ask $2000 is a lot of money huh? But the guy has to pay for school and has to troubleshoot knowledge is not cheap this insurance are reaping us up for billions of dollar nobody talks about that. they also have to pay bills.
@mikewhittaker5984
@mikewhittaker5984 3 месяца назад
Curt not trying to be mean but looks like a 3 year old did that braze job
@delavan9141
@delavan9141 3 месяца назад
Maybe removing the side cover would have resulted in a better job.
@gregsidel3557
@gregsidel3557 3 месяца назад
Great video good job I'd like to know what you did after that head pressure was going up
@JustinMiales
@JustinMiales Месяц назад
Most companies will tell you you need a new unit😢
@jeffkablock3229
@jeffkablock3229 3 месяца назад
man you need to use a number 2# tip and 7/11 on your oxg and cet
@philiphusain3923
@philiphusain3923 3 месяца назад
What is his torch tip?
@steveprice-n9b
@steveprice-n9b 2 месяца назад
NEVER quote what you are charging people on these kind of channels that should be common knowledge by now!
@badger305
@badger305 10 дней назад
Why not? Unless you are ashamed of the amount you are gouging people for!
@frankveronese1290
@frankveronese1290 3 месяца назад
Maybe someone knows yesterday on a 7 year ago Lennox had to have the air handler blower motor replaced. The new motor spools up or starts low then goes to full speed. Is this now normal on new motors.
@henryduke722
@henryduke722 3 месяца назад
He should have clean all the pine needles out
@ChrisHall02
@ChrisHall02 Месяц назад
$2,000 - easy, $450 of R22 marked up to $900, because he has to buy it, and keep it on his truck and eat any losses. 2 service calls, run capacitor, 4-5 hours of time, materials fees for things like solder, zip ties, screws, gas, etc. And, enough profit to pay for the truck, insurance, health, dental, income, sales and medicare/SS taxes if he's self-employed, and the cost of a potential callback, and then savings for retirement because no pension or 401k. The fastest way to go broke as a contractor is to charge too little for a job. This guy knows how to run a profitable business.
@hinspect
@hinspect 3 месяца назад
That ought to last a *_Long_* time! 😉
@HVACGUY
@HVACGUY 3 месяца назад
I hope so!
@mwreyf1
@mwreyf1 3 месяца назад
He quoted $2000 to fix this. It is ridiculous what HVAC people charge for a few minutes of work, regardless of their expertise. He has two capacitors and a brazed pipe in this job.
@imhooks
@imhooks 3 месяца назад
I'm hoping that was 2000 to replace the compressor and lines or something. Hopefully it wasn't 2000 to patch the holes in existing lines.
@bobward7489
@bobward7489 Месяц назад
A few minutes of work? Wow are you clueless. A couple hours on the previous diagnostic and probably 2-3 hours on the repair. 4-5 hours total. Add to that parts, refrigerant, insurance (vehicle, business, liabiliyy, workmams comp of he has employees), gas, depreciation on the truck, depreciation on the tools and it adds up quickly. But I'm sure you could could do it yourself.......🙄
@fidelgarcia5683
@fidelgarcia5683 3 месяца назад
no superheat or subcooling?
@dolfinwriter5389
@dolfinwriter5389 3 месяца назад
Why did it cost $2,000 to braze a couple of pipes that rubbed together? Not trying to be snarky--serious question.
@offgridwanabe
@offgridwanabe 3 месяца назад
For that kind of money I would install a mini split with solar and get free AC.
@robertgregory2618
@robertgregory2618 3 месяца назад
You have no idea how expensive that would be. none. Splits are super expensive installed. Not counting solar expense..
Далее
An Unusual No Cooling Call
22:56
Просмотров 160 тыс.
I Bought 5 Tools You Didnt Know Existed!
38:56
Просмотров 207 тыс.
Clogged AC P Trap worst ever
20:33
Просмотров 15 тыс.