Тёмный

The Best RSlinx Classic Driver for Auto Detecting Ethernet IP Device Any Version 

Shane Welcher
Подписаться 28 тыс.
Просмотров 16 тыс.
50% 1

Опубликовано:

 

29 окт 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 16   
@jeremycayer204
@jeremycayer204 4 года назад
Best explanation i have seen on this yet. Good work.
@ShaneWelcher
@ShaneWelcher 4 года назад
Thank you
@JayKrueger
@JayKrueger 3 года назад
Solid Video, Solid explanation. Thumbs Up!
@ShaneWelcher
@ShaneWelcher 3 года назад
Thank you for the kind words
@shahriarshajib541
@shahriarshajib541 3 года назад
How will I create communicate between my laptop & my SLC 5/05? Here is the scenario in my case: 1. When I connected ethernet with the SLC, signal LED of the module turned ON, but no device found in latest version of RSlinx. 2. IP address of the module is unknown. 3. I have used BOOT DHCP tool ( Version 3.05 )of rockwell using different subnet mask, while there was no any sign of Mac address of my SLC. However it showed only Mac address of my ethernet adapter whenever I connected ethernet cable to my module. 4. I have tried using both automatic & manual IP address from IP4 configuration of my ethernet adapter properties. 5. I have used one crossover cable between my laptop & module. No switch or router in between.
@ShaneWelcher
@ShaneWelcher 3 года назад
1. this depends on the RSLinx driver used. Use the Ethernet Devices driver then manually enter in the IP address of the SLC 5/05. 2. Get the MAC address of the processor from the side to it then use BootP server then connect to the processor when turned on & enter in the MAC address to find to IP address. No need for cross-over cable, laptop nic cards are smarter these days.
@adalmadera25
@adalmadera25 4 года назад
What if the devices have a yellow question mark with a red X over them? Would there be any way that I could changed the ip addresses on the ethernet ip modules so that I can auto detect them using this function of rslinx? Thank you.
@ShaneWelcher
@ShaneWelcher 4 года назад
Make sure you can ping the device. CMD ping
@adalmadera25
@adalmadera25 4 года назад
@@ShaneWelcher it wont ping, even though the ethernet ip card shows the correct ip address.
@adalmadera25
@adalmadera25 4 года назад
@@ShaneWelcher it seems like the modules lost their assigned ip address but they still show the IP adress. The adress still appears in rslinx but it won't connect. I have pinged both addresses and no response from neither. By the thank you for sharing and replying.
@ShaneWelcher
@ShaneWelcher 4 года назад
@@adalmadera25 use Bootp to put it back in then turn off Bootp & DHCP
@adalmadera25
@adalmadera25 4 года назад
@@ShaneWelcher I am able to connect to the factory adress on the module thru boot p. I have typed the ip adress that is supposed to be for one of the ethernet modules. Then I hit disable bootp... which is done if power is lost or plc is turned off it does not loose its IP adress, is that correct? Do I have to do anything else, because I ping the ip adress and I get no connection.
@iouseff3707
@iouseff3707 7 месяцев назад
I can ping in the cmd the ip adress of my PLC, but in the Rslinx do not appear my PLC using Ethener-IP, and by using Ethernet devices appear a yellow question mark? what can I do?
@ShaneWelcher
@ShaneWelcher 7 месяцев назад
Try a different Ethernet driver
Далее
Adding I/O in Studio 5000 program
25:30
Просмотров 35 тыс.
Ледник 1:0 Мужик
00:53
Просмотров 1,3 млн
Why Can't I Connect to my PLC over Ethernet?
10:37
Просмотров 45 тыс.
Adding a Powerflex 525 to RSlogix 5000 over ethernet
16:56
WHAT IS RSLINX?
15:17
Просмотров 6 тыс.
RSLinx Setup - PLC Tutorial 1
9:14
Просмотров 50 тыс.
RSLogix 5000 Making An Add On Instruction Or AOI
16:53