Walk in cooler iced up now it works ok. This is one of those calls where you have to look at all the clues, ask the right questions, and make a educated assumption of what happened and how to prevent it from happening again.
💥 Facebook - / hvacrsurvival
💥 Email- hvacrsurvival@gmail.com
💥 Want to help support the channel? paypal.me/RickDirmeyer
💥 WANT TO SUPPORT THE CHANNEL BY PURCHASING THE TOOLS I USE? kit.co/hvacrsu...
💥 Amazon Store: www.amazon.com...
💥 Anything not listed in my kits can be purchased through my amazon store using the link above if you would like to support my channel without costing you a penny more.
💥 My crimper www.cleavelandt...
Warning Notice Disclaimer - Video content listed on the channel HVAC*R Survival is for entertainment purposes only and not meant to be a substitute for not contacting a competent HVAC/R PROFESSIONAL. Do not attempt anything said or seen on my videos, The tasks that are shown are dangerous and deadly without proper training.
This page contains affiliate links, which means that if you click on the link and make a purchase, I’ll receive a small commission. HVAC/R Survival is a participant in the Amazon Services LLC Associates Program.
#CoolerIcedUp,#BadDefrostClock,#hvacrDiagnostics

Опубликовано:

 

10 сен 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 92   
@HVACRSurvival
@HVACRSurvival 3 года назад
10,000+ Subscribers! A BIG THANK YOU TO ALL OF YOU THAT HAVE SUBSCRIBED!!!! Thanks for ridding along and CLICKING THE SUB. BUTTON w/Notifications!!!!
@Ted_E_Bear
@Ted_E_Bear 3 года назад
You are so smart ! Great work !!
@HVACRSurvival
@HVACRSurvival 3 года назад
I don't sound like it when I'm working it out on the video LOL. But thank you for the compliment, I appreciate you watching it and giving me feedback 👍👍
@Alco16-251F
@Alco16-251F 3 года назад
Love the Copeland CR18 recip!
@HVACRSurvival
@HVACRSurvival 3 года назад
Copeland make some top end stuff. Just so happens to be built right here in Ohio or at least some of it 🤭.
@crforfreedom7407
@crforfreedom7407 3 года назад
Great video as ALWAYS Rick! Love your content brother, keep it coming! FEED ME!!!!!!!!!!!!!!!😉🤣😂🤣
@HVACRSurvival
@HVACRSurvival 3 года назад
🍔🍟🍦🤭🤣
@garypoplin4599
@garypoplin4599 3 месяца назад
1:47 - I’m new to refrigeration so I’ve not seen the water-down-the-condenser-coil-trick. Can you explain how that works? I would have expected the sight glass would stay clear since the saturation temperature is now lower and there’s _more_ room in the coil for condensing to take place. Guess I’m not thinking about this correctly. How is this different than a hot gas bypass defrost, where the sight glass flashes each time the valve opens to the evaporator coil (bypassing the TEV)?
@HVACRSurvival
@HVACRSurvival 3 месяца назад
Basically, I’m imitating a colder day. The pressure drops so the saturation temperature depending on whether it has a headmaster control or a fan cycle control it’s still going to flash for a while if it’s not at full receiver capacity.
@neilvestervictor180
@neilvestervictor180 3 года назад
the condenser fan blade rotates funny in the video
@HVACRSurvival
@HVACRSurvival 3 года назад
I record at 60 frames per second that changes the way things look in the video. Higher the frame rate the more it slows down motion.
@Tjita1
@Tjita1 3 года назад
@@HVACRSurvival That's not an entirely correct explanation, but for all intents and purposes I guess it works. If you're curious there are two effects at play, called the stroboscopic effect and the rolling shutter effect.
@HVACRSurvival
@HVACRSurvival 3 года назад
You must be into photography so you know that anything above a 500 shutter speed you can stop motion. At least at most points. Since it's not a photography site I didn't go into great detail but I do know that shutter speed affects the way it looks in the video.
@neilvestervictor180
@neilvestervictor180 3 года назад
I am a chill water technician
@HVACRSurvival
@HVACRSurvival 3 года назад
@@neilvestervictor180 I'm still working my way into the chillers, mainly done a lot of Geo thermals plus the things you have seen on the videos.
@airconditioningrefrigerati5837
@airconditioningrefrigerati5837 3 года назад
Great job 👍🏻
@HVACRSurvival
@HVACRSurvival 3 года назад
Thanks for the feedback 👍👍
@gregbowman3598
@gregbowman3598 3 года назад
Good one Rick 👍
@HVACRSurvival
@HVACRSurvival 3 года назад
Thanks man 👍👍
@Sctronic209
@Sctronic209 3 года назад
Those calls can be tough to pin down need to Scrutinize everything.
@HVACRSurvival
@HVACRSurvival 3 года назад
Yes sir.
@davidhodgin3792
@davidhodgin3792 Год назад
I have on in Colorado that only freezes coil in July and August which are by far the most humid months here. The door is opened every 2 minutes as they are in and out constantly. Had curtains but they dont like them and take them down. They use it like its an air conditioner for 10hrs a day for 2 months. Also can't give condenser coil good cleaning as beehives are kept on roof. They also store food uncovered from previous day. Once September gets here there will be no more frozen coil. Once temp goes up from being opened so much it struggles to recover without freezing coil. Giving customer option of replacing thermostat wit KE2 which will let me set defrost in box. It will still struggle though due to door being opened 30 times an hour which is why they hate the curtains.
@mr.invisible3770
@mr.invisible3770 5 месяцев назад
Ditch the contract
@HughesManHVAC
@HughesManHVAC 3 года назад
Great vid Rick! Keep em coming
@HVACRSurvival
@HVACRSurvival 3 года назад
Thanks bud 👍👍I have a bunch of them that I didn't want to use and this is one of them. I recorded this back in July, I'm just going to start releasing them and see how they go. Not every one of them is going to be a masterpiece I guess 🙈
@HughesManHVAC
@HughesManHVAC 3 года назад
@@HVACRSurvival I enjoyed seeing your process.
@joemorales9093
@joemorales9093 3 года назад
Yeah....sometimes it's something suttle.....like the time clock maybe getting hung up....
@HVACRSurvival
@HVACRSurvival 3 года назад
I ran this call in July of this year, I haven't had to go back yet so I must have gotten it. Thanks 4 watching!
@Blazen.g
@Blazen.g 3 года назад
Love the video
@HVACRSurvival
@HVACRSurvival 3 года назад
Thanks Chase, I appreciate you taking the time to watch it 👍👍
@DanO181919
@DanO181919 Год назад
What is the purpose of the suction line tank, is it an accumulator? Im used to a liquid line receiver on a walk in cooler but not on the suction side. Could you explain the purpose of that. Thanks in advance!
@HVACRSurvival
@HVACRSurvival Год назад
If what you your describing is on the suction line before the compressor that's the accumulator, keeps liquid from getting to the compressor washing away the oil.
@DanO181919
@DanO181919 Год назад
Thank you for the reply. @ 3:05 in your video it’s center screen. Suction comes in to the condenser goes through a filter into the accumulator(I’m guessing). I guess what confuses me is that I don’t usually see a accumulator on a walk-in , just a liquid receiver. (On heat pumps I understand the accumulator) I guess my question is why is it I rarely see an accumulator on a walk-in cooler condenser.
@HVACRSurvival
@HVACRSurvival Год назад
@@DanO181919 some of it could have to do with it being such a short run from the evaporator to the condenser, when you trying to keep a 8 to 10 degrees superheat at the evaporator and when the condenser is really close it's hard to give the compressor the 20 - 25* superheat that the compressor manufacturer wants. Basically it's just an extra line of protection to keep the compressor from getting slugged with liquid.
@DanO181919
@DanO181919 Год назад
@@HVACRSurvival Thank you, appreciate your time. Everything I’ve learned in this trade has been on my own. I research everyday… watch videos everyday. I mostly learn from guys like you who are willing to take the time to help guys like me. Guys like you are God sent!! 🙏Thank you!!
@HVACRSurvival
@HVACRSurvival Год назад
Pick up the book "refrigeration for air conditioning technicians"you can find it used on eBay or some downloadable versions of it online. It is straight to the point without all the extra bullshit because they feel as though you already know air conditioning.
@migceloyiloceb1541
@migceloyiloceb1541 3 года назад
Good job idol
@HVACRSurvival
@HVACRSurvival 3 года назад
Thanks for watching 👍👍
@johndeerefan725
@johndeerefan725 3 года назад
Kind of weird Heatcraft system. Bohn condensing unit and Larkin evaporators.
@donnierobertson3088
@donnierobertson3088 3 года назад
Ok
@joehead1294
@joehead1294 3 года назад
Condenser fans are taching different rpm? How about the run caps ok?
@HVACRSurvival
@HVACRSurvival 3 года назад
They only looked like that on camera, in person they looked normal. Back to your question, even if the fan was going slow or stopped that wouldn't cause the evap coil to freeze.
@joehead1294
@joehead1294 3 года назад
@@HVACRSurvival Seemed like you were questioning head pressure is all. I still think the rpm of the condenser fans are different,but would it matter if they were? Probably not but maybe.
@HVACRSurvival
@HVACRSurvival 3 года назад
No.... Your correct 👍👍 There was problems with the head pressure, I didn't record any of that for whatever reason. I washed the coil out three times, twice with coil cleaner and it still was higher than it should of been. That's why I was reluctant to add any more refrigerant and drive the pressure higher.
@TechnicalLee
@TechnicalLee 3 года назад
@@HVACRSurvival I think Chris had a video on one similar to this, he cleaned the coil but the head pressure was still too high. Ended up replacing the condenser fan motors even though they looked to be running normally and that dropped the head pressure down to normal. You could maybe check the fan RPM with one of those laser tachometer things. Sometimes 200-300 RPM faster can make a huge difference.
@HVACRSurvival
@HVACRSurvival 3 года назад
I had a video earlier this summer like that, I have a rpm tachometer. Generally you only need it for blowers and setting pulleys but maybe I should have checked it. Good idea 4 next time👍👍
@throttlebottle5906
@throttlebottle5906 3 года назад
ICE ICE Baby!
@HVACRSurvival
@HVACRSurvival 3 года назад
To cold, to cold. Word to your mother 🙈🤣
@dmiestercommkitchentech3043
@dmiestercommkitchentech3043 3 года назад
Your comment about connecting the bulb to the PLASTIC drain line because of heat transfer from plastic is an insulator and because of the distance to the mounting bulb thickness of the amount of plastic the heat would need to travel will prevent any heat transfer but if you wrap the plastic pipe with a heat tape the heat radiates inward toward the water not along the length of the pipe the only reason it is not common practice is because drain pipes are typically in areas where either the bulb can be snagged on something and ripped off or it could accidentally be installed on a freezer drain line or water could get trapped in the pipe effecting the operation of the cooler due to the bulb sensing the cold water that is flowing in the pipe which could cause thermostat to short cycle causing contacts to stick case and point a contactor that chatters will either burn contacts off or stick contacts together.
@dmiestercommkitchentech3043
@dmiestercommkitchentech3043 3 года назад
Meant to say heat transfer from outside
@publicmail2
@publicmail2 3 года назад
DO most techs braze aluminum leaks with say AL822 rods, is it done on the residential side? Thx great channel.
@HVACRSurvival
@HVACRSurvival 3 года назад
I haven't had the chance to try the good aluminum rods yet, I'm working on getting some from a sponsor. We might do a repair if it's out of warranty but not if it's in warranty.
@throttlebottle5906
@throttlebottle5906 3 года назад
twisted tea, don't care for it unless you're the free supplier, then I'll drink up( cases) :)))
@HVACRSurvival
@HVACRSurvival 3 года назад
I hate tea in general. It tastes like watered down "pop" to me or "soda pop" to the rest of the general public that doesn't know what pop is. LOL welcome to the Ohio lingo. 😲😁🤣
@TH-ji1ed
@TH-ji1ed 3 года назад
Maybe issue occurred with one of the other coils and messed up the load on this evaporator
@HVACRSurvival
@HVACRSurvival 3 года назад
You might be correct? Those units have heaters on the coil but since I did this call back in July and haven't had to go back ever since, I would say we probably got it.
@prettycureforever7102
@prettycureforever7102 3 года назад
If its at 32-38° why do you need defrost when you can air defrost ?
@HVACRSurvival
@HVACRSurvival 3 года назад
This defrost clock just shuts off the condenser for the preset amount of time while the evap fans run. It's not a full-blown heated defrost on the coils. Depending on the humidity levels of where you live at you might get away with no defrost clock but around here it's the preferred method. Normally twice per 24 hours is plenty for 60 minutes each time.
@prettycureforever7102
@prettycureforever7102 3 года назад
@@HVACRSurvival so like mid Atlantic and northeast you'll find more defrost since we have more humidity and it'll cause more defrost right
@HVACRSurvival
@HVACRSurvival 3 года назад
👍👍. I'm in Ohio
@prettycureforever7102
@prettycureforever7102 3 года назад
@@HVACRSurvival baltimore. I want to get in the industry im almost done with school want to do commericail but everybody wants experience here
@HVACRSurvival
@HVACRSurvival 3 года назад
They don't have a choice around here, there's not enough of experience people around here to fill the positions. If we find someone that is willing to work and shows promise,motivation and dedication there hired.
@pepsicolachao4537
@pepsicolachao4537 3 года назад
They could’ve went with the center mount refrigeration coil.
@HVACRSurvival
@HVACRSurvival 3 года назад
You talking about a low profile coil?
@pepsicolachao4537
@pepsicolachao4537 3 года назад
@@HVACRSurvival yes
@HVACRSurvival
@HVACRSurvival 3 года назад
As you might have noticed the evaporator is older than the outside unit. Most the places I work at don't spend any more money than they need to. The moral of the story is it used to work fine then one time it froze up for no good reason and I had to figure out why. That's why I was checking all kinds of different things, since we never had to go back for that same problem again I must have been right on the defrost clock.
@primetime758
@primetime758 3 года назад
are you new ? you do realize its a drink cooler right? where the doors are open non stop and you need fast moving air? please think before you say something
@HVACRSurvival
@HVACRSurvival 3 года назад
@@primetime758 sounds like you got it all figured out 👍👍, why don't you fill me in on your hypothesis.
@royamberg9177
@royamberg9177 3 года назад
What about txv
@HVACRSurvival
@HVACRSurvival 3 года назад
My suction pressure and super heat was fine. Sometimes I forget to record everything that's why I've been holding off on this video since July.
@steveblake8766
@steveblake8766 3 года назад
#106 thumbs uP
@harrydickson4575
@harrydickson4575 3 года назад
👍👍👍
@HVACRSurvival
@HVACRSurvival 3 года назад
Thanks man 👍👍
Далее
Iced up walk in freezer
26:52
Просмотров 174 тыс.
Walk-In Cooler Warm and Compressor Is HOT
12:26
Просмотров 15 тыс.
OUR WALK IN IS TOO COLD PLEASE HURRY
17:21
Просмотров 37 тыс.
Why is the walk-in cooler icing up
44:47
Просмотров 21 тыс.
Walk in Cooler is not Cooling. Rebuilding a TXV.
17:16
WALK IN COOLER ICED UP
12:58
Просмотров 50 тыс.
WALK IN FREEZER DEFROST ISSUE
34:29
Просмотров 104 тыс.
WALK IN COOLER ICED UP
12:15
Просмотров 80 тыс.