Trane reversing Valve won't cool but heats ok. 

Rick Pazmino
Подписаться 974
Просмотров 93 тыс.
50% 1

Video of a confirmed diagnosis of a 3-way reversing valve not cooling but heating ok.

Опубликовано:

 

9 май 2017

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 42   
@mariobryant8803
@mariobryant8803 4 года назад
The inside of those three ways can affect the system depending on the mode - gotta check everything that can affect the three way reversing valve. They can be tough to figure out, those seals can affect the system bigtime. Great video in general.
@adamspears3819
@adamspears3819 4 года назад
Great find! I think someone should really tell an engineer to angle the 2 outer pipes away from the center pipe, so that we can get better access to braising those fittings during installation of the new one! Thanks for this one. I'll look out for this. Especially since we primarily install Lennox & Trane.
@loganc339
@loganc339 3 года назад
Encase you haven't figured it out yet, engineers couldn't give two shits about u lol
@adamspears3819
@adamspears3819 3 года назад
@@loganc339 You are wrong about that. There are reversing valves designed this way. Nice try though!
@loganc339
@loganc339 3 года назад
@@adamspears3819 it seems like engineers build units purely to screw with the techs that work on them. They dont give a damn lol. If anything they think it's funny to do stuff like put screws in places you can't reach
@DJV94022
@DJV94022 5 месяцев назад
Heres a tip: tap the reversing valve lightly with a hammer til it gets to what you want. Just like your old starter on your cars or work vans when you tap it and it works there goes to your indication. You could also fix it by tapping it on a new one.. sometimes you gotta have faith .cause in the automotive world mechanics say this and that could not work then you do it and it works!
@brunoshvac2578
@brunoshvac2578 3 года назад
I have heard about this, however never seen it. Great video.
@vernroach3413
@vernroach3413 5 лет назад
Damn good video....Excellent camera work...Thank you for making this.
@terrancethomassr8947
@terrancethomassr8947 3 года назад
I am happy I found this video I am going through the same thing right now with the same type of brand AC outside unit I’m going to show this to the AC Man
@DJV94022
@DJV94022 5 месяцев назад
You mean Goodman service rep
@benjaminreynolds3866
@benjaminreynolds3866 6 лет назад
Holy crap I think I've got the exact same issue going on at one of my customers house. Found bad compressor, changed it. The way it acted seemed very odd. I've been leaning towards the reversing valve but it also seemed as it the compressor wasn't pumping right so I ordered a new compressor under warranty and new reversing valve just to get it all done at one time. My company does a lot of home warranty, it sucks but man our company have really thrived over the years because of it.
@joepalooka4720
@joepalooka4720 3 года назад
Doing this at work tomorrow, I was trying everything in mind to not lead me here but symptoms are hard to ignore , that hot gas bleeding into my suction side giving me a 2 to 1 compression ratio on a scroll , doesn’t help it’s 2000 degrees in Southern AZ
@THEMOWERMEDIC1
@THEMOWERMEDIC1 3 года назад
Will one hang up a little? Noticed mine not cooling as good as good as it was yesterday. Cycled my system back and forth Now it’s cooling fine. What gives?
@gotchaplumber
@gotchaplumber 4 месяца назад
Good diagnosis.
@vernroach3413
@vernroach3413 5 лет назад
Good video, good catch for the newer guy...I'm betting he felt good and this must have built his confidence up....One of the most important things that comes with experience only...Thanks for the video.
@JisINSANE3
@JisINSANE3 5 лет назад
At my job we had high head pressure and low low side pressure. Had a horrible ac company come out and claimed the liquid line dryer was clogged replaced it. $1200 charge. Well the same shit started happening within a week and the evaporator was hissing except this time instead of freezeing at the lower portion of the evap it was heating on the lower end with the same head pressures. After seeing the repairs these idiots did on other ac systems, Like electrical taping caps hanging under the condensor fans exposed to the elements I said the hell with that. So I smacked the reversing valve with a rubber mallet and WOW the damn thing started working. I learned that cause about 25% of our amana PTACS do the same damn thing. Heat when they are supposed to cool. Just smack the damn valve once.
@eddiekilby
@eddiekilby 6 лет назад
Just work on one for a friend his is doing the same thing bypassing in cooling but works in heating.
@love2hvac
@love2hvac Год назад
Great video, I have not seen one like that.
@jimeburg4828
@jimeburg4828 2 года назад
Have you heard of the Carrier Heat Pump doing the same thing being stuck on the Defrost cycle/
@RobertTuck-vo8cw
@RobertTuck-vo8cw 3 месяца назад
A reversing valve is a 4-way valve, Notice the 4 ports?
@paulbailey5742
@paulbailey5742 6 лет назад
Have you had one build up pressure on the high and low side then make a hissing sound but not shut off the compressor? Head pressure will get up to 450 suction gets to 275-280 the it "pops" off and the pressure goes back to normal.
@rickpazmino5820
@rickpazmino5820 6 лет назад
Yes. Not necessarily due to a reversing valve issue exclusively, but any kind of head pressure problem. Some compressors have internal high pressure reliefs that cause head pressure to bypass internally (possibly causing the housing noise) to the compressor if there is a high pressure condition. A hot system, compressor, low capacity operation, and your previously mentioned pressures, may be signs of this. Just a guess, but a blocked reversing valve could indeed cause this.
@726scooty
@726scooty 5 лет назад
Thank you guys I’m having this problem on a brand new Lennox heat pump I installed. I ran the unit added a pound for line set length unit ran for thirty minutes perfectly. Customer says she cut it off it would cut off I was thinking reversing valve cause I kept hearing it move or attempt to move but I’m my pressures would go to almost 600 and cut off on high head pressure can’t be a bad compressor right has to be the reversing valve? Help me please? I didn’t not amp out the compressor it only runs for a short period and I don’t want damage anything at 600 psi. I was going evacuate and weigh charge back in. Any other suggestion
@hillside7077
@hillside7077 4 года назад
@@726scooty could be bad txv in condenser
@ChrisVanSlykeCVS
@ChrisVanSlykeCVS 5 лет назад
This might be my problem....I have a 15 year old york R-22 outside unit which heats but will not cool. When I program in cooling mode everything appears to be working ie. outside fan works, I hear the condenser, inside fan is blowing air, air filter and coil are clean but it does not cool and I don't see and water condensing on the inside drain. Earlier this year I had the refrigerant checked and it was low. We pressurized the system looking for leaks but there was none found it held 350 PSI for 30 mins. The tech though it might have been the gauge valve since when he opened the cap he heard a it of gas escape. So we added refrigerant to the level required 5 lb 11 ozs. After this the heating worked fine compared to before when it was going constantly with little heat. Fast forward a few months now I want to cool and it does not work but heating does. Cooling didn't work last summer either but I figured adding refrigerant would fix the no cooling problem this year which turned out to be wrong. In cooling none of the lines feel cool but in heating the large line gets very hot to the touch. What would you suggest to check now or is it most likely the reversing valve? Great video thanks!
@jesusbautista7962
@jesusbautista7962 2 года назад
DID YOU GET THIS FIXED, CAUSE MINE IS DOING THIS RIGHT NOW. AND HOW?
@ChrisVanSlykeCVS
@ChrisVanSlykeCVS 2 года назад
@@jesusbautista7962 Mine was leaking refrigerant slowly from somewhere but we could not find where. I fixed it by replacing the outside and indoor units since the air handler had to match the new refrigerant.
@bobboscarato1313
@bobboscarato1313 2 года назад
@@ChrisVanSlykeCVS Hey that's not fixing it; you replaced the entire system!
@Hvacmania
@Hvacmania 4 года назад
If the indoor unit is second stage does the outdoor unit have to be second stage also?
@HarryHafsak
@HarryHafsak 11 месяцев назад
Hopefully the new one never got hung up on copper shavings lol
@ravisingh1285
@ravisingh1285 4 года назад
these valve technology is bad?
@shuaib8908
@shuaib8908 4 года назад
Did you cut those pipes with an angle grinder?
@samuelzendejas5651
@samuelzendejas5651 Год назад
Where did you purchase this valve from and what brand is it ?
@alexv3866
@alexv3866 5 лет назад
Great video, thanks!
@AAsoberlife
@AAsoberlife 3 года назад
Good video
@arthurmitch
@arthurmitch Год назад
Well i have got one.... restriction that blows the compressor caused by 3 way valve
@OcRefrig
@OcRefrig 6 лет назад
Good show.
@patstansberry8189
@patstansberry8189 6 лет назад
Good job
@jollyscaria1922
@jollyscaria1922 9 месяцев назад
Systom working revsl conrolld gastopinv sy oen gax pas sys stop het systom fee0o
Далее
Heat Pump 03 Reversing valve
21:04
Просмотров 31 тыс.
Insane Coffee trick EXPOSED 😱☕️ #shorts
00:20
4 WAY VALVE | REVERSING VALVE | HEAT PUMPS
8:03
Просмотров 2,8 тыс.
Trane XE1000 Down. No Cooling
27:51
Просмотров 9 тыс.
Crucial Knowledge To Heat Pump Troubleshooting
14:15
Просмотров 25 тыс.
Diagnosing the stuck HVAC reversing valve
8:43
Просмотров 507 тыс.
Troubleshooting Heat Pump Reversing Valves
6:22
Просмотров 49 тыс.