REWIRED BY A CHIMPANZEE! Skeleton Board EICR 

Artisan Electrics
Подписаться 246 тыс.
Просмотров 175 тыс.
50% 1

REWIRED BY A CHIMPANZEE! Skeleton Board EICR
Things are getting a little bit spooky over at Artisan Electrics as we dive a Skeleton Board EICR! In this episode, Jordan and John are carrying out an EICR on a property that in Jordan's words, was rewired by a Chimpanzee. How many shocking discoveries do you think they'll find in this EICR?
Thanks to TRADIFY for sponsoring this video: Get 50% Off your first 3 months using our discount code "ARTISAN" here: bit.ly/37G9BZX
Subscribe to our RU-vid Channel for more great electrical content: ru-vid.com...
Get more from Artisan Electrics here!👇
linktr.ee/artisanelectrics
⏱️Timestamps
00:00 Coming Up
01:10 EICR Rundown
03:26 Worth Pointing Out
04:46 New Cut Out Fuse
06:07 Wander Lead Test
08:45 Not Earthed
11:16 A Tricky One
13:26 Classifications
14:47 Worst Thing I’ve Seen
16:47 Bathroom
17:55 In The Loft
20:05 Power Off
21:16 Bang Bang
23:42 Found The Problem
25:23 Really Rough
27:16 Half A Day
28:30 TRADIFY
29:13 EV Plans
30:09 Importance
🧰🛠️ Tool Of The Day 👇
Unilite Work Lights:
Get 25% off all Unilite Products using our code "ARTISAN25"
UK Store - bit.ly/UNILITE
Europe Store - bit.ly/UNILITE-EU
USA Store - bit.ly/UNILITE-NA
Australia Store - bit.ly/UNILITE-AUS
🏷️😱 Big Boots - get 5% off our amazing work boots when you use our discount code "ARTISAN" at checkout here bit.ly/BIGBOOTS
🎵 Use music the Artisan Way - Sign up to Epicmedic Sound here 👇🏼
www.epidemicsound.com/referra...
🔔 Become a Channel Member To Get Access To Exclusive Perks 👇
➤ / @artisanelectrics
✅ Check Out All Our Favourite Tools Here 👇
➤ www.amazon.co.uk/shop/artisan...
-----Electricians Business Course-----
📩 Sign Up To The Electricians Business Course Here And Get The First 4 Lessons Free 👇
➤ bit.ly/2Z582zI
🔔 Subscribe to TOOLS4SPARKS RU-vid Channel 👇
We Also Have A Dedicated RU-vid Channel About Tools:
➤ / tools4sparks
-----MY ENERGY PROVIDER-----
🐙 Get £50 credit when you switch to Octopus Energy 👇
➤ share.octopus.energy/zappy-sh...
🏷️ DISCOUNT BUSINESS SUPPLIES 👇
➤ www.amazon.co.uk/tryAB?tag=ar...
📈Make the most of your RU-vid analytics with TubeBuddy - Sign up here👇
➤www.tubebuddy.com/ARTISAN
-----TRADES INSURANCE DISCOUNT-----
If you need to renew your public liability insurance or need tools in van insurance, I recommend Rhino Trade Insurance, I've just renewed my insurance with them.
🏷️ Use My Discount Code “ART5” and you get a 5% Extra Discount On Their Already Excellent Prices.
➤ www.rhinotradeinsurance.com/quote
📞 or call 01162437904.
📱 Don't Forget to Follow Social Media, FOLLOW US on Your Favourite Social Networks 📱
📸 Artisan Electrics Instagram Account 👇
➤ / artisanelectrics
🐦 Artisan Electrics Twitter Account 👇
➤ / artelectrics
📓 Artisan Electrics Facebook Account 👇
➤ / artisanelectrics
⏰ Artisan Electrics TikTok Account
➤ / artisanelectrics
💼 Artisan Electrics Linkedin
➤ / artisan-electrics
🎥 Get in touch with the Media Team
➤media@artisanelectrics.co.uk
This video is for entertainment purposes only please do not attempt to copy or recreate it. Do so at your own risk.
#sparkylife #electricianlife #artisanelectrics

Наука

Опубликовано:

 

25 июн 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 384   
@artisanelectrics
@artisanelectrics 2 года назад
Thanks to TRADIFY for sponsoring this video: Get 50% Off your first 3 months using our discount code "ARTISAN" here: bit.ly/37G9BZX What the most shocking thing that you've found on an EICR...
@RWBHere
@RWBHere 2 года назад
'so that they're all at the same potential difference.' ? Surely you mean 'so that they're all at the same potential.'?
@plosscrot
@plosscrot Год назад
60A main DNO fuse blown, replaced with wire between the blades and MANY other bodges over the years!
@kieranl29
@kieranl29 Год назад
I love how i watch this but half the video i sit here thinking "what the fuck is this dude on about?"
@ironclay3939
@ironclay3939 10 месяцев назад
First question refer to public comments
@adamhardy8690
@adamhardy8690 7 месяцев назад
Can you do a video of how many electricians abuse the now regulatory 5 yearly EICR for landlords. In my experience you request an electrician does the inspection he doesn't sign off and gives a bill of thousands of pounds for minor issues. E. G. I had a hairline crack in the consumer unit and got a bill for 800 to come back and replace it.
@tombarrett1487
@tombarrett1487 2 года назад
Really like John, talks a lot of sense and knows his stuff. More John please 🙏
@artisanelectrics
@artisanelectrics 2 года назад
Lots more coming up!
@alanjrobertson
@alanjrobertson 2 года назад
Loved the tips from his DNO perspective 👍
@richardwhitwam9979
@richardwhitwam9979 2 года назад
agreed more of John please
@nusermane1076
@nusermane1076 2 года назад
Maybe he can, once and for all, provide the DNO answer to the question, whether the DNO would notice a pulled cut-out fuse, if a smart-meter is fitted 😄 (That question came up in one of the earlier videos)
@rjkelectrical6086
@rjkelectrical6086 2 года назад
@@artisanelectrics he is very knowledge and knows his stuff 👌🏻
@MatthewHawkyard
@MatthewHawkyard 2 года назад
John seems to really know his stuff, a great asset to the team and Jordan still learning is the reason I love this industry. Always be ready to learn more.
@sk0nhet
@sk0nhet 2 года назад
I'm completely new to electrics,16 and I've fallen in love with electrics! Literally changed my entire career path as I find electrics more enjoyable than any construction skill. You're a great help for me as I'm learning quite a lot. Thanks so much for your work!!!
@BlRaidX
@BlRaidX 2 года назад
The look of confusion as he heard "Is it half a day" Johns info about the MCB date, Love that kind of knowledge. !
@howarthelectricalltd.356
@howarthelectricalltd.356 Год назад
Every company needs a John, conscientious and knows his stuff. Great video from you both and looking forward to the next instalment.
@Stimps1983
@Stimps1983 2 года назад
Really good video. Getting a more in depth look at some of the more regular things you do day to day. Really good to show that regardless of how experienced or knowledgeable you may be, there's always something new new to learn.
@rexeady4325
@rexeady4325 2 года назад
Interesting video and would definitely want to see the board change, and the solar install.
@artisanelectrics
@artisanelectrics 2 года назад
👍🏻
@tommahoney7940
@tommahoney7940 2 года назад
Really enjoyed that fella’s,John looks like a great addition to the ARTISAN TEAM.
@artisanelectrics
@artisanelectrics 2 года назад
👌🏼
@anyolirons
@anyolirons 2 года назад
“The names Arthur, Arthur Day!” But seriously I love that Jordan helped John out rather than him working on his own! What a boss 🤜🏽🤛🏼
@gadgetman36
@gadgetman36 2 года назад
I really liked your explanation of C1/C2/C3 codes in this video Jordan. Those skeleton boards are also quite common in London apparently.
@chrisholt2474
@chrisholt2474 2 года назад
A great film, it answered a lot of questions for me. Jordan and John have some fantastic electrical knowledge. Well done, I would love to see the board change in part two. 👍👍👍
@michailangelopoulos5602
@michailangelopoulos5602 Год назад
You really take pride in your work. Very informative video. By the way, the PSU at 08:55 is supposed to be used within an enclosure or device chassis. It is not rated to be left exposed like that.
@rootyourmom
@rootyourmom 2 года назад
12:09 - a tricky one: not sure if it applies, but IEC 60364-4-43 433.2.2 says something like "the protective device can be along the run if there's no sockets, no branch circuits, and it's protected against fire and danger to persons"
@rootyourmom
@rootyourmom 2 года назад
Also, at 13:13 - sure 2.5mm² isn't great here, naughty at least, but if the upstream protection was like 16A, what class fault would that be? Nuisance trips if you ever actually plug something needing 32A in, sure...
@williammartinculleton5875
@williammartinculleton5875 2 года назад
Good to see Jordan on the tools again, John’s obvious experience shows. Well done
@davidjones6779
@davidjones6779 2 года назад
More please - Looking forward to seeing Part 2 - Consumer Unit install. John has taken being on camera like duck to water. You can tell he's got a vast about of knowledge. What a great asset to you business Jordan.
@artisanelectrics
@artisanelectrics 2 года назад
Couldn't agree more! John is brilliant!
@fattoamanowoodwork3638
@fattoamanowoodwork3638 8 месяцев назад
Brilliant video again, thank you. love the technical explanation yet you always bring it back to simple terms and great explanations. Love your work.
@ianchristie7153
@ianchristie7153 2 года назад
Hi, great video. Just a comment, not all DIY electrical work is dodgy! I agree that people shouldn't do any electrical work if they don't know what they are doing. I have just completed a full rewire of my 3 bed bungalow, it was extended from 2 to 3 bedrooms. I needed to get an EICR so I could apply for my completion certificate. I got a pass (satisfactory) with no faults found. I went for all radial circuits with an RCBO board. Many thanks to you guys, David Savery and John Ward for your fonts of knowledge!
@cuebj
@cuebj Год назад
Exactly. I've had to fix work by every professional I've ever used
@alanhollingsworth4405
@alanhollingsworth4405 2 года назад
Just a quick tip remove the consumer unit cabinet surround makes it so much easier to see the incoming cables and gives you a lot more room to manoeuvre.
@webzterd
@webzterd 2 года назад
10.5kw shower.... Hold on while I go back to that fuse board in the video. Doubt it's on 16mm either. Doubt it's on 10mm. 6mm? Maybe. 4mm? Possibly.... Edit; kept watching, that blackened wiring is not surprising!
@cutzwithrazzor
@cutzwithrazzor 2 года назад
Do you have a video explaining ring and radial circuits for us Americans watching? Im glad you explained all about the EICR's, sounds like the UK's regs are far more stringent that here in the US.
@tomstovell7425
@tomstovell7425 2 года назад
Scary what you can find when you scratch the surface. Definitely would like to see the board change and solar battery install. Another good vid artisan team!
@MrTendentious
@MrTendentious 2 года назад
A mate of mine was carrying out PAT tests and found an extension lead made out of coaxial aerial cable. It was coiled under a rug so that the renter could keep his feet warm.
@alsanova
@alsanova 2 года назад
😳
@wizard3z868
@wizard3z868 2 года назад
Reminds me of an old elderly cple that saved on heating by placing coins behind the old Edison fuses scary lol
@mattyb1771
@mattyb1771 Год назад
Regarding the 1mm feeding the spur, I was taught not to use different size conductors in the same terminal, if you're going to install a spur for a small load use 2.5mm then reduce on the load side of the spur.
@jeffreyconway3389
@jeffreyconway3389 2 года назад
Guys - great video. Love all the details and explanations of the terms. As an American it helped me to better understand your processes and regulations. Would love to hear more from John.
@shiamjad
@shiamjad 2 года назад
One of the best video on the channel... So much Informative and well prepared
@artisanelectrics
@artisanelectrics 2 года назад
Many thanks, glad you enjoyed!
@superhardgel
@superhardgel 2 года назад
Absolutely class act and generous with explanation, especially with the technical terms. Watching this from Singapore, and we do match British electrical standards fairly closely. Please keep up the quality content!
@TheChipmunk2008
@TheChipmunk2008 2 года назад
Really don't like those shower isolators with one screw, you can't be confident it's not gonna burn up again esp on 10+ kw
@Peter195267
@Peter195267 2 года назад
I would love too see more on this installation and upgrade. thanks Artisan Electrics.
@essexcountyelectricalltd
@essexcountyelectricalltd 2 года назад
Great video of all the defects thY wr come across on a day to day basis.
@simonparkinson1053
@simonparkinson1053 2 года назад
26:20 Standard square shower pull cord switch issue. I use the round Crabtree ones, you fix it down and then terminate the cables with nice bend radius. Neon is connected to the cover so ideal for I.R. testing, just fit it after.
@plosscrot
@plosscrot Год назад
Crabtree are far easier to terminate, especially if they are 10mm
@mohamedsiadabdille7631
@mohamedsiadabdille7631 2 года назад
Great Jordan enjoyed your videos learn a lots while at work have spare time keep watching and learn thanks and appreciate for time take care bro
@lilbuddhist
@lilbuddhist 2 года назад
What a helpful video this is, studying for my 2365 at the moment and this has so many intriguing insights, thank you
@pauliboo2
@pauliboo2 2 года назад
Please have a video with John telling us everything he knows! What a great addition to your team!
@tobysherring1369
@tobysherring1369 2 года назад
re the outdated MCB and RCD, use an old copy of the regs to check they still pass the tests. Then decide whether it's immediately dangerous, needs replacing, advisory or nothing. If they trip at the right current/fault, old or not, they aren't unsafe. That's not to comment on whether there are other reasons for an upgrade.
@henriquerabelo6339
@henriquerabelo6339 2 года назад
Well done gentlemen. I will definitely watch the board change and the battery install videos.
@baron5747
@baron5747 2 года назад
John is great, his knowledge is incredible. He brings a more informative, and educational style to the videos. Over the more humorous, and less serious vibe that Corey brings. Also, the way Jordan says "marijuana" at 15:44, just brilliant.
@artisanelectrics
@artisanelectrics 2 года назад
Glad to see everyone is enjoying the content from John!
@hks-lion
@hks-lion 2 года назад
Marry-wana 😂
@euro216
@euro216 2 года назад
John is a great addition to the team, great hire guys
@artisanelectrics
@artisanelectrics 2 года назад
Glad you think so!
@Djcraig90
@Djcraig90 Год назад
Love watching your guys videos! Really makes me realise how rubbish my electrics are in my house! 😕 plus working on building sites you guys give me that bit more Knowledge of what the electricians are doing 😀
@ItzD3fW1sH
@ItzD3fW1sH 2 года назад
I'm on a looped supply from a 1950s ex council house. The DNO put an 80amp fuse in my side, and said next door wouldn't be able to go above 60 now without unlooping the supply
@rouman7
@rouman7 2 года назад
Nice to see your keeping your quality in tradesmen , with John being a excellent addition ….
@lezlienewlands1337
@lezlienewlands1337 2 года назад
You know someone really bodged up an outlet install when an electrician just takes one look at it and re-terminates it, just to know it's safe.
@gregf9160
@gregf9160 2 года назад
Jeez -- that place is a fire hazard waiting to happen 😱 An insult to Chimpanzees ... they're highly intelligent and physically _very_ strong, and they could be trained to do far better than this. I would love to see a follow-up to this 👍
@leexgx
@leexgx Год назад
Guess he had to be really careful with the customer being around (customer has past electrical experience :)
@stuartlee8041
@stuartlee8041 2 месяца назад
I can just imagine the builders I've worked for, " how much? " " how long?" " hurry up then!"
@martinbateman2467
@martinbateman2467 Год назад
those class 2 metal light fittings with the plastic box are designed for singles peing run through conduit. Where I've fitted them, I have used a bit if PVC sleaving from the exit of the conduit to the plastic box for the line and neutral and have crimped a ring fitting to the earth wire and attached it wall/ceiling mounting
@ronanotoole1973
@ronanotoole1973 2 года назад
The face on Jordan - looks like he was caught with his pants down 😁 Another great episode guys and very informative 👍
@D4rthvaper
@D4rthvaper Год назад
19:52 what a plesent suprise i have the same technics su-v500m2 amp
@sionpritchard2060
@sionpritchard2060 2 года назад
Definitely 100% need to see the follow up!
@HelloOJ
@HelloOJ 2 года назад
Thank you for sharing. Very interesting!!!!. Could i ask about the battery storage, is the loft the best place for placing them. Just thinking of weight and temperature fluctuations. Also fire risk. Keep up the good work.
@cooliocrib4409
@cooliocrib4409 2 года назад
I was thinking the same... however its actually what is stopping me from doing my batt install in the loft.. everything is wooden so not chancing it. I'm now leaning towards doing it in the garage but it means I got to run a really long cable.. kitchen is the next best and easiest area for me
@joparish1037
@joparish1037 2 года назад
Another fascinating video! And yes, board change in that property would be an interesting video too.
@artisanelectrics
@artisanelectrics 2 года назад
Noted 📝
@drwizzle
@drwizzle Год назад
That's a sweet tomato grow setup there. Love all your videos, keep them coming!
@alunstone
@alunstone Год назад
I was told by an electrical tutor that it was OK to use 1.5mm twin and earth on a 13 amp socket ,double or single provided that it was supplied by a connection unit with a 13 amp fuse. 1mm maybe OK in some circumstances but if any correction factors had to be applied it may end up with the cable only being able to take say 11amps and the fuse rating at 13 amps so I don't think it would be a good choice of cable with that fuse ,although with the short run of cable you have there I can't see there being an issue,although strictly speaking I don't think it does comply with regulations. Interesting video,thanks for uploading .Happy new year.
@joshuavc
@joshuavc Год назад
Great save from Jordan, jumping off the gas bonding was on the tip of his tongue there 😜
@JohnCap523
@JohnCap523 2 года назад
Hey hey, it’s not “obsessive” to want to monitor your power consumption. I have the same Emporia Vue on my breaker panel (what you call a consumer unit). It works great.
@sugardaddyxxx
@sugardaddyxxx 2 года назад
The 0.05 ohms is like a max reading for 10mm earth cable as it’s it’s good for about 27-28 metres. Hence if it was not in range, you may have to up the size of cable but in domestic you wouldn’t as it’s never gonna be that more than a 28 metre run, so we would probably just replace it for another 10mm earth cable. GHS Electrical done a video a few years back on it saying something similar. Keep up the good work.
@theodorgiosan2570
@theodorgiosan2570 6 месяцев назад
Being from the US, seeing 40A and 60A services is crazy to me. The average house here has a 150 or 200A service, 120/240 split phase. 400A is common on all new construction. Some areas have residential 3 phase, usually 120/240 delta or open delta, but sometimes 120/208Y on a main road. My own house has 100A 120/240 open delta. 100A is almost never installed in new construction, and really was only common 1980s and earlier. Power company where I live is phasing out open delta services, so to upgrade to 200A, we need to wait for the power company to connect us to a 120/208Y transformer set that's on the next pole over. Waiting to hear back on what the max amps we can upgrade to is. Usually 200 but they may let us go 250-300. A 60 amp single phase service here would have been installed in the 1950s or earlier. Unfortunately most power companies in the US will not allow 3 phase for a residential customer so people are stuck with these ridiculous 400 amp single phase services. Lucky to live in one of the few places here where it is possible.
@simonmaclennan677
@simonmaclennan677 11 месяцев назад
Great informative video as always. BUT...Was John working on a live light installation at the end there?
@SKraus-pb1ii
@SKraus-pb1ii 2 года назад
Like the wander lead reel. I bought some of these myself for work which makes life so much easier.
@colinedwards1163
@colinedwards1163 10 месяцев назад
Hi Jordan great content as always. yes I would love to see a part 2
@l337pwnage
@l337pwnage 8 месяцев назад
For those who are new to modern lingo, "upgrade" means "make it worse". ;p And I can probably guess why they changed the phase colors, and it already is getting on my nerves, lol. Those burnt wires remind me of the only time I almost had a real electrical fire. I had a electric drier outlet that felt a little, I don't want to say "loose", but "not very firm" when I moved into a place. Any experienced people know right where this is going. Many years later I noticed that I could smell burning and almost see a haze, it was obviously concerning, but I just couldn't pin point it. As it got worse, I started poking around, and when I unplugged the dryer and the outlet just fell apart. O,O Both the outlet and dryer cord were melted and charred, and *that's* when I remembered years ago when I first plugged it in that the outlet felt "odd". I kicked myself in the butt because I should have seen it coming. One lucky thing is I'm one of those guys who will not leave a dryer or stove running if I'm not in the house, and I won't even leave a portable heater plugged in if I'm not home. That last habit means I've worn out many outlets over the years because outlets aren't designed to be plugged an unplugged daily. They wear out surprisingly fast. I actually got several outlets in my current place on the "needs replaced" list due to them being loose fits and I can feel heat in the vacuum cleaner cord after use. For the unfamiliar, anytime you unplug any electrical device, note the temperature of the plug and cord, even if it only feels "warm" and make sure you are expecting that. Certain high amp appliances, like vacuums, will always have some heat after use, but make sure to learn what is "normal" and what is not. When in doubt, just consult an expert. It's cheaper, and safer, than a house fire.
@JohnDunne001
@JohnDunne001 9 месяцев назад
Yes to the video of you changing the CU - great videos! Thanks
@Some1Special2you
@Some1Special2you 2 года назад
All RCD breakers are supposed to be failed if they are put in the fuse panel before 2018. This is due to the amount of DC circuits in the circuit. You need a DC rated RCD for circuit with DC circuits connected to it. (DC circuit I mean devices like LED lights, electric car chargers, washing machines and other stuff that might have DC PSU in them) The responisble thing is to change the MCB's also to the same brand as the RCD. This is how we are suppose to do it in Iceland, you guys in the UK usually have harsher rules.
@lawrencemanning
@lawrencemanning 2 года назад
Pet peeve: “Amps of power”. Great video.
@Ragnar8504
@Ragnar8504 2 года назад
The 1 mil off the socket is protected against overload by the fuse in the FCU, no matter what. The one potential issue is short-circuit protection if the cable between the socket and FCU gets damaged. If the socket is on a 20 amp or smaller radial the MCB is probably sufficient to protect the cable, if it's 30 or 32 most likely not. RIngs and 4 mm2 radials are precisely the reason why BS1363 plugs have fuses in them (and of course overload protection of power strips). 4 MΩ is theoretically a pass but anything less than high double digits would leave me a bit concerned there might be something on its way out. With plenty of loads connected it's probably just a bunch of Y capacitors affecting the numbers though.
@evanfpv
@evanfpv Год назад
Worst I’ve seen was steel conduit covered in years of paint feeding an outdoor front porch light that had been connected to line rather than cpc, tenant reported occasional ‘static shocks’ when switching the switch. EICR for landlord on domestic premises.
@tmd63
@tmd63 Год назад
Spurs off rings: 1.5mm2 for PVC insulated copper cables or 1.0mm2 for MICC copper conductor cable
@oliverjames8070
@oliverjames8070 2 года назад
Good video as always. We have just had a hypervolt fitted can’t seem to get WiFi to it where it is placed, what booster would u recommend with it being 20 metres from the house.
@radders261
@radders261 2 года назад
What a brilliant video! Would love to see a follow up.
@artisanelectrics
@artisanelectrics 2 года назад
Sure thing 👍🏻
@thegreatvincenzo8159
@thegreatvincenzo8159 11 месяцев назад
RCD's. Very important piece of safety kit. I moved into a newbuild some years ago. After a couple of weeks, an RCD would pop after switching on the kitchen light. Got a local sparky in to have a look and, after about 15-min's, he told me he had cured it. I asked him what he had done. He showed me how he had swapped the RCD for a switch. No more problems! 😱😱😱 I gave him a verbal boot up the arse and got another sparky. Turned out that when the kitchen light had been installed they had drilled through the cable and there was an intermittent short between live and earth. If it keeps popping, there's a problem!
@tmd63
@tmd63 Год назад
The water pipes in my Swindon home is a rubber reinforced pipe in a tube and are not therefore bonded to the pipes at that point. But the pipes etc are all buried into a concrete floor. The Electrics are unusual in that all the sockets are on one ring coming from the first floor.
@laidbackguyhk
@laidbackguyhk 2 года назад
John's a top man. A great addition to the Company.
@nusermane1076
@nusermane1076 2 года назад
That moment in Jordans life, when he opened a board and he and his one single ct clamp for the zappi were soo lost in that ocean of ct clamps 😂
@williamdawson6351
@williamdawson6351 2 года назад
There is a chance that a rewire is in this house future it may be easier than just a simple breaker box replacement.
@pinchermartyn3959
@pinchermartyn3959 2 года назад
Awesome. GREAT info.
@chrisgoodwin3617
@chrisgoodwin3617 2 года назад
John is a great addition to the team Jordan. Artisan obviously attracts the best. Chris.
@themagicsponge
@themagicsponge 2 года назад
Marry-juana grow 🍃😂 Excellent video guys, super informative 💡🙌🏼
@TheDaf95xf
@TheDaf95xf Год назад
I’m no electrician but enjoy watching how it’s done professionally 👍🏻 I used to watch Tom on RU-vid but he seems to have disappeared 🤔
@luce2988
@luce2988 8 месяцев назад
You always choose the fuse for the load then you have and choose the cable after that so the cable and the things attached to it is always properly connected but I don't know how you do it there(Germany)
@adambrammeld9286
@adambrammeld9286 2 года назад
I’m sure you get this a lot, but as an apprentice who would like to gain more knowledge with testing and eicrs these videos are great 👍
@jasonbrown476
@jasonbrown476 2 года назад
The MCB's would be a C3. It's just doesn't comply with the regs. It's not immediately dangerous. The kitchen extractor I would code a C2. The only reason I would is if something happens in the cable going to the spur. It would exceed its current rating before the breaker trips. Otherwise, it's not an immediate danger.
@gavowassy7655
@gavowassy7655 2 года назад
More John plz.. Seems a good likeable chap... Knows his onions too
@Evilserge
@Evilserge 2 года назад
I did a separate line for each room and category. That is overkill but it is safe. So it is like 3 lines just for a my working room - 1 for lights, 1 for outlets, 1 for a AC. My switchboard looks like a nuclear power plant control center. It is expensive.
@haydenwall3803
@haydenwall3803 Год назад
John is a standout (head and shoulders) sparky. You are building a great AE team.
@Goreuncle
@Goreuncle 9 месяцев назад
16:48 Given how concerned these guys are about safety, I find it funny that they're ok with electric showers... and this one didn't even have RCD protection 🤣
@claytonlarkin8329
@claytonlarkin8329 Год назад
Just found your channel and videos, great stuff guys
@tomlowe4156
@tomlowe4156 2 года назад
Scary.. how a company or one man band can allow anything less than a day for an EICR on a house is beyond me. Sometimes profit is more important than doing a good job, especially when it’s not your name on the test certificate!
@timw1971
@timw1971 2 года назад
Great video. I would love to see the follow-up video.
@WowwDann
@WowwDann 2 года назад
Crazy seeing how different England is from Australia in electrical wiring and installations
@SamNalty
@SamNalty 2 года назад
I am not an electrician but I definitelyt pulled a disgusted look when John spoke about the house wired with speaker wire.
@pezzermra
@pezzermra Год назад
As a former ADT Sparky Its uncommon to install a switched spur. Its usually Un Switched for a Intruder panel.
@DirkDelahaye
@DirkDelahaye 2 года назад
The quality of the painting job in that place reflects the electric work! 😆
@Dranok1
@Dranok1 2 года назад
BS 3871 was assimilated into IEC 898 because the responses were close enough to each other to make 3871 satisfy the same standard, which is why it was part of tables right up to now. BS 4293 was not assimilated into 61008 because they didn't satisfy other parts of the standard, hence why the 4293 standard is not recognized by 7671 (does not appear in the reference tables) and hasn't been since at least 16th if not before. The trouble is, 4283's respond faster than 61008 (200ms vs 300ms) and are pretty rock solid until they fail, but they are prone to failure. I haven't bought Amd 2 yet so I don't know that 3871 has been removed, but it is surprising to hear since nothing about them has changed...
@rjkelectrical6086
@rjkelectrical6086 2 года назад
The overall resistance doing the global IR, is always lowest than the lowest one. So recording that value is fine as you know all the circuits are within the required limit of 1 M ohm
@Dranok1
@Dranok1 2 года назад
1MΩ complies but only after further investigation to ensure no latent fault exists. GN3: "...where an i.r. of less than 2MΩ is recorded... each cct should be tested separately." Basically, if there's VIR or MICC (Pyro) in the house you really need to know if it is degrading by taking proper readings and comparing them with (snigger🤭) the previous test results.
@reedy8585
@reedy8585 Год назад
@ 12:05 If its a dedicated socket that has the correct fuse, its fine and within regulations
@davideyres955
@davideyres955 2 года назад
My personal opinion on the cooker hood is that if the wire is thin enough then your going to have a higher resistance and if it shorts you won’t necessarily get enough current to go through and trip the protective device in the time period you want. You could calculate that. Couple this to the lack of rcd and it’s starting to smell risky. You are not going to pull more than the in line fuse will pop at so wouldn’t be concerned about the motor failing and pulling more current as the fuse will blow. Just the possibility of a fault between the fuse and the socket which has the fuse for that supply ie 32amp or less. You could code it as a c2 but it’s unlikely to fail so c3 and let home owner know.
@ianmontgomery7534
@ianmontgomery7534 2 года назад
"Dyson Hoover" I love the way that you English can't say vacuum cleaner and have to call them Hoovers whether they are or aren't.
@silentassailant3905
@silentassailant3905 2 года назад
i once saw my boss working to fix machinery on a 3 phase supply he opened up the panel to adjust the plc he slipped with his screw driver and i went blind for a second as the rail pretty much exploded. he soon replaced the entire panel
@jarodsnyder1698
@jarodsnyder1698 2 года назад
as an American the whole concept of required inspections on electrical work is interesting. just today I pulled an 8 AWG which is a 6.0mm cable right out of its screw clamp on a brand new RV. the amount of wrong and intentionally bad wiring I found is just amazing. how a manufacturer can put a 55A output power converter on an 8 AWG (6.0mm) cable and then put an auto-resetting 40A breaker inline to "comply" with the wire current limits. but that breaker will be thermal cycling for the rest of its short life and fail prematurely.
@shaunlewis286
@shaunlewis286 2 года назад
And then the RV company will charge him over the odds to replace it for what shouldn't have been installed in the first place, because lets face it, a lot of people go back to where they get the vehicle from instead of finding someone who knows what they are doing.
@paulbradbury4612
@paulbradbury4612 2 года назад
During the IR test it appeared John tested individual circuits at 500V without worrying about any devices still connected. This is about 22 minutes in after the global tests, he states he is testing line to earth without the neutral. I can see the meter is on 500V. I'm new to this but I am always ultra careful before testing at 500V. I didn't understand his comment along the lines of the Megger will always bring the voltage down. Did I miss something or can anyone explain why he was not concerned about the risks of 500V between line and earth and his comment about Meggers?
@keithjackett9895
@keithjackett9895 Год назад
Brilliant Vid Gents, most informative. Keep up the Good work, there's a lot of people watching you who Don't Understand the work load going into a Simple situation. That's why they need Professional Help! My Local Solicitor chargers £600 PH in 10 Minute interval's.... And We're Considered to be Expensive by people whom cant Understand the Bigger Picture in Electrics... Yet they understand a Solicitor Word for Word... and freely Pay them a Fortune. Planning is Key People!
Далее
GUILTY MISTAKES! Too many electricians do this wrong!
26:17
Commercial EICR. How Do We Do Them!
22:02
Просмотров 3,5 тыс.
ANOTHER DIY BODGE! 🤯 "Why are people like this?!"
28:10
Fault Finding Electrical Circuits - Electrician Life
24:57
Consumer Unit Fire
17:31
Просмотров 177 тыс.
Will the battery emit smoke if it rotates rapidly?
0:11