had a walk in cooler that kept tripping out on DLL, discharge line temp, lock out, I finally replaced controller with mechanical psi switches. the old controller would have intermittent faults, because it would no longer cycle the condenser fan motors correctly.
If you would like to buy me a cup of coffee www.paypal.me/...
#hvac #refrigeration

Опубликовано:

 

10 сен 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 87   
@sherwinalvarez7365
@sherwinalvarez7365 2 года назад
Aw man this is a great video for new tech like me trying to get a grasp on the electrical aspect of refrigeration.
@sknight0391
@sknight0391 2 года назад
Damn Dave! Those are some beautiful manifolds! Too bad some RU-vidr doesn't have an awesome video on how to rebuild those? 😉👍
@gregfox785
@gregfox785 2 месяца назад
Brilliant Dave. I started working out in the field again. Got on with a school district last month and loving it. Working on this very system. I guess it's been tripping on DLT multiple times within an hour which locks it down. Super hot up on the roof obviously. If it keeps tripping I might do this to it.
@ronkurey8840
@ronkurey8840 2 года назад
Excellent fix….saved the customer money and solved the problem without going to the supply house…come on David….make more videos.
@NorCal-refrigeration
@NorCal-refrigeration 2 года назад
I’m try n
@jeffhall2958
@jeffhall2958 Год назад
I do this as well on the B.S. of the Beacon II systems. Beacon II's, pull it all out. Replace with a liquid line solenoid valve, TXV sized to the coil, and a KE2 temperature controller with "off cycle" defrost control. Get rid of the Electronic expansion valve and transducer, as well as the temperature sensor on the suction side. They "say" they've reduced the components, when they have actually increased them. I agree with Dave on the Emerson shite as well, get rid of the over hyped electronic controls and go with "old fashioned" mechanical controls, not transducers. Bring it back to a mechanical systems, as it is. No more failures, no more faults. And, it actually works for years opposed to months with the electronics. Use what works, not what is newly tested,. Make your customers happy and gracious that you actually fixed the problems. The "old stuff" works better than the new shite.
@scottk0623
@scottk0623 2 года назад
Love it , old school controls and “ leak lock” on the threads. I was already arrested by the “ Flare Police” for doing that. I like to use a manual reset high head switch if possible. Nice job Dave 👍
@OcRefrig
@OcRefrig 2 года назад
Yea, Manual Re-set High press. is My go to too ! Too many times i see auto re-sets where the compressor short cycled it self to death 💀. anyway. if it has a Manual Re-set , Customer calls , units down , usually a dead Cond. fan motor , Replace fan motor, hit re-set and everybody's happy ! Auto Re-set = Big bill for Very unhappy customer. Longer Down time too. More Product Loss , Bigger Bill never a good way to go if possible.
@NorCal-refrigeration
@NorCal-refrigeration 2 года назад
That high head switch is OEM. GOOD enough for me. 🤘⚡️🤘
@OcRefrig
@OcRefrig 2 года назад
@@NorCal-refrigeration yea , i wonder if the oem high press port has a schraeder in it ? IF it does , it would be a easy change out. id do it with nor cals way of doing this changeover. if not , i would just leave oem h. p. probably.
@NorCal-refrigeration
@NorCal-refrigeration 2 года назад
@@OcRefrig soldered in
@throttlebottle5906
@throttlebottle5906 2 года назад
🚨🚨🚨 🤣
@davejohnsonnola1536
@davejohnsonnola1536 2 года назад
Haven't seen that much blue goo since the last time Jim Pettinato dropped a video. OG style analogs and all, just the right groove with that golden moldy wooden walk in! ¡Props to you mate!
@repairdays9814
@repairdays9814 2 года назад
I use your Super Tech song as a ringtone for the super techs I work with. I do hot side. Just starting my channel. It needs a lot of work.
@mikecastillo5941
@mikecastillo5941 2 года назад
You are an OG HVAC-R youtuber! Been subscribed since 2015 I think 🤙🏽
@glennsepelak5113
@glennsepelak5113 Год назад
Nice job, Funny I have the same cresent wrench made by channel lock because it is very narrow at the head. Same drill also.
@philltafolla
@philltafolla 2 года назад
Thats a happy Box . Leak lock works great , Good stuff NorCal . 😃
@JStorysuoertech
@JStorysuoertech 2 года назад
I have so much to learn when it comes to walk in boxes. We never had many calls on walk ins, but as our company grows, the calls are coming in. Great video Dave, keep up the good work.
@thomasmann3560
@thomasmann3560 Год назад
Don't do this repair. This is a bypass, not a repair
@josemartinez-jt6tw
@josemartinez-jt6tw 11 месяцев назад
Wat do u work on alot
@JStorysuoertech
@JStorysuoertech 11 месяцев назад
@josemartinez-jt6tw we do the hot and cold side of any restaurant . The calls has gone up more on the hot side, but reach ins, beer coolers, and definitely ice machines are daily.
@Randylazz
@Randylazz 2 года назад
Great Educational Video I service a handful of those same exact condensing units thanks for the tips = )
@garywarren5800
@garywarren5800 2 года назад
Love that little Milwaukee impact
@sknight0391
@sknight0391 2 года назад
It might have worked just a little bit better if you would have switched it over to circus peanut relays. 😁👌 #YourTheManDave
@johnbell6956
@johnbell6956 2 года назад
Nice video. I have done the same alteration a number of times. Works great. In my area would have gone with 150-225 fan cycling.
@OcRefrig
@OcRefrig 2 года назад
for a 134a unit - yea , u go with a 150-225. for 407c , r-22 , 448a , 404 etc. u go with what dave used here. u go by Refrigerant , not area.
@johnbell6956
@johnbell6956 2 года назад
You must be in California with Dave. Here it can vary +95f to -20f. On 404A dual fan condensers with no flooded head pressure control, I want the second fan on at 225f in the summer to keep the liquid temp at 80-90f leaving the condenser.
@Eddy63
@Eddy63 2 года назад
Tippy never disappoints does she Super Dave ... She's always tipped over ... Good vid ...
@Wdog84
@Wdog84 2 года назад
That was a great little video, love being able to take something from electrical to old school and have it running sweet. A young guy started with us and used the viper nylog on everything, been using that lately as a bit of re assurance lol
@gene-khvacr
@gene-khvacr 2 года назад
Another great vid 👍🏻👍🏻👍🏻💦
@goldhammer561
@goldhammer561 2 года назад
Wow Dave great content
@jamierushing8811
@jamierushing8811 2 года назад
Hi bro from west Alabama ty for your show peace love
@danwittels5542
@danwittels5542 2 года назад
Simpler is usually better. Nice video!
@jayxiao3
@jayxiao3 2 года назад
Fun staff~ nice video NorCal Dave.
@cesservicedepartment3609
@cesservicedepartment3609 2 года назад
Good job Dave, hope to see more of your pro videos.
@thesilentonevictor
@thesilentonevictor 2 года назад
Great job Dave on this one you made her ran smooth 😆
@davidharmon8745
@davidharmon8745 2 года назад
Thank you for the videos. Keep them coming
@HVACRDUDE
@HVACRDUDE 2 года назад
MY FAVOOOOOOOORITE REPAIR!
@crayfen082
@crayfen082 2 года назад
love the rebuild and fresh analogs bub!! thnx for your vids!!
@harrydickson4575
@harrydickson4575 2 года назад
👍👍👍
@NorCal-refrigeration
@NorCal-refrigeration 2 года назад
🤘⚡️🤘
@IFIXCASTLES
@IFIXCASTLES 2 года назад
Yup good job!
@anthonywoolf9087
@anthonywoolf9087 2 года назад
But look at the fancy rebuilt Guages nice video.
@theduffster2581
@theduffster2581 2 года назад
Love that retrofit 👍🏻 those digital controls suck 👍🏻
@gregbowman3598
@gregbowman3598 2 года назад
Nice job Dave 👍
@jakem117
@jakem117 2 года назад
I've had issues with those. Referring to the high discharge temperature thermistor when a freezer is doing a hot pull down. Sometimes the condensing unit is slightly undersized by the installer. So when I run into that I just quote to go mechanical or for the mentioned issue I put the discharge sensor on the liquid line lol
@phil955i
@phil955i 2 года назад
Good call on your method of curing the intermittent fault, but I'm sorry to say mate that those bullet type (as you call them) pressure switches I find are quite unreliable, they don't seem to be able to handle constant operations in an LP pump down situation (I've never used a fan cycling one though, they may be better). They seem to last a year to 18 months tops. Although saying that maybe that's long enough until the next callout ;-)
@NorCal-refrigeration
@NorCal-refrigeration 2 года назад
We’ve had great luck with em. They even come oem on units.
@phil955i
@phil955i 2 года назад
@@NorCal-refrigeration yeah they come on oem units here in the UK too, that's where I've experienced the suspect longevity
@garywarren5800
@garywarren5800 2 года назад
Really like watching you work, very cool dude. BTW , I teach Scuba Diving , do you scuba also?
@NorCal-refrigeration
@NorCal-refrigeration 2 года назад
Snorkel but never scuba
@garywarren5800
@garywarren5800 2 года назад
@@NorCal-refrigeration same love for the water , thanks for your videos bro , really like to watch you work.
@arotechmechanicalhvacr1158
@arotechmechanicalhvacr1158 2 года назад
Damn Dave blue death? Nice job but when that leak lock dries good luck getting any of that off in the future if one of those switches fails..
@realestateservicessaleshea99
@realestateservicessaleshea99 2 года назад
Thanks again for the videos! 🥃🥃🍺🍺🍺🎯🍿 Stay safe. Retired (werk'n)keyboard super tech. Wear your safety glasses!
@Freonleon
@Freonleon 2 года назад
Dave got the trap beats going threw the video
@NorCal-refrigeration
@NorCal-refrigeration 2 года назад
I had to subscribe to music 🎶 service RU-vid was coming hard for the copyright
@davejohnsonnola1536
@davejohnsonnola1536 10 месяцев назад
A "golden moldy"!
@sykotictendencies6032
@sykotictendencies6032 Год назад
Good job tippins haha
@FrostHVAC
@FrostHVAC 2 года назад
Some old Master Bilt condensers do the same set up you did, and I like those preferably better because it's super simple lol. I've worked on quite a bit of those Emerson Condensers, never had the issues ya mentioned. Did ya replace the controller? I've seen them go finnecky before, great video as always dave
@kingrum5147
@kingrum5147 2 года назад
Hello Dave. Do we know each other don't know. I've been doing commercial in the Bay Area since 93. I Enjoy watching your videos. I'm the last one of a group of people I worked with who have passed on. I tried a procedure on a Hoshizaki I saw you repair on a bigger unit. Turned out great 👍
@stephwaylonwells3218
@stephwaylonwells3218 2 года назад
👍
@billyfield8984
@billyfield8984 2 года назад
Is sir Lawrence sandwiche prep table ($2300) comparable to true ? 48 in prep table in true cost $4300,Traulsen is 5k,centerline by traulsen cost 3340.which one would you buy for your food truck
@NorCal-refrigeration
@NorCal-refrigeration 2 года назад
Can you get it in n out for service?
@billyfield8984
@billyfield8984 2 года назад
@@NorCal-refrigeration YES ! easily
@NorCal-refrigeration
@NorCal-refrigeration 2 года назад
@@billyfield8984 good. The Traulsen has been the best, true has been good, the 2300 one no idea.
@kevinpoore5626
@kevinpoore5626 2 года назад
Yay I'm number one in comments well happy Sunday to everybody
@billj4859
@billj4859 2 года назад
If that unit goes low on gas or gets a plugged condenser what keeps the comoressor from short cycling on the safeties?
@NorCal-refrigeration
@NorCal-refrigeration 2 года назад
Customer when beer is warm.
@DanO181919
@DanO181919 2 года назад
@@NorCal-refrigeration 😂
@richardboyle3142
@richardboyle3142 2 года назад
Absolutely 🍺🍹🍺🍷🍺 There is no better alarm in the world then a empty Mug!
@DanO181919
@DanO181919 2 года назад
At the end of the video I didn’t see any cargo ships offshore.
@NorCal-refrigeration
@NorCal-refrigeration 2 года назад
No toys this Christmas
@juliochavezunacosa4147
@juliochavezunacosa4147 2 года назад
how cold is the water?
@NorCal-refrigeration
@NorCal-refrigeration 2 года назад
58-56 F
@georgen.8027
@georgen.8027 2 года назад
Is that the neighborhood grocery store where you demonstrated fan cycling with a piece of cardboard? And now it's going mechanical lol Is Biden running Emerson?
@kingofthecrease30
@kingofthecrease30 2 года назад
these digital controls & sensors on all this new equipment is just 💩 and fails constantly....the old mechanical controls have worked for years and it the way to go.
@NorCal-refrigeration
@NorCal-refrigeration 2 года назад
Right on the King 👑 I’m glad you feel this way to.
@shifter8207
@shifter8207 2 года назад
Made the big number poo
@lifeproject9182
@lifeproject9182 2 года назад
407c 20psi=1*F and 5psi= -22 seems to low for a walk-in cooler. But I am new to this
@NorCal-refrigeration
@NorCal-refrigeration 2 года назад
It’s on pump down.
@OcRefrig
@OcRefrig 2 года назад
Good video ! Nice & easy conversion doing it that way. should be pretty reliable too. should get 5-6 years out of those peanuts at least. How old was that Emerson control that took a Dumper ?
@NorCal-refrigeration
@NorCal-refrigeration 2 года назад
2016
@OcRefrig
@OcRefrig 2 года назад
@@NorCal-refrigeration 5 years is about the life of everything these days. 🤦‍♂️.
Далее
Basic walk in freezer wiring
11:16
Просмотров 68 тыс.
Walk In Freezer Isn't Getting Cold Enough
12:09
Просмотров 41 тыс.
iPhone 16 - презентация Apple 2024
01:00
Просмотров 62 тыс.
Basic walk in box control wiring
12:30
Просмотров 58 тыс.
Walk in freezer warm
12:41
Просмотров 44 тыс.
Walk in Cooler low pressure control problems
11:07
Просмотров 119 тыс.
Refrigeration: Low Pressure Control As Temp Control
25:22
WALK IN FREEZER SUPERHEAT TOO LOW
17:15
Просмотров 117 тыс.
WALK IN COOLER BASIC TROUBLESHOOTING SEQUENCE
7:07
Просмотров 34 тыс.
How a Headmaster valve works
8:35
Просмотров 32 тыс.
iPhone 16 - презентация Apple 2024
01:00
Просмотров 62 тыс.