Tech Tip #3: HVAC Systems - HOW TO Correctly Install Condensate Drains 

Standard Supply
Подписаться 2 тыс.
Просмотров 713 тыс.
50% 1

THIS VIDEO IS INTENDED FOR LICENSED HVAC PROFESSIONALS ONLY. DO NOT ATTEMPT PROCEDURES WITHOUT PROFESSIONAL HVAC TRAINING.

Опубликовано:

 

7 сен 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 129   
@Ranger11413
@Ranger11413 Год назад
Good job omitting describing the difference between negative and positive systems so that the home owner understands the difference. I figured it out on my own. Hopefully most others will also. 👍
@timmcquerry6068
@timmcquerry6068 2 месяца назад
I'm still a little confused 😕
@johnconnor7501
@johnconnor7501 Месяц назад
@@timmcquerry6068 The position of the blower motor in relation to the evaporator coil.
@ThingsIdRatherBeDoing
@ThingsIdRatherBeDoing 4 года назад
I like this guy. I'd call you. It seems whoever installed mine had no idea what they were doing. Now I'm fixing it!
@hudiburgh
@hudiburgh 4 месяца назад
Like him too,wish he could come to my place right now and fix the mess I got. Can tell he has integrity.
@dallaspilotcar9293
@dallaspilotcar9293 Год назад
The best explanation of condensate traps on all of youtube thank you
@alexpaic2984
@alexpaic2984 8 лет назад
Vent and trap primary drain always put a float switch in the secondary drain. Best way to do it. Primary clogs up secondary switch will shut down the unit. Simple as that. Never have a flood or drain pan overflowing. Always trap and vent your primary drain though. That vent will allow it to drain in any situation as long as your air handler is higher than the fall of the drain.TRAP AND VENT GUYS.
@picayunebill6614
@picayunebill6614 6 лет назад
unless of course the float switch fails like mine did TWICE. Put bleach in system in June to make sure no algae in drain line. by mid July flooding downstairs unit. 10k+ damage because no one was occupying unit below. Rectorseal ss1 said not under warranty because lack of maintenance. Guess I am supposed to check drain line twice a month every month. Don't see use in buying float switch if I have to check drain line that often.
@picayunebill6614
@picayunebill6614 6 лет назад
They usually have a set of instructions that come with float switch. But look for Red wire coming from Thermostat. trace it down to where it connects in the air handler unit itself. That thermostat wire should be wire nutted together. Disconnect that wire nut and install float switch. You should now have the red wire coming from thermostat connecting to one wire of the float switch and the other wire of the float switch will connect to where the red wire used to connect. The float now bridges that connection. Turn system on and once on flip float switch upside down and unit should turn off.
@justinrichard4190
@justinrichard4190 4 года назад
@@jeffsadowski yes break r wire from thermostat
@HausOfPain
@HausOfPain 3 года назад
How do you determine which is primary and secondary?
@PIndyJones
@PIndyJones 2 года назад
@@HausOfPain secondary will be partially blocked off on the other side of the threads on the pan.
@georgewoolinghamii488
@georgewoolinghamii488 5 месяцев назад
So how does the secondary trap get water supply for an air seal when it's not in use except during a primary blockage.
@ronaldswindell1525
@ronaldswindell1525 2 года назад
I have never in over 15 years of HVAC service seen or heard of a pee trap on a secondary drain
@billl2969
@billl2969 25 дней назад
It’s because there will not be any drain water going through the secondary pipe in normal conditions unless the primary pipe is clogged. So the P trap there wouldn’t work.
@brianhood1044
@brianhood1044 3 года назад
I’m more confused than when the video started 🤷🏻‍♂️💯‼️⁉️👌
@ssdhvac
@ssdhvac 10 лет назад
The first thing that I would consider is to trap unit #2 with a vent on the exiting side of the trap. Depending on the fall between unit #1 and #2 will determine the application. Pressure equal on both drains equals proper draining. Hope this helps.
@abtra
@abtra 6 лет назад
You touched it last, so you own it. Thank you sir
@Justin-yk1du
@Justin-yk1du 7 лет назад
The PVC lines for the drain are lower on that model pan which I'm glad they changed/updated, I've seen several where the PVC line is 1/4 inch above the pan causing standing water and mold in the large surface area pans, most of those I've seen mounted in attics that are humid anyway. This pan looks much better.
@GregoryGuay
@GregoryGuay 2 месяца назад
I have water in my pan now but not enough to drain into the secondary tube. Unfortunately, there’s no cleaning T on my primary drain.
@gregh9824
@gregh9824 2 года назад
At 4:17 you noted that in a positive pressure system, if air is coming out the secondary, it prevents water from drainingout the primary. I have experienced this (resulted in water coming out the secondary while the primary wasn't clogged, and filling the emergency pan), but can anyone explain why this is the case? Putting a vent before the trap, exactly as shown in the video, fixes it. I'd just like to understand why this happens if anyone knows.
@user-du7dw1kq5t
@user-du7dw1kq5t 5 лет назад
I dont understand how I know LESS after watching this
@ukaszlewicki3533
@ukaszlewicki3533 4 года назад
me either! this is the worse tutorial i have ever seen!
@bradl1982
@bradl1982 7 лет назад
So you're telling me the company that installed mine and used a piece of a garden hose didn't do it correctly?
@816thatguy
@816thatguy 6 лет назад
B Landel a lot of the newer units have traps built into them so it may not be wrong piping it with a garden hose
@coolezum
@coolezum 3 года назад
😂🤣😂
@paulbryant68
@paulbryant68 Месяц назад
@@816thatguywhat????? nothing built in and garden hoses…well, “garden” nothing has anything to do with hvac. guessing you are a pro diy’er. ha
@biblebloopers946
@biblebloopers946 2 года назад
This doesn't make sense with the secondary drain. There shouldn't ever be any water in the secondary drain line unless the primary is clogged. So if the primary is working properly then how would the secondary ever form an airtight seal? There won't be any water in that p-trap
@NicodemusatNite
@NicodemusatNite 9 лет назад
Thanks for this. My ac unit leaking water one drip at a time. I'll have to keep working on it.
@kirbyyasha
@kirbyyasha 10 лет назад
Now I have an older furnace. It appears to only have 1 drain, and I noticed the drain dumped into my crawl space. Well I just put a new encapsulation in, so now it's dumping into a plastic. Should I go though the hassle of putting a P trap in? It's a vertical application, I have no documentation on my system, and the condenser is under the blower. And it blows air down. I was thinking of just running a line to my sump pump.
@swiftles
@swiftles 9 лет назад
The problem I see with primary and secondary traps is that the secondary trap well not have a water seal an tell the primary plugs up if you just add water to the secondary trap it will soon evaporate out. One other big problem I see is installing Condensate lines directly to the main sewer pipe with out a bacteria air gap trap sewer gas and bacteria leaching in to the evaporator.
@hudiburgh
@hudiburgh 4 месяца назад
Good job, very clear, thank you Sir!
@816thatguy
@816thatguy 4 года назад
How do you keep water in your secondary trap if the primary is working as it should
@henrycrunyion7770
@henrycrunyion7770 3 года назад
Exactly, a trap only works when water is in the trap !!! The secondary tap should have an overflow switch to shut off unit when main drain clogs...............
@111000100101001
@111000100101001 2 года назад
Some mineral oil pour into the secondary will last 15yrs and will let water pass right though
@PIndyJones
@PIndyJones 2 года назад
I have never seen a secondary condensate line drain directly into the emergency pan. Why wouldn't you just cap it?
@Eltonmorris
@Eltonmorris 3 года назад
I just got brought into a brand new property where there’s 266 drains built wrong. I’m so furious. And of course nobody in the office(leasing) understands why there is an issue. Hopefully this video will help them understand...doubt it, but I can hope.
@tribalwind
@tribalwind 3 года назад
Our air handler sits on rubber vibration pads on the floor,it's only 2" off attic floor. Your traps extend 6+" below the pan?! How's that possible unless the unit is jacked way up on a platform or a desk like you're using here?
@wyrenutt
@wyrenutt 14 дней назад
Is a Trap and vent needed for an outdoor rooftop HVAC unit:
@condor5635
@condor5635 Год назад
The issue I see with your secondary drain P trap and negative pressure scenario is the trap will never get primed, and even if it does get primed manually it will evaporate. So essentially, you’ll just be venting through the secondary drain. What am I missing?
@mptr1783
@mptr1783 9 месяцев назад
As long as the main drain isnt working, yes, you'll be pulling air from the secondary pipe, which is fine. If the main drain clogs and water rises in the pan to where it needs to drain out of the secondary pipe, water will then fill the P-pipe.
@jasonhunter3753
@jasonhunter3753 9 лет назад
Appreciate the comments. First of all, the secondary drain trap can be taken care of by way of a simple substance called baby oil/mineral oil. When the trap is filled with oil water bypasses the oil when needed and oil remains in the trap keeping the system sealed. Trap never runs dry. Equal resistance pertaining to airflow not the flow of the water is the key. If you choose to cap secondary with an emergency switch that's fine too. However, if the switch fails then the cabinet is ruined. Hope this clears up any concerns you might have and thanks again.
@plainoldme7322
@plainoldme7322 5 лет назад
How is a trap effective on a secondary when there is not supposed to be fluid in there? Even if you intentionally put some there, it will dry out in way less than a season, especially for units in the attic.
@houstonpaul7374
@houstonpaul7374 3 года назад
You prolly dont give a damn but does anybody know of a trick to get back into an Instagram account?? I was dumb lost the account password. I would love any help you can give me.
@allantorin9307
@allantorin9307 3 года назад
@Houston Paul instablaster ;)
@houstonpaul7374
@houstonpaul7374 3 года назад
@Allan Torin Thanks so much for your reply. I found the site thru google and Im trying it out now. Takes quite some time so I will get back to you later when my account password hopefully is recovered.
@houstonpaul7374
@houstonpaul7374 3 года назад
@Allan Torin it did the trick and I finally got access to my account again. I'm so happy:D Thanks so much you saved my account!
@allantorin9307
@allantorin9307 3 года назад
@Houston Paul no problem :)
@vinodbansal9936
@vinodbansal9936 4 года назад
My installer did not add a J trap on the secondary drain and it appears my primary drain was not used at all and all the condensate was draining through secondary drain. I added J trap on the secondary drain as per your video and I can see that condensate is draining through my primary drain now but I am still getting some condensate through my secondary drain. How do you make it go away? Is it something to do with the height of shorter leg on the Strap on the primary and secondary drain. If they are kept at the same height then that can behave the same and condensate can drain through either line. Water level difference is only few mm higher on the secondary drain as compared to the primary drain. Thanks for your feedback.
@cantbefaded83
@cantbefaded83 5 лет назад
Cleanout required now at main condensate drain line
@realvanman
@realvanman 9 лет назад
The traps serve to prevent the loss of conditioned air (or the introduction of unconditioned air on a negative pressure system), but ONLY when they have water in them. The emergency drain trap would never get water in it unless the first one became sufficiently clogged.... That said, my system had the emergency drain port plugged (cute), the primary trap clogged, and my wood floor got F'd up. This is a commercial installation, and employees did not recognize the sound of falling water in the air handler every time it cycled off! I'm going to install a float switch and a manual reset circuit such that the unit will be shut down if the condensate ever backs up again.
@picayunebill6614
@picayunebill6614 6 лет назад
Be careful trusting in that float switch. I installed two. tested to make sure they work properly and then less than a year later they both failed within two months of each other. one was caught before it had any chance to do damage and both were cleaned out and sent on their merry little way. then the second one failed sometime July and 10k+ worth of damage to lower floor happened. Just be careful.
@DS-fb9te
@DS-fb9te 2 года назад
@@picayunebill6614 🥺😪that really sad
@charlotteruse158
@charlotteruse158 2 года назад
Oh ,mine doesn't drain outside it drips onto the laundry room floor where there is no floor drain. Thus the "leak" that my landlord discovered a few days before I was scheduled to move in. A neighbor said that there is a floor drain in the laundry room so I am assuming when the linoleum was replaced it was laid over the floor drain, beacause its not there. Sure would be a shame if this new carpet and floor boards and linoleum and sheet rock (assuming it was replaced from the water line) all had to be replaced again because the maintenance supervisor is lazy. I've had a cookie sheet under it since I noticed the drip. Can't use the A/C because it fills everytime It shuts off so I'm afraid it will overflow. So now I will have to notify the landlord of the leak, the disruption, walking on my carpet with dirty shoes, having to move my washer and dryer and dining room table, tearing up the linoleum. Or i'm thinking I could run some same diameter plastic tubing from the elbow to the washer hose drain thats uphill so that is no good. I Could pull out the washer find the indention from the floor drain and cut the linoleum out would still have to run something from the pipe to the drain cut a hole in the drain trap so water doesn't go under the linoleum Pour gallons of water down the drain to make sure its not clogged. Wiggle the washer back into place The pipe sticks out of a hole in the wall about 5 inches theres a elbow on the end that sits about 2 inches above the floor. There is plaster all around the pipe where it comes through the wall. There is no chance of rotating it. I don't know lol. Just venting.
@timothydougherty7855
@timothydougherty7855 2 года назад
I have pretty much this set up with my A/C. However, I need a dehumidifer and would like to have that drain into the existing piping too. Does anyone have an example of that?
@sal8575
@sal8575 6 лет назад
How do you know if you have a positive or negative pressure system?
@darrenallen1387
@darrenallen1387 5 лет назад
This!
@moisesbonilla9362
@moisesbonilla9362 5 лет назад
Sal positive air blows out on negative air is sucking
@ChiRickyboy
@ChiRickyboy 4 года назад
Last owners put a toilet roll as an adapter lol. I only realized after It was dripping. I pulled it out and it was drenched. Don’t know why they came up with an idea like this. Also they had stripped threads.
@henribenavidez6898
@henribenavidez6898 11 месяцев назад
Can you run the drain line into the washing machine drain pipe
@dustyflair
@dustyflair 3 года назад
in our city the second opening has a SHUT OFF to the unit and it wont run it water backs up...
@laserman132
@laserman132 3 месяца назад
How do you know if you have a negative or positive system
@joleaiperlis5347
@joleaiperlis5347 Год назад
I'm guessing the p trap on secondary drain pipe has to be primed with water?? Can anyone answer this question please. 🙏
@normanziegelmeyer7693
@normanziegelmeyer7693 3 года назад
I have a carrier 58mca 060 with a pump on the outside to pump the condensation water outside the house(built on a slab). There is a pvc pipe from the trap to the pump, sticking down through a hole into the bottom of the pump. If the tube is under the surface of the water in the pump before it empties, is that considered another trap and should I shorten it to keep it above the water? It has been installed and operating that way for about 20 yrs but I don't know if it should be. Thanks
@richardplatt2020
@richardplatt2020 7 месяцев назад
Can I drain my dehumidifier drain line into my gravity fed hvac line
@UltraHydrophobiccoat
@UltraHydrophobiccoat 4 года назад
Some commercial AC normally at high speed and the trap wouldn’t work since the negative pressure is so strong that all the water in the trap will be sucked out
@rkgsd
@rkgsd 7 лет назад
On rooftop units, is that where the rainwater that gets in from the top fan opening goes?
@alexpaic2984
@alexpaic2984 3 года назад
Lol.
@deanmurray4953
@deanmurray4953 6 лет назад
Run lines 1 inch ,saves lots of problems on condensate line ,blow out or vacuum every 5 years
@jking3892
@jking3892 7 лет назад
Good video , very good
@Tableaux15
@Tableaux15 8 лет назад
You show the primary is vented into (say an attic). Since many systems drain into house sewer system do you want these sewer gases in the attic even it is through a 3/4" opening.
@brianellsworth4767
@brianellsworth4767 7 лет назад
Never drain them into a stink pipe. Some will go into a laundry drain that should be trapped . Most attic installs drain out with the line set or close by.
@thehvachacker
@thehvachacker 3 года назад
Here is a video on a good way to install a condensate drain with clean out. ru-vid.com/video/%D0%B2%D0%B8%D0%B4%D0%B5%D0%BE-6CSQbsijZM8.html
@calvinmitchell6381
@calvinmitchell6381 3 года назад
I don't have a trap on my 12 foot drain line. It's a rooftop combo furnace/AC unit with a slight drop of maybe 2 inches on the 12 feet of drain. I am in Southern Arizona with very little humidity. It drains just fine. Is it working because the unit doesn't have to remove humidity?
@PIndyJones
@PIndyJones 2 года назад
That's exactly right. I'm in Georgia. Our ac units produce about 8 to 10 gallons a day. In peak times.
@stevejill91
@stevejill91 10 лет назад
I have a question about drains. I have two units upstairs and one #1 has a drain with a stack and a trap, no issues. The other unit #2 has just a straight drain with no stack) they both murge into the same pipe 3/4 pipe to the sink drain. drain #1 is higher than #2 were it ties in to the 3/4 pipe. The issue is that it seems that drain #1 puts pressure in the pipe pushing water back up pipe #2 .all the back to the unit. How can I correct this cause its ruined my cielings a couple times and every a/c tech say nothing wrong and that the pipes are cloggeg. They are not clogges just fighting each other. Hope you have some ideas. I wish I could draw you a picture!
@moisesbonilla9362
@moisesbonilla9362 5 лет назад
Thank you sir!
@marylamb6063
@marylamb6063 5 лет назад
is the lower drain the main drain? You didn't explain.
@coolezum
@coolezum 5 лет назад
Mary Lamb yes, the lower is the primary drain and higher is secondary. I prefer a float safety switch in the secondary outlet, peace.
@ShakeelAhmad-gf1bo
@ShakeelAhmad-gf1bo 2 года назад
From where we can absolute pressure value for trap
@samsagullo5577
@samsagullo5577 5 лет назад
Does the access hole in the drain line have to be plugged it t left open
@Justin-yk1du
@Justin-yk1du 7 лет назад
Why would someone combine the primary and secondary drain? they did this on my current unit. it has both lines going in the wall but they just connected them, only one trap.
@kooq544
@kooq544 3 года назад
Thank you for your information. What is the difference between positive and negative pressure? Do we need a p trap if it’s vertical? Where can we find one for a furnace?
@garcoheatingandair9493
@garcoheatingandair9493 6 лет назад
Why does my unit need a vent before the trap in the main drain? The secondary line is teed off to the emergency drain pan and then it goes out to the backyard by my window
@troymason4799
@troymason4799 4 года назад
Vent tube is not before the trap.
@awomanwonderful
@awomanwonderful 9 лет назад
Help! What's the noise coming from my condensation pipe! Its an electric furnace!
@bmorris8276
@bmorris8276 Год назад
All the mention of code is irrelevant code is the bare minimum. We float protect the main pan via the secondary hole AND still float protect the safety pan via a pan mounted float. We have NEVER p trapped a secondary and never would.
@truthfiend6909
@truthfiend6909 5 лет назад
i always put EZ trap on my installs along with a float switch in the emergency pan and i just plug the secondary drain ...is this wrong?.. if it is , why?....just curious, thanks in advance!
@moisesbonilla9362
@moisesbonilla9362 5 лет назад
ILL LOKANO put a safety switch on the secondary drain
@truthfiend6909
@truthfiend6909 5 лет назад
@@moisesbonilla9362 isn't that overdoing it tho...already have safety switches on the primary and emergency pan, adding another safety on the secondary would make it 3 ..i mean is it really practical?
@troymason4799
@troymason4799 4 года назад
ILL LOKANO thats not a bad idea because if theres water in the secondary pan it wont be alot. As long as you have a safeT switch in the secondary you’ll be fine. But i know its not recommended to merge drains but it works
@johntempest267
@johntempest267 4 года назад
What make the secondary drain secondary? They are both at the same level. It's not a primary/secondary it's a duel drain......and I don't see the point. Obviously I am missing something.
@WOODYSOOPY
@WOODYSOOPY 4 года назад
The secondary drain is a little bit above the primary that's what it make the secondary "secondary " probability you can tell in the video but that's how it is 👌
@mptr1783
@mptr1783 9 месяцев назад
@@WOODYSOOPY On my Carrier, both vents are the same height. The difference is(and I only found out after taking out the connections) is the secondary has a dam that restricts the water from coming out and the main has no restriction
@jeremylittle9023
@jeremylittle9023 Месяц назад
I enjoy the tips but when your snaking gum loud enough to come through the video I had turn to another, please remedy this for until then I will not share your video
@stevejill91
@stevejill91 10 лет назад
Sorry, I dont think tthe drain is restricted, I have replace the trap for the sink drain.
@Brekstahkid
@Brekstahkid 5 лет назад
Great tips 👌🏼
@asmith8623
@asmith8623 Год назад
2023 thanks
@crujones4046
@crujones4046 5 лет назад
Mine was wrong. thank you sir
@ogweasel4273
@ogweasel4273 4 года назад
My drain is cold and has condensation dripping off it!! How do I stop it?
@creaperkiller16
@creaperkiller16 4 года назад
OG WEASEL put insulation around it
@ogweasel4273
@ogweasel4273 4 года назад
That’s what I did. Thanks for the help
@smokeydoke100
@smokeydoke100 10 лет назад
I never did understand the reasoning behind putting traps on a condensate drain. Considering that they are usually run to openly dump into a floor drain or basement sink, it's not like you need to block sewer gas from coming back up. So what's the point?
@stephenshaw67
@stephenshaw67 9 лет назад
Preventing vacuum loss in a negative pressure system. Furnace pressure switch won't allow start if condensate drain has no trap... No trap, no vacuum, no start...
@rollo-koster5338
@rollo-koster5338 8 лет назад
+Maxwell Edison there is this thing called VACUUM. Certain system require it. Some don't.
@MrMunchiemo
@MrMunchiemo 7 лет назад
Does the second drain sit higher than the first drain?
@OlGoodJoe
@OlGoodJoe 3 года назад
I don't see the purpose of adding the extra primary T and cap - that is silly and redundant.
@dan827
@dan827 2 года назад
It's a clean out. Bc if you do the rest correct, it'll all be glued except that cap. Then when you call for maintenance they pop the cap off and clean out the drain line. Not code everywhere. But not a bad idea. Future visits will thank you
@MP_Soundbox
@MP_Soundbox 7 лет назад
Licensed professionals only!
@hg2.
@hg2. 6 лет назад
Confusing for students hearing this the first time.
@pondboggen
@pondboggen 7 лет назад
primary drain line. ok. it connects "lower" on the drain pain. and will see water. secondary / aux / emergency drain line, it connects higher. and will only see water if primary drain line gets clogged. ISSUE #1, secondary drain line, will never see water, on normal usage, as a result P trap will be dry and/or simply run dry completely. and in that, no Air seal. air will simply be pushed out the emergency drain all the time. ISSUE #2, installing a P trap on the secondary / aux / emergency drain line = a CLOG. it will take more pressure for water to get through the P trap. this is an emergency / aux / secondary drain line. it should have direct flow of water with no traps. if i installed a TRAP on pressure/temperature relief valve piping on a gas hot water heater. i would be RED FLAGGED. ISSUE #3 your drain pain stinks. both primary and secondary connections in video look exactly the same height going into the pan itself. NOW if the drain pan itself was tilted. so the emergency / aux / secondary connection was physically higher than the primary drain line. ok, but no mention of that in video. and the pan is laying perfectly flat in video. ================= ISSUE #4a P trap on primary drain line. = required, it does a couple things 1st. water will be in this line in normal usage, if air was also being pushed through, it would be like someone talking and spit flying ever were as they talked. a P trap creates enough pressure difference to block air from going through the Primary drain line. ISSUE #4b EXAMPLE: in old furnace and a/c coil on top of it. if primary drain line of A/c coil did not have a large enough P trap (using hose) on it. water would "SURGE" back and forth like a wave going up and down inside the P trap. and would create like a hammering effect or piston effect or water hammering effect. that would change air pressure inside the system causing issues with sensors and noise. having a trap that is to small in height difference from inlet to outlet side of P trap. ISSUE #5 there is always statements about PULLING AIR FROM A UTILITY ROOM were a furnace and/or A/C Coil is located. primarily due to dryers, other gas appliances, chemicals, etc... within the room. but it does not say much about putting air into the utility room. there should be no issue for a little 3/4" to 1" inch pipe. putting air into the same room as the furnace and/or a/c coil. that 3/4" to 1" pipe would be the emergency / aux / secondary drain line.
@UshouldTryReality
@UshouldTryReality 6 лет назад
Ryan Sanders very good points, so much science in a simple drain!
@acoustic4037
@acoustic4037 6 лет назад
Issue 2 contradicts the correct issue 1. Issue 3 is a mistake as its an illusion the holes are not same height.
@deltat5775
@deltat5775 6 лет назад
Dude ......loose the gum......good vid otherwise
@george5120
@george5120 4 года назад
This guy cannot teach, worth a damn. The only viewer who would understand what he is talking about is somebody who already knows this stuff. What I get from the video is a lot of hand movement and pipe shuffling and talk about negative and positive air pressure, without defining what any of that terminology means.
@ravynx
@ravynx 6 лет назад
Also another thing not to do is chew gum while speaking for a video.
@deltat5775
@deltat5775 6 лет назад
Dude, loose the gum, otherwise good video
@butchtheiw
@butchtheiw 7 лет назад
uhhm. uhhm.....uh.
@FatPotatoe
@FatPotatoe 3 года назад
What pressures is the PVC experiencing? You think the pvc will blow apart with the trickle of water going down? What's the point of the J trap even? Told hold back odors, meanwhile you have open PVC connected out to the sewage. If there is a clog, then what? You insert a tool and it pops out the other end, as opposed to going down towards the sewer, towards the clog. Just ass-backwards. And I've only done this for two months. You need to set the T out of your air handler with the middle port connected. The top of the T is then capped. You run a P-trap, J-trap, whatever, down the T. So now the "Vent" can be used properly. AS A CLEANOUT. WTF this guy's theory of pressures in the PVC is so dumb.
@notgiven9166
@notgiven9166 7 лет назад
Do you do sheetrock work also? Tell me what happens over the winter when the water trapped in p-trap freezes because you didn't bother to provide a drain or easy means to disassemble the pipes to remove the water. I'll tell you. THE TRAP BURSTS. Then in the spring when you turn it on again for the first time it DUMPS ONTO YOUR CEILING CAUSING IT TO COLLAPSE. New house, first with central air. Had no idea how the AC drained. Now I know!. Ripped the builder a new one that following spring. His answer was " Duhhh, code doesn't call for a drain", so water is supposed to come out by MAGIC over the winter.WARNING TO EVERYONE WITH HOUSEHOLD CENTRAL AIR IN A ZONE WHERE TEMPERATURES GO WELL BELOW FREEZING IN THE WINTER. DON'T DO WHAT IS SHOWN IN THIS VIDEO, Either build your own home grown trap with a drain or do as I did and re-plumb with a pair of unions so the trap can be easily removed and drained before winter. No, you will not find a 3/4 pvc p-trap with a cleanout plug in any plumbing supply store, they don't exist.I've asked several HVAC people I've stumbled across what they do to prevent pipe burst over the winter. The answer NOTHING!!!!! They just assume your attic has crappy insulation and the pipes won't freeze. Commercial AC? The air hander unit is generally in a heated space so its not an issue.
@MP_Soundbox
@MP_Soundbox 7 лет назад
If your attic is freezing, your home comfort priorities are better focused on insulation. Address the dwelling's insulation issues. If you have any sort of AC unit, you must reside in a warm region, hence the cooling requirement. How can a condensate trap still have water in it, in freezing temperatures? Condensate drains do not burst unless Summer turns to Winter, overnight. Commercial rooftop units crank out AC for office buildings, with exposed PVC external traps all over the globe, in the dead of winter, to suck the heat away from mall zombie shoppers, server rooms, gyms, rec centers. They don't split from freezing dude. If you have water in a drain line, freezing well after the warm season, it must be a tub sized vessel, riddled with moldy, yucky, soon to be yuckysicle attic pops. Something else is happening at your place dude. Basic ratios apply to draining water. If your drain worked in warm weather, then the drain works. If your house is freezing, on the INSIDE and you magically have preserved condensate from warm weather, well, you've got something really special, my friend.
@FatPotatoe
@FatPotatoe 3 года назад
Learn to wire a safety switch
@TananBaboo
@TananBaboo 6 лет назад
How do you tell if you have a negative pressure system?
@caseycoffman4405
@caseycoffman4405 5 лет назад
If the condensate is on the suction side of the fan, its negative.
Далее
How to Properly Pipe a Drain on a Fan Coil
6:50
Просмотров 259 тыс.
Installing AC Condensate Drain With Clean Out Port
20:06
Новый хит Люси Чеботиной 😍
00:33
Modus males sekolah
00:14
Просмотров 11 млн
Condensate Line Installation - Alexander Services
10:11
How To Unclog Condensate Drain Line
5:53
Просмотров 621
HVAC Contractors Hate Me For Sharing This Secret
10:21
Просмотров 923 тыс.
03/22/2022 Condensate Drain Installation
4:30
Просмотров 14 тыс.
Why you need a P trap
2:41
Просмотров 41 тыс.
I Made My AC Condensate Drain Much More Functional
14:35
Новый хит Люси Чеботиной 😍
00:33