Тёмный

Secret Menu inside a Notifier NFS640 fire alarm panel 

Fire Alarm Apprentice
Подписаться 514
Просмотров 3,5 тыс.
50% 1

The notifier panel is packed with features. Some are well documented, others are more secret. I have worked on these panels since 1990 and own a bunch of them in my shop, for training. Lets look at just a couple of commands that will help you service these panels.

Хобби

Опубликовано:

 

29 май 2022

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 39   
@kneesee100
@kneesee100 Год назад
RESET is not really a hidden menu. It just reboots the panel. Just like removing 24vdc and 120vac and then turning on the 120vac and 24vdc back on again. It is useful when you can't find the breaker.
@firealarmapprentice4517
@firealarmapprentice4517 Год назад
Correct. I read it in the documentation later on. Seems like it was never in previous documentation I flipped through over the years.
@blenzlens6345
@blenzlens6345 2 года назад
Cute background.
@VocalSongs175
@VocalSongs175 11 месяцев назад
any help me for i have NFS-320 Panel and all module pull station and smoke detector red lights blinking i didnt understand whats going on now i just turn off the power breaker .also how to solve Invrep in all devices
@vijeshvijay544
@vijeshvijay544 2 года назад
Brother how to disable all out put module s
@firealarmapprentice4517
@firealarmapprentice4517 2 года назад
You could pull the loop OR you could disable the CBE that follows all modules in the disable menu.
@jawad4074254
@jawad4074254 7 месяцев назад
if there is an alarm, Program corrupted..... what is the issue and what is the solution?
@firealarmapprentice4517
@firealarmapprentice4517 7 месяцев назад
Upload to the laptop with verifier tools then download it back to the panel. That will clear the program corrupt 99.9% of the time. If you don't have verifier tools or if you are in a remote area, there is a way to do it over the internet.
@mimi2
@mimi2 Год назад
When will you make a part 2?
@firealarmapprentice4517
@firealarmapprentice4517 Год назад
I got distracted with Smartwatches, then after I got the "vid" my priorities changed. You need to know more about notifier ? Contact me if you like.
@mimi2
@mimi2 Год назад
@@firealarmapprentice4517 would any of these commands work on the afp-300/400? Been trying to connect mine to older verifier tools without much luck
@firealarmapprentice4517
@firealarmapprentice4517 Год назад
@@mimi2 Oh you got me there. I barely remember the 400 because they didn't last long due to RAM /ROM issues. The the serial port rs232 or did they use a 5pin ? Make sure you have RX TX properly connected. Remember, its NULL meaning RX > TX and TX > RX.. the physical connection.
@hilo2-est3-elev
@hilo2-est3-elev Год назад
@@firealarmapprentice4517 What are all the parts needed to build a NFS2-640 system?
@firealarmapprentice4517
@firealarmapprentice4517 Год назад
@@hilo2-est3-elev Parts? You mean for text alerts? Google sheets population?
@weisler808
@weisler808 Год назад
Wait! What? You just creat a digital printer using the printer connection. You can also use teraterm app using usb to serial cable. Locate your TX, RX and Reference…
@firealarmapprentice4517
@firealarmapprentice4517 Год назад
I mostly use minicom. More than just a printer.. ru-vid.com/video/%D0%B2%D0%B8%D0%B4%D0%B5%D0%BE-kc0IfUopZmQ.html
@VocalSongs175
@VocalSongs175 11 месяцев назад
any help me for i have NFS-320 Panel and all module pull station and smoke detector red lights blinking i didnt understand whats going on now i just turn off the power breaker .also how to solve Invrep in all devices
@firealarmapprentice4517
@firealarmapprentice4517 11 месяцев назад
I can help but I need to be at the panel or minimum need much more detail. The LEDs blink, that is normal.@@VocalSongs175
@VocalSongs175
@VocalSongs175 11 месяцев назад
Invrep appear on the panel screen and all devices blicking red light smoke,pull station all devices . also we try smoke but not respoding also pull station not working , we also changed Module with new some with same address but still same @@firealarmapprentice4517
@AnyoPo
@AnyoPo 8 месяцев назад
lost password program
@firealarmapprentice4517
@firealarmapprentice4517 8 месяцев назад
?? Its really a lookup.. not decryption.
@fallbrookdave
@fallbrookdave Год назад
Seems like your really distracted making this.
@firealarmapprentice4517
@firealarmapprentice4517 Год назад
Not sure, I will re watch it. There are some menu items I wanted to publish, then I said to myself.. "maybe not"
@mattking7676
@mattking7676 2 года назад
This stuff locked away and not documented just makes repairs more difficult. To be honest it should stop as it should be illegal and all cert. technicians (cfaa) should be able to check system configurations.Also fire systems like this are getting too fragile.
@firealarmapprentice4517
@firealarmapprentice4517 2 года назад
I agree mostly to your point but I would add this.. fire alarm technicians (technologists) or a qualification exceeding that of just an inspector should be the requirement for opening the hood and looking at the code.
@mattking7676
@mattking7676 2 года назад
i believe looking like being able to pull the programed information should be available to all techs on inspection (programed information can get corrupted though it could be found by other means its still a thing the industry needs to look at) . programing changes is like changing a device location and should require a verification. so i don't see harm allowing technicians to work on them but all resources should be available from manufacturer. programming fire panels (like setting up a router) is seen to be a hard thing its not " if information is available" and is made to do so.
Далее
Auto Program NFS-320E@NFS2-640E
5:37
Просмотров 3,4 тыс.
Notifier Nfs2-640 agent release demo
5:17
Просмотров 593
Fire Panel Password  recovery
3:20
Просмотров 3,6 тыс.
HOW TO REMOVE"GROUND FAULT" IN NFS-320 PANEL?
6:05
Просмотров 9 тыс.
Descarga de programacion Notifier VeriFire Tools
4:17
Просмотров 3,5 тыс.
Anular y Habilitar equipos Notifier NFS-320 y 640
2:38
Systems In Action #11 - Notifier NFS-640 with AMG-1
5:32
Survive 100 Days In Nuclear Bunker, Win $500,000
32:21