Why Neutrals & Grounds are Connected in 90 Seconds 

Benjamin Sahlstrom
Подписаться 434 тыс.
Просмотров 15 тыс.
50% 1

Full Video Here: • Why Neutrals & Grounds...
NEC Codebook Hardcover (50% discount as of posting): amzn.to/3CvdgGG
My Favorite Tool: amzn.to/3NIFJuO
Tools We Recommend: amzn.to/3Cssuwh
In this 90 second video we go over why it is not just permitted, but required to bond your neutrals and grounds in your main panel (more correctly, your first disconnect means).
Keep in mind that there's only so much that we could fit into 90 seconds, so please watch the full video to learn a lot more about bonding neutrals and grounds. WARNING: in some circumstances it is not allowed to bond neutrals with grounds, and I cover that in detail in the full video. You can watch that here: • Why Neutrals & Grounds...
Thanks for watching and subscribing! As an Amazon affiliate I earn from qualifying purchases. Thank you for your support!
Was this video helpful to you? Send a tip:www.paypal.me/bensahlstrom
Become a Patron: / bensahlstrom

Опубликовано:

 

1 окт 2023

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 37   
@spelunkerd
@spelunkerd 9 месяцев назад
The concepts are laughably simple, it's the strange jargon (like "grounding conductor" vs "grounded conductor") that trips people up. Bright people, like Ben, find a way to explain it easily, avoiding confusing descriptive terms.
@spankymagee
@spankymagee 9 месяцев назад
I recommend everyone watch the full video. It explains a lot for even people like me that already knew quite a bit about this stuff. Ties it all together and makes a lot of sense. I learned a couple of things NOT to do as well in that video.
@mfsperring
@mfsperring 9 месяцев назад
🤣 I was thinking this looks familiar but I remembered it differently. Then I read your comment and realized I had watched the original. Maybe I did hang on to that live wire a little longer then I thought. 🤣🤣🤣
@dunckeroo1987
@dunckeroo1987 9 месяцев назад
Circuit ground, case ground, power ground, panel ground, earth ground -- it is a hierarchy of grounding for safety and electrical noise reduction. Normally the ground is not supposed to carry current -- but will do so if leakage happens to occur. It is a back-up system to avoid electrocution and fire -- independent of the voltage drop of the neutral conductors.
@georgeswindolljr1980
@georgeswindolljr1980 9 месяцев назад
Excellent summary!!!
@martysheets6882
@martysheets6882 9 месяцев назад
Great explanation, thanks for making it simple.
@zekenzy6486
@zekenzy6486 9 месяцев назад
Great Video. Thank you for sharing
@stevenhansen5453
@stevenhansen5453 9 месяцев назад
Awesome explanation.
@theastuteangler
@theastuteangler 9 месяцев назад
Quick, simple, straight to the point. I like it.
@2011k1500
@2011k1500 9 месяцев назад
Good job. A lot packed in 90 seconds.
@imevbore
@imevbore 8 месяцев назад
How do I bond three tenant apartments with individual meter boards? Please, I need a detailed explanation
@Soprano0913
@Soprano0913 4 месяца назад
I love your videos! You guys are great! I need your professional knowledge on my panel. I have a 100amp 20 circuit General Electric 1960 era. I'm out of neutrals i want to add a type 1 surge protector. Is it code to add a neutral bar and a bumper wire from old to new? Also does the addon neutral bar need to be isolated the original? Lastly no ground bar can i just simply screw one into the panel?
@rangerBlu
@rangerBlu 9 месяцев назад
Beginning at around 45s: "Connecting something to the dirt does not make a system safe in any way." I strongly disagree with this statement. The most basic reason for grounding is to make sure that any conducting materials that might be handled by people are at the same potential as those people. The assumption is that people stand on the ground hence they are typically at ground potential. Grounding of conductors (e.g. metal equipment boxes, copper pipes, solar panels, etc.) protects people by shunting stray voltages that build up on those conductors, by natural or other means (e.g. electric faults), into ground keeping them at ground potential and preventing electric shock when touched.
@nayemhossain4283
@nayemhossain4283 9 месяцев назад
Thanks for your time and sacrifice, Is it possible to make a video gas tankless combi boiler wiring , Thanks again .
@BenjaminSahlstrom
@BenjaminSahlstrom 9 месяцев назад
On just the wiring specifically?
@jfbeam
@jfbeam 9 месяцев назад
Lightning hits ungrounded things everyday without any damage. (airplanes, and sometimes even cars) When it hits your shed, that's connected to your _grounded_ house, then yes, it'll blow things up in your house.
@christfollower1768
@christfollower1768 8 месяцев назад
Question : Can I use a gfci 2 pole breaker with 12/2 with bare ground wire and that gfci breaker work as intended ? Fyi the device connected to does not require a neutral wire. Thank you
@robertmeyer4744
@robertmeyer4744 9 месяцев назад
that was good. now this bounding is at one point only at the main ! all comes together with 1 or 2 ground rods. not just lightning also for static charge build up. like heave rain or snow can build up a charge that can shock you or arc trying to make it to earth.
@jimmywh22
@jimmywh22 7 месяцев назад
Kind of based of this topic so I thought I would see if anyone has a definitive answer… So I have a main panel with shared ground and neutrals on the neutral bars. Yes, it is the first means of disconnect so I know that is fine. The issue is the neutrals aren’t all under one screw. Can I add a separate ground bar to move some of the grounds over to in order to make it to code? Unfortunately the electrician installing the panel many years ago didn’t leave a ton of slack so I only plan on moving the bare minimum of grounds over to free up enough space. Logically, I don’t see any issues having some grounds on the neutral bar and some on a bonded separate ground bar provided there is never a neutral on that ground bar. But I know the NEC can have some weird rules and just wanted to see if anyone knows if it’s an all or nothing type deal with moving the grounds?
@americanmotorsam-caz524
@americanmotorsam-caz524 8 месяцев назад
OK so my water service was just updated last year and the electrician bonded the meter and service to my neutral bar. Was this correct I do have a separate ground bar in my panel. While he was leaving he said I needed to have a ground bar installed in my panel. I just opened it up again after watching this video and maybe because 2 grounds were run into the neutral and my ground wire to outside is still cloth wrapped as the house is 170 yrs old. I did think this strange. I may just pull a new copper 6g wire and drive 2 new rods and put to ground bar. My breaker box conduit input is bonded at the nut and to the neutral, is this normal or should it be to ground bar. I have ordered 10 space ground bar to get those 2 wires into the frame of box. *** I did post this on old video but realize it was older so you may not see.
@grayeagle247
@grayeagle247 6 месяцев назад
Maybe someone can answer this question for me. I have bought some property and the main panel first disconnect is separated, the ground and the neutral, my sub panel. The sub panel is connecting neutral and ground and everything test is good. Is that OK
@hippo-potamus
@hippo-potamus 9 месяцев назад
12/2 Stranded vs 12/2 solid?
@minergate4066
@minergate4066 9 месяцев назад
I still don't know
@jakubmakalowski6428
@jakubmakalowski6428 9 месяцев назад
Definitely misread the title as connecting both within 90 sec, not an explanation in the span of 90 sec haha!
@electricsuitbatman
@electricsuitbatman 9 месяцев назад
😂 I read this title like he was bragging about taking 90 seconds to land 2 wires. 😂😂 Cheers to being too literal.
@electricsuitbatman
@electricsuitbatman 9 месяцев назад
Disregarding the fact he said why too 😂
@slidewaze
@slidewaze 9 месяцев назад
Good subject but the jump-cuts.....
@BenjaminSahlstrom
@BenjaminSahlstrom 9 месяцев назад
I get ya...
@slidewaze
@slidewaze 9 месяцев назад
@@BenjaminSahlstrom Oh! This was pieced together from the original video? In that case, jump-cuts forgiven. That must have been a tough edit. Nice and thanks!
@JohnSmith-kw8lt
@JohnSmith-kw8lt 9 месяцев назад
Since AC (Alternating Current) is reversing polarity 60 times a second that means that when neutral is connected to the ground you are shooting Hot or Positive directly into the ground 50% of the time or paying for electricity that you are not using.
@timg6850
@timg6850 9 месяцев назад
The Neutral by being connected to the Ground Bar (Earth) is at 0 Volts (Earth potential) so will not carry Power its just the current return when using a single phase circuit.
@jkbrown5496
@jkbrown5496 9 месяцев назад
But only if there is a failure or open in the combined earth-neutral wire in the power company's drop to the house. Otherwise, the potential difference between the ground rod at the house and the one at the pole is negligible. But if that Earth-neutral is broken, then there is a resistance path through the earth that will cap the voltage spike, especially for induced currents from nearby lightning. Strictly speaking you do not bond the ground and centertap/neutral at the first panel, but rather separate the combined earth/neutral the power company gives you at the service drop from the transformer. By separating this CEN, you are creating the neutral and safety ground separation that keeps things people can touch safe.
@mak4374
@mak4374 8 месяцев назад
Maybe "the first thing you want" is not to do the skip-video bullshit on ANYTHING that has to do with safety, just to "look" cool. It is NOT cool. It is just destructing, annoying, and makes people want to skip IMPORTANT information. I like your information, just, please, present it in a cohesive way...
@MAGAMAN
@MAGAMAN 9 месяцев назад
Instead of chopping the hell out of the video to hit 90 seconds and making it unwatchable in the process, why not just put it up in a normal pacing? We aren't on Tik tok with all the tik tok losers and have an attention span that goes over a minute or two.
@BenjaminSahlstrom
@BenjaminSahlstrom 9 месяцев назад
Good point! That's why the full video is linked at the end.
@stusue9733
@stusue9733 9 месяцев назад
@@BenjaminSahlstrom Perhaps he didn't make it that far? lol
Далее
Why Neutrals & Grounds are Connected in a Main Panel
20:13
Why Neutrals and Grounds are Separated in a Sub Panel
17:46
How to Wire an Electrical Panel - Good Workmanship
27:38
What is Ground? Earth Ground/Earthing
9:27
Просмотров 3,2 млн
Where Does Grounded Electricity Actually Go?
19:36